Baytech-MIB-403-1
- Namespace
- baytech
- Source file
Baytech-MIB-403-1- Digest
sha256:eaf324ed0f0cf1c88efce14981631e3aa6036e339153caea70395454aa27d732
Imports
| From | Symbols |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | Gauge32, IpAddress, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, TimeTicks, enterprises, iso |
| SNMPv2-TC | DisplayString, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
Baytech-MIB-403-1 SNMPv2-CONF SNMPv2-SMI SNMPv2-TC
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| baytech OBJECT-IDENTITY | 1.3.6.1.4.1.4779 | |||
| btadevices OBJECT-IDENTITY | 1.3.6.1.4.1.4779.1 | |||
| sBTAIdent OBJECT-IDENTITY | 1.3.6.1.4.1.4779.1.1 | |||
| sBTAIdentFirmwareRev OBJECT-TYPE An 8 byte ID string identifying the DS72 firmware revision. This value is set at the factory. | 1.3.6.1.4.1.4779.1.1.1 | DisplayString | read-only | mandatory |
| sBTAIdentSerialNumber OBJECT-TYPE A number identifying the serial number of the DS72. This value is set at the factory. | 1.3.6.1.4.1.4779.1.1.2 | INTEGER | read-only | mandatory |
| sBTAIdentUnitName OBJECT-TYPE A 64-character string identifying the name (UnitID) of the DS72. This value is set at the factory to a default of DS72. | 1.3.6.1.4.1.4779.1.1.3 | DisplayString (SIZE(64)) | read-write | mandatory |
| sBTANetworkConfig OBJECT-IDENTITY | 1.3.6.1.4.1.4779.1.2 | |||
| sBTANetworkConfigBootpEnable OBJECT-TYPE Enables/disables bootp. Bootp will not take effect until the unit is reseted. | 1.3.6.1.4.1.4779.1.2.1 | INTEGER {disabled(0), enabled(1)} | read-write | mandatory |
| sBTANetworkConfigDHCPEnable OBJECT-TYPE Enables/disables DHCP. DHCP will not take effect until the unit is reseted. | 1.3.6.1.4.1.4779.1.2.2 | INTEGER {disabled(0), enabled(1)} | read-write | mandatory |
| sBTANetworkConfigSSHEnable OBJECT-TYPE Enables/disables SSH logins. Disable/enable SSH will take effect after the unit is reseted. | 1.3.6.1.4.1.4779.1.2.3 | INTEGER {disabled(0), enabled(1)} | read-write | mandatory |
| sBTANetworkConfigTelnetEnable OBJECT-TYPE Enables/disables telnet. | 1.3.6.1.4.1.4779.1.2.4 | INTEGER {disabled(0), enabled(1)} | read-write | mandatory |
| sBTANetworkConfigActivityTimeout OBJECT-TYPE A value from 0 to 120. 0 disables activity timeouts. Value represents minutes of non-activity before telnet / SSH sessions are automatically logged out. Default is 0. | 1.3.6.1.4.1.4779.1.2.5 | INTEGER | read-write | mandatory |
| sBTANetworkConfigDirectConnEnable OBJECT-TYPE Enables/disables direct port connection upon login. | 1.3.6.1.4.1.4779.1.2.6 | INTEGER {disabled(0), enabled(1)} | read-write | mandatory |
| sBTANetworkConfigSNMP OBJECT-IDENTITY | 1.3.6.1.4.1.4779.1.2.8 | |||
| sBTANetworkConfigSNMPReadOnlyCommunity OBJECT-TYPE The community name to use for read only access. Maximum len 16 bytes. | 1.3.6.1.4.1.4779.1.2.8.1 | DisplayString | read-write | mandatory |
| sBTANetworkConfigSNMPReadWriteCommunity OBJECT-TYPE The community name to use for read-write access. Maximum len 16 bytes. | 1.3.6.1.4.1.4779.1.2.8.2 | DisplayString | read-write | mandatory |
| sBTANetworkConfigSNMPNumTrapReceivers OBJECT-TYPE The maximum number of managers to send traps to. Currently 4. | 1.3.6.1.4.1.4779.1.2.8.3 | INTEGER | read-only | mandatory |
| sBTANetworkConfigSNMPTrapReceiverTable OBJECT-TYPE A list of managers to send traps to. The number of entries is given by the value of sBTANetworkConfigSNMPNumTrapReceivers. Maximum number of Trap Receivers is four. | 1.3.6.1.4.1.4779.1.2.8.4 | not-accessible | mandatory | |
| sBTANetworkConfigSNMPTrapReceiverEntry OBJECT-TYPE Table of managers to send traps to. | 1.3.6.1.4.1.4779.1.2.8.4.1 | not-accessible | mandatory | |
| trapIndex OBJECT-TYPE The index to a trap receiver entry. | 1.3.6.1.4.1.4779.1.2.8.4.1.1 | INTEGER | read-only | mandatory |
| receiverAddress OBJECT-TYPE The IP address of the manager to send traps to. | 1.3.6.1.4.1.4779.1.2.8.4.1.2 | IpAddress | read-write | mandatory |
| sBTANetworkConfigRadius OBJECT-IDENTITY | 1.3.6.1.4.1.4779.1.2.9 | |||
| sBTANetworkConfigRadiusEnable OBJECT-TYPE Enables / disables RADIUS telnet logins. | 1.3.6.1.4.1.4779.1.2.9.1 | INTEGER {disable(0), enable(1)} | read-write | mandatory |
| sBTANetworkConfigRadiusPrimaryServer OBJECT-TYPE Ip address of the primary RADIUS server. | 1.3.6.1.4.1.4779.1.2.9.2 | IpAddress | read-write | mandatory |
| sBTANetworkConfigRadiusSecondaryServer OBJECT-TYPE Ip address of the back-up RADIUS server. | 1.3.6.1.4.1.4779.1.2.9.3 | IpAddress | read-write | mandatory |
| sBTANetworkConfigRadiusLocalLogin OBJECT-TYPE Enables / disables the use of local (usernames stored in the DS72) logins in the case that both the primary and secondary RADIUS server are not available. | 1.3.6.1.4.1.4779.1.2.9.4 | INTEGER {disable(0), enable(1)} | read-write | mandatory |
| sBTANetworkConfigWEB OBJECT-IDENTITY | 1.3.6.1.4.1.4779.1.2.10 | |||
| sBTANetworkConfigWebEnable OBJECT-TYPE Enables WEB. | 1.3.6.1.4.1.4779.1.2.10.1 | INTEGER {disabled(0), enabled(1)} | read-write | mandatory |
| sBTANetworkConfigWebSecureEnable OBJECT-TYPE Enables WEB Security. | 1.3.6.1.4.1.4779.1.2.10.2 | INTEGER {disabled(0), enabled(1)} | read-write | mandatory |
| sBTANetworkConfigWebLoginEnable OBJECT-TYPE Enables WEB Login. | 1.3.6.1.4.1.4779.1.2.10.3 | INTEGER {disabled(0), enabled(1)} | read-write | mandatory |
| sBTANetworkConfigWebActivityTimeout OBJECT-TYPE A value from 0 to 120. 0 disables WEB activity timeouts. Value represents minutes of non-activity before WEB sessions are automatically logged out. Default is 0. | 1.3.6.1.4.1.4779.1.2.10.4 | INTEGER | read-write | mandatory |
| sBTAModules OBJECT-IDENTITY | 1.3.6.1.4.1.4779.1.3 | |||
| sBTAModulesNumberOfModules OBJECT-TYPE Number of modules installed into the DS unit. | 1.3.6.1.4.1.4779.1.3.1 | INTEGER | read-only | mandatory |
| sBTAModulesModulesInstalled OBJECT-TYPE A character string listing the modules installed seperated by commas. Each module is identifed by a two digit number indicating the slot. For example 02,03,04,06 means modules 2,3,4 and 6 are installed. | 1.3.6.1.4.1.4779.1.3.2 | DisplayString | read-only | mandatory |
| sBTAModulesResetModulesCmd OBJECT-TYPE This command is no longer supported. | 1.3.6.1.4.1.4779.1.3.3 | INTEGER | read-only | deprecated |
| sBTAModulesNumberOfIntelligentModules OBJECT-TYPE The number of Intelligent Modules installed in the DS Unit. | 1.3.6.1.4.1.4779.1.3.4 | INTEGER | read-only | mandatory |
| sBTAModulesRPC OBJECT-IDENTITY | 1.3.6.1.4.1.4779.1.3.5 | |||
| sBTAModulesNumberOfRPCModules OBJECT-TYPE The number of DS30 Modules installed in the DS Unit. | 1.3.6.1.4.1.4779.1.3.5.1 | INTEGER | read-only | mandatory |
| sBTAModulesRPCTable OBJECT-TYPE Allows for control of individual outlets and individual RPC modules. | 1.3.6.1.4.1.4779.1.3.5.2 | not-accessible | mandatory | |
| sBTAModulesRPCEntry OBJECT-TYPE The RPCs to control and get status on. | 1.3.6.1.4.1.4779.1.3.5.2.1 | not-accessible | mandatory | |
| sBTAModulesRPCIndex OBJECT-TYPE The index into the RPC table. Indexes for rpcs attached to ds74 modules are calculate with the following formula: ((module - 2) * 4) + port. For example module 3 port 1 = index 5. | 1.3.6.1.4.1.4779.1.3.5.2.1.1 | INTEGER | read-only | mandatory |
| sBTAModulesRPCName OBJECT-TYPE The name (unit id) of the rpc. | 1.3.6.1.4.1.4779.1.3.5.2.1.2 | DisplayString | read-write | mandatory |
| sBTAModulesRPCFirmwareVersion OBJECT-TYPE The firware version of the rpc. | 1.3.6.1.4.1.4779.1.3.5.2.1.3 | DisplayString | read-only | mandatory |
| sBTAModulesRPCCurrent OBJECT-TYPE The current reading for the power strip. If current measurement is not installed this value will always read 0. | 1.3.6.1.4.1.4779.1.3.5.2.1.4 | INTEGER | read-only | mandatory |
| sBTAModulesRPCMaxCurrent OBJECT-TYPE The maximum detected current reading for the power strip. If current measurement is not installed this value will always read 0. Setting this value to 0 will clear the maximum current detected. | 1.3.6.1.4.1.4779.1.3.5.2.1.5 | INTEGER | read-write | mandatory |
| sBTAModulesRPCVoltage OBJECT-TYPE The voltage reading for the power strip. If voltage measurement is not installed this value will always read 0. | 1.3.6.1.4.1.4779.1.3.5.2.1.6 | INTEGER | read-only | mandatory |
| sBTAModulesRPCPower OBJECT-TYPE The power reading for the power strip. If power measurement is not installed this value will always read 0. | 1.3.6.1.4.1.4779.1.3.5.2.1.7 | INTEGER | read-only | mandatory |
| sBTAModulesRPCTemperature OBJECT-TYPE The temperature reading for the power strip. Readings are in degrees C. If temperature measurement is not installed this value will always read 0. | 1.3.6.1.4.1.4779.1.3.5.2.1.8 | INTEGER | read-only | mandatory |
| sBTAModulesRPCRebootTimeout OBJECT-TYPE The length of off time for automatic reboot sequences. Currently a read-only value set to the fixed reboot timeout. | 1.3.6.1.4.1.4779.1.3.5.2.1.9 | INTEGER | read-only | mandatory |
| sBTAModulesRPCAllOutletsCmd OBJECT-TYPE Turns all outlets on, off or reboot. 0 = off 1 = on 2 = reboot A get will return unknown (6). | 1.3.6.1.4.1.4779.1.3.5.2.1.10 | INTEGER {off(0), on(1), reboot(2), lockon(3), lockoff(4), unlock(5), unknown(6)} | read-write | mandatory |
| sBTAModulesRPCAllOutletsStatus OBJECT-TYPE Reports status of outlets in a comma deliminated string. 0 = off 1 = on 2 = reboot 3 = locked on 4 = locked off | 1.3.6.1.4.1.4779.1.3.5.2.1.11 | DisplayString | read-only | mandatory |
| sBTAModulesRPCCurrentAlarmThreshold OBJECT-TYPE The current alarm threshold level *10. A value of 105 will set the level to 10.5. | 1.3.6.1.4.1.4779.1.3.5.2.1.12 | INTEGER | read-write | mandatory |
| sBTAModulesRPCOverVoltageThreshold OBJECT-TYPE The over voltage alarm threshold level *10. A value of 105 will set the level to 10.5. | 1.3.6.1.4.1.4779.1.3.5.2.1.13 | INTEGER | read-write | mandatory |
| sBTAModulesRPCUnderVoltageThreshold OBJECT-TYPE The under voltage alarm threshold level *10. A value of 105 will set the level to 10.5. | 1.3.6.1.4.1.4779.1.3.5.2.1.14 | INTEGER | read-write | mandatory |
| sBTAModulesRPCNumberOfOutlets OBJECT-TYPE Number of outlets for this RPC. This will be the size of outlet table for this RPC index. | 1.3.6.1.4.1.4779.1.3.5.2.1.15 | INTEGER | read-only | mandatory |
| sBTAModulesRPCCircuitBreaker OBJECT-TYPE Status of circuit breaker in power strip. 0=off 1=on. | 1.3.6.1.4.1.4779.1.3.5.2.1.16 | INTEGER {off(0), on(1)} | read-only | mandatory |
| sBTAModulesRPCOverTempThreshold OBJECT-TYPE The over temperature alarm threshold level *10. A value of 505 will set the level to 50.5. | 1.3.6.1.4.1.4779.1.3.5.2.1.17 | INTEGER | read-write | mandatory |
| sBTAModulesRPCUnitVA OBJECT-TYPE Total Volt-Amps for this RPC. | 1.3.6.1.4.1.4779.1.3.5.2.1.18 | INTEGER | read-only | mandatory |
| sBTAModulesRPCNumberOfBreakers OBJECT-TYPE Number of breakers for this RPC. | 1.3.6.1.4.1.4779.1.3.5.2.1.19 | INTEGER | read-only | mandatory |
| sBTAModulesRPCLowCurrentThreshold OBJECT-TYPE Low current threshold for this RPC. | 1.3.6.1.4.1.4779.1.3.5.2.1.20 | INTEGER | read-write | mandatory |
| sBTAModulesRPCVoltageSource OBJECT-TYPE Voltage source for this RPC. | 1.3.6.1.4.1.4779.1.3.5.2.1.21 | INTEGER | read-write | mandatory |
| sBTAModulesRPCSourceSwitchCount OBJECT-TYPE Count of Voltage Source Switches for this RPC. | 1.3.6.1.4.1.4779.1.3.5.2.1.22 | INTEGER | read-only | mandatory |
| sBTAModulesRPCNumberOfSensors OBJECT-TYPE Number of environmental sensors for this RPC. | 1.3.6.1.4.1.4779.1.3.5.2.1.23 | INTEGER | read-only | mandatory |
| sBTAModulesRPCType OBJECT-TYPE The type of RPC installed at the indexed location. | 1.3.6.1.4.1.4779.1.3.5.2.1.24 | DisplayString | read-only | mandatory |
| sBTAModulesRPCOutletTable OBJECT-TYPE Allows for control of individual outlets. The number of entries is contained in the sBTAModulesRPCOutletTableSize OID. | 1.3.6.1.4.1.4779.1.3.5.3 | not-accessible | mandatory | |
| sBTAModulesRPCOutletEntry OBJECT-TYPE The outlets to control and get status on. | 1.3.6.1.4.1.4779.1.3.5.3.1 | not-accessible | mandatory | |
| sBTAModulesRPCOutletModuleIndex OBJECT-TYPE The index to the outlet entry. | 1.3.6.1.4.1.4779.1.3.5.3.1.1 | INTEGER | read-only | mandatory |
| sBTAModulesRPCOutletIndex OBJECT-TYPE The index to the outlet entry. | 1.3.6.1.4.1.4779.1.3.5.3.1.2 | INTEGER | read-only | mandatory |
| sBTAModulesRPCOutletState OBJECT-TYPE Getting this variable will return the state of the outlet. Valid return states are unknown, on, off, lockon, lockoff. 0 = off 1 = on 2 = reboot 3 = lockon (outlet is on and no changes are allowed) 4 = lockoff (outlet is off and no changes are allowed) 5 = unlock. | 1.3.6.1.4.1.4779.1.3.5.3.1.3 | INTEGER {off(0), on(1), reboot(2), lockon(3), lockoff(4), unlock(5), unknown(6)} | read-write | mandatory |
| sBTAModulesRPCOutletName OBJECT-TYPE The name of the outlet. Maximum size is 16 characters. | 1.3.6.1.4.1.4779.1.3.5.3.1.4 | DisplayString | read-write | mandatory |
| sBTAModulesRPCGroupCmd OBJECT-TYPE A character string listing the outlets that need to be controlled, turned off, or turn on as a group. Command is the first character followed by a space. Valid commads are 0=off,1=on, or 2=reboot. A list follows the command in the format module.outlet. For example 2 2.1,2.12,3.1 will reboot module 2 outlet 2&12 module 3 outlet 1. | 1.3.6.1.4.1.4779.1.3.5.4 | DisplayString | read-write | mandatory |
| sBTAModulesRPCModPortTable OBJECT-TYPE Allows for control of individual outlets and individual RPC modules. The number of entries is contained in the sBTAModulesNumberOfRPCModules OID. | 1.3.6.1.4.1.4779.1.3.5.5 | not-accessible | mandatory | |
| sBTAModulesRPCModPortEntry OBJECT-TYPE The RPCs to control and get status on. | 1.3.6.1.4.1.4779.1.3.5.5.1 | not-accessible | mandatory | |
| sRPCModuleIndex OBJECT-TYPE The module number index into the RPC table. | 1.3.6.1.4.1.4779.1.3.5.5.1.1 | INTEGER | read-only | mandatory |
| sRPCPortIndex OBJECT-TYPE The port number index into the RPC table. In the case of ds30 modules this number is always 1. | 1.3.6.1.4.1.4779.1.3.5.5.1.2 | INTEGER | read-only | mandatory |
| sRPCType OBJECT-TYPE Type of RPC at the module, port index. | 1.3.6.1.4.1.4779.1.3.5.5.1.3 | DisplayString | read-only | mandatory |
| sRPCName OBJECT-TYPE The name (unit id) of the rpc module. | 1.3.6.1.4.1.4779.1.3.5.5.1.4 | DisplayString | read-write | mandatory |
| sRPCFirmwareVersion OBJECT-TYPE The firware version of the rpc module. | 1.3.6.1.4.1.4779.1.3.5.5.1.5 | DisplayString | read-only | mandatory |
| sRPCCurrent OBJECT-TYPE The current reading for the power strip. If current measurement is not installed this value will always read 0. | 1.3.6.1.4.1.4779.1.3.5.5.1.6 | INTEGER | read-only | mandatory |
| sRPCMaxCurrent OBJECT-TYPE The maximum detected current reading for the power strip. If current measurement is not installed this value will always read 0. Setting this value to 0 will clear the maximum current detected. | 1.3.6.1.4.1.4779.1.3.5.5.1.7 | INTEGER | read-write | mandatory |
| sRPCVoltage OBJECT-TYPE The voltage reading for the power strip. If voltage measurement is not installed this value will always read 0. | 1.3.6.1.4.1.4779.1.3.5.5.1.8 | INTEGER | read-only | mandatory |
| sRPCPower OBJECT-TYPE The power reading for the power strip. If power measurement is not installed this value will always read 0. | 1.3.6.1.4.1.4779.1.3.5.5.1.9 | INTEGER | read-only | mandatory |
| sRPCTemperature OBJECT-TYPE The temperature reading for the power strip. Readings are in degrees C. If temperature measurement is not installed this value will always read 0. | 1.3.6.1.4.1.4779.1.3.5.5.1.10 | INTEGER | read-only | mandatory |
| sRPCRebootTimeout OBJECT-TYPE The length of off time for automatic reboot sequences. Currently a read-only value set to the fixed reboot timeout. | 1.3.6.1.4.1.4779.1.3.5.5.1.11 | INTEGER | read-write | mandatory |
| sRPCAllOutletsCmd OBJECT-TYPE Turns all outlets on, off or reboot. 0 = off 1 = on 2 = reboot 3 = lockon (will lock outlets to on state) 4 = lockoff (will lock outlets to off state) 5 = unlock (will unlock all outlets) A get will return unknown (6). | 1.3.6.1.4.1.4779.1.3.5.5.1.12 | INTEGER {off(0), on(1), reboot(2), lockon(3), lockoff(4), unlock(5), unknown(6)} | read-write | mandatory |
| sRPCAllOutletsStatus OBJECT-TYPE Reports status of outlets in a comma deliminated string. 0 = off 1 = on 2 = reboot 3 = locked on 4 = locked off | 1.3.6.1.4.1.4779.1.3.5.5.1.13 | DisplayString | read-only | mandatory |
| sRPCCurrentAlarmThreshold OBJECT-TYPE The current alarm threshold level *10. A value of 105 will set the level to 10.5. | 1.3.6.1.4.1.4779.1.3.5.5.1.14 | INTEGER | read-write | mandatory |
| sRPCOverVoltageThreshold OBJECT-TYPE The over voltage alarm threshold level *10. A value of 105 will set the level to 10.5. | 1.3.6.1.4.1.4779.1.3.5.5.1.15 | INTEGER | read-write | mandatory |
| sRPCUnderVoltageThreshold OBJECT-TYPE The under voltage alarm threshold level *10. A value of 105 will set the level to 10.5. | 1.3.6.1.4.1.4779.1.3.5.5.1.16 | INTEGER | read-write | mandatory |
| sRPCNumberOfOutlets OBJECT-TYPE Number of outlets for this RPC. This will be the size of outlet table for this RPC index. | 1.3.6.1.4.1.4779.1.3.5.5.1.17 | INTEGER | read-only | mandatory |
| sRPCCircuitBreaker OBJECT-TYPE Status of circuit breaker in power strip. 0=off 1=on. | 1.3.6.1.4.1.4779.1.3.5.5.1.18 | INTEGER {off(0), on(1)} | read-only | mandatory |
| sRPCOverTempThreshold OBJECT-TYPE The over temperature alarm threshold level *10. A value of 505 will set the level to 50.5. | 1.3.6.1.4.1.4779.1.3.5.5.1.19 | INTEGER | read-write | mandatory |
| sRPCUnitVA OBJECT-TYPE Number of outlets for this RPC. This will be the size of outlet table for this RPC index. | 1.3.6.1.4.1.4779.1.3.5.5.1.20 | INTEGER | read-only | mandatory |
| sRPCNumberOfBreakers OBJECT-TYPE Number of breakers for this RPC. | 1.3.6.1.4.1.4779.1.3.5.5.1.21 | INTEGER | read-only | mandatory |
| sRPCLowCurrentThreshold OBJECT-TYPE Low current threshold for this RPC. | 1.3.6.1.4.1.4779.1.3.5.5.1.22 | INTEGER | read-write | mandatory |
| sRPCVoltageSource OBJECT-TYPE Voltage source for this RPC. | 1.3.6.1.4.1.4779.1.3.5.5.1.23 | INTEGER | read-write | mandatory |
| sRPCSourceSwitchCount OBJECT-TYPE Voltage source switch count for this RPC. | 1.3.6.1.4.1.4779.1.3.5.5.1.24 | INTEGER | read-write | mandatory |
| sRPCNumberOfSensors OBJECT-TYPE Number of sensors for this RPC. | 1.3.6.1.4.1.4779.1.3.5.5.1.25 | INTEGER | read-only | mandatory |
| sBTAModulesRPCModPortOutletTable OBJECT-TYPE Allows for control of individual outlets. The number of entries is contained in the sBTAModulesRPCOutletTableSize OID. | 1.3.6.1.4.1.4779.1.3.5.6 | not-accessible | mandatory | |
| sBTAModulesRPCModPortOutletEntry OBJECT-TYPE The outlets to control and get status on. | 1.3.6.1.4.1.4779.1.3.5.6.1 | not-accessible | mandatory | |
| sRPCOutletModuleIndex OBJECT-TYPE The module index to the outlet entry. | 1.3.6.1.4.1.4779.1.3.5.6.1.1 | INTEGER | read-only | mandatory |
| sRPCOutletPortIndex OBJECT-TYPE The port index to the outlet entry. In the case of ds30s this number is always 1. | 1.3.6.1.4.1.4779.1.3.5.6.1.2 | INTEGER | read-only | mandatory |
| sRPCOutletIndex OBJECT-TYPE The outlet index to the outlet entry. | 1.3.6.1.4.1.4779.1.3.5.6.1.3 | INTEGER | read-only | mandatory |
| sRPCOutletState OBJECT-TYPE Getting this variable will return the state of the outlet. Valid return states are unknown, on, off, lockon, lockoff. 0 = off 1 = on 2 = reboot 3 = lockon (outlet is on and no changes are allowed) 4 = lockoff (outlet is off and no changes are allowed) 5 = unlock. | 1.3.6.1.4.1.4779.1.3.5.6.1.4 | INTEGER {off(0), on(1), reboot(2), lockon(3), lockoff(4), unlock(5), unknown(6)} | read-write | mandatory |
| sRPCOutletName OBJECT-TYPE The name of the outlet. Maximum size is 16 characters. | 1.3.6.1.4.1.4779.1.3.5.6.1.5 | DisplayString | read-write | mandatory |
| sBTAModulesRPCModPortGroupCmd OBJECT-TYPE A character string listing the outlets that need to be rebooted, turned off, or turn on as a group. Command is the first character followed by a space. Valid commads are 0=off,1=on, or 2=reboot. A list follows the command in the format module.port.outlet. For example 2 2.1.1,2.1.12,3.4.1 will reboot module 2 port 1 outlet 2&12 module 3 port 4 outlet 1. | 1.3.6.1.4.1.4779.1.3.5.7 | DisplayString | read-write | mandatory |
| sBTAModulesRPCCurrentGroupsCurrentTable OBJECT-TYPE A list of total current for RPCs in each current group | 1.3.6.1.4.1.4779.1.3.5.8 | not-accessible | mandatory | |
| sBTAModulesRPCCurrentGroupsCurrentEntry OBJECT-TYPE Table of total current measurement by group | 1.3.6.1.4.1.4779.1.3.5.8.1 | not-accessible | mandatory | |
| groupCurrentIndex OBJECT-TYPE The index to a group total current. | 1.3.6.1.4.1.4779.1.3.5.8.1.1 | INTEGER | read-only | mandatory |
| groupCurrent OBJECT-TYPE Current total for all RPCs in group. | 1.3.6.1.4.1.4779.1.3.5.8.1.2 | INTEGER | read-only | mandatory |
| rpcGroup OBJECT-TYPE A character string listing the RPCs, by port index, that will be included in a measurement of total current. For each group, a sum will be periodically computed of currents of all listed RPCs, which will be compared to warning and emergency thresholds, generating appropriate traps as required by transit of a threshold. A maximum of 8 RPCs may be monitored within a group. The RPC must be connected and operating and the corresponding DS74 serial port must be configured for an RPC-SNMP device type to be allowed group membership. | 1.3.6.1.4.1.4779.1.3.5.8.1.3 | DisplayString | read-write | mandatory |
| warningThreshold OBJECT-TYPE The current level, in tenths of an amp, that will cause a Current Level Warning trap to be sent if the total current for the associated group if exceeded. Conversely, a Current Level Warning Clear trap will be sent whent the total group current falls below the threshold. | 1.3.6.1.4.1.4779.1.3.5.8.1.4 | INTEGER | read-write | mandatory |
| emergencyThreshold OBJECT-TYPE The current level, in tenths of an amp, that will cause a Current Level Emergency trap to be sent if the total current for the associated group if exceeded. Conversely, a Current Level Emergeny Clear trap will be sent whent the total group current falls below the threshold. | 1.3.6.1.4.1.4779.1.3.5.8.1.5 | INTEGER | read-write | mandatory |
| sBTAModulesRPCBreakersTable OBJECT-TYPE Allows monitoring of individual outlet strips on RPCs. | 1.3.6.1.4.1.4779.1.3.5.9 | not-accessible | mandatory | |
| sBTAModulesRPCBreakersEntry OBJECT-TYPE Status organization by breaker. | 1.3.6.1.4.1.4779.1.3.5.9.1 | not-accessible | mandatory | |
| sBTAModulesRPCBreakersModulesIndex OBJECT-TYPE The index into the RPC table. | 1.3.6.1.4.1.4779.1.3.5.9.1.1 | INTEGER | read-only | mandatory |
| sBTAModulesRPCBreakersBreakersIndex OBJECT-TYPE The index into the RPC breaker table. | 1.3.6.1.4.1.4779.1.3.5.9.1.2 | INTEGER | read-only | mandatory |
| sBTAModulesRPCBreakersCircuitBreaker OBJECT-TYPE Status of circuit breaker in power strip. 0=off 1=on. | 1.3.6.1.4.1.4779.1.3.5.9.1.3 | INTEGER {off(0), on(1)} | read-only | mandatory |
| sBTAModulesRPCBreakersCurrent OBJECT-TYPE The detected current reading for the power strip. If current measurement is not installed this value will always read 0. | 1.3.6.1.4.1.4779.1.3.5.9.1.4 | INTEGER | read-only | mandatory |
| sBTAModulesRPCBreakersMaxCurrent OBJECT-TYPE The maximum detected current reading for the power strip. If current measurement is not installed this value will always read 0. | 1.3.6.1.4.1.4779.1.3.5.9.1.5 | INTEGER | read-only | mandatory |
| sBTAModulesRPCBreakersVoltage OBJECT-TYPE The voltage reading for the power strip. If voltage measurement is not installed this value will always read 0. | 1.3.6.1.4.1.4779.1.3.5.9.1.6 | INTEGER | read-only | mandatory |
| sBTAModulesRPCBreakersPower OBJECT-TYPE The power reading for the power strip. If voltage measurement is not installed this value will always read 0. | 1.3.6.1.4.1.4779.1.3.5.9.1.7 | INTEGER | read-only | mandatory |
| sBTAModulesRPCBreakersVA OBJECT-TYPE The volt-amps reading for the power strip. If voltage measurement is not installed this value will always read 0. | 1.3.6.1.4.1.4779.1.3.5.9.1.8 | INTEGER | read-only | mandatory |
| sBTAModulesRPCBreakersCurrentAlarmThreshold OBJECT-TYPE The current alarm threshold level *10. A value of 105 will set the level to 10.5. | 1.3.6.1.4.1.4779.1.3.5.9.1.9 | INTEGER | read-write | mandatory |
| sRPCModPortBreakersTable OBJECT-TYPE Allows monitoring of individual outlet strips on RPCs. | 1.3.6.1.4.1.4779.1.3.5.10 | not-accessible | mandatory | |
| sRPCModPortBreakersEntry OBJECT-TYPE Status organization by breaker. | 1.3.6.1.4.1.4779.1.3.5.10.1 | not-accessible | mandatory | |
| sRPCBreakersModIndex OBJECT-TYPE The module index into the RPC breaker table. | 1.3.6.1.4.1.4779.1.3.5.10.1.1 | INTEGER | read-only | mandatory |
| sRPCBreakersPortIndex OBJECT-TYPE The port index into the RPC breaker table. | 1.3.6.1.4.1.4779.1.3.5.10.1.2 | INTEGER | read-only | mandatory |
| sRPCBreakersBreakersIndex OBJECT-TYPE The breaker index into the RPC breaker table. | 1.3.6.1.4.1.4779.1.3.5.10.1.3 | INTEGER | read-only | mandatory |
| sRPCBreakersCircuitBreaker OBJECT-TYPE Status of circuit breaker in power strip. 0=off 1=on. | 1.3.6.1.4.1.4779.1.3.5.10.1.4 | INTEGER {off(0), on(1)} | read-only | mandatory |
| sRPCBreakersCurrent OBJECT-TYPE The detected current reading for the power strip. If current measurement is not installed this value will always read 0. | 1.3.6.1.4.1.4779.1.3.5.10.1.5 | INTEGER | read-only | mandatory |
| sRPCBreakersMaxCurrent OBJECT-TYPE The maximum detected current reading for the power strip. If current measurement is not installed this value will always read 0. | 1.3.6.1.4.1.4779.1.3.5.10.1.6 | INTEGER | read-only | mandatory |
| sRPCBreakersVoltage OBJECT-TYPE The voltage reading for the power strip. If voltage measurement is not installed this value will always read 0. | 1.3.6.1.4.1.4779.1.3.5.10.1.7 | INTEGER | read-only | mandatory |
| sRPCBreakersPower OBJECT-TYPE The power reading for the power strip. If voltage measurement is not installed this value will always read 0. | 1.3.6.1.4.1.4779.1.3.5.10.1.8 | INTEGER | read-only | mandatory |
| sRPCBreakersVA OBJECT-TYPE The volt-amps reading for the power strip. If voltage measurement is not installed this value will always read 0. | 1.3.6.1.4.1.4779.1.3.5.10.1.9 | INTEGER | read-only | mandatory |
| sRPCBreakersCurrentAlarmThreshold OBJECT-TYPE The current alarm threshold level x10. A value of 105 will set the level to 10.5. | 1.3.6.1.4.1.4779.1.3.5.10.1.10 | INTEGER | read-write | mandatory |
| sRPCOutletGroupTable OBJECT-TYPE Allows control of outlets via a group of up to four outlets. | 1.3.6.1.4.1.4779.1.3.5.11 | not-accessible | mandatory | |
| sRPCOutletGroupEntry OBJECT-TYPE Organized by group number. | 1.3.6.1.4.1.4779.1.3.5.11.1 | not-accessible | mandatory | |
| sRPCOutletGroupIndex OBJECT-TYPE The index into the outlet group table. | 1.3.6.1.4.1.4779.1.3.5.11.1.1 | INTEGER | read-only | mandatory |
| sRPCOutletGroupName OBJECT-TYPE The name of the outlet group. | 1.3.6.1.4.1.4779.1.3.5.11.1.2 | DisplayString | read-write | mandatory |
| sRPCOutletGroupOutlets OBJECT-TYPE The list of outlets in the outlet group. Format is mod.port.outlet,mod.port.outlet up to 4 outlets. | 1.3.6.1.4.1.4779.1.3.5.11.1.3 | DisplayString | read-write | mandatory |
| sRPCOutletGroupCmd OBJECT-TYPE Command for outlet group. Same rules as rpc commands. | 1.3.6.1.4.1.4779.1.3.5.11.1.4 | INTEGER {off(0), on(1), reboot(2), lockon(3), lockoff(4), unlock(5), unknown(6)} | read-write | mandatory |
| sBTAModulesSerial OBJECT-IDENTITY | 1.3.6.1.4.1.4779.1.3.6 | |||
| sBTAModulesModem OBJECT-IDENTITY | 1.3.6.1.4.1.4779.1.3.7 | |||
| sBTAControl OBJECT-IDENTITY | 1.3.6.1.4.1.4779.1.4 | |||
| sBTAControlResetUnit OBJECT-TYPE Setting this value to 1 will cause the unit to reset. A get of this OID will return 0. | 1.3.6.1.4.1.4779.1.4.1 | INTEGER {noreset(0), reset(1)} | read-write | mandatory |
| sBTAControlResetModules OBJECT-TYPE Setting this value to 1 will cause the unit to reset modules simular to the telnet RM command. A get of this OID will return 0. | 1.3.6.1.4.1.4779.1.4.2 | INTEGER {noreset(0), reset(1)} | read-write | mandatory |
| sBTAControlNumOfLoggedUsers OBJECT-TYPE Number of users logged in via telnet or SSH. | 1.3.6.1.4.1.4779.1.4.3 | INTEGER | read-only | mandatory |
| sBTAControlUserTable OBJECT-TYPE A list of users and user information. The number of entries is contained in the sBTAControlNumOfLoggedUsers OID. | 1.3.6.1.4.1.4779.1.4.4 | not-accessible | mandatory | |
| sBTAControlUserEntry OBJECT-TYPE The users to get status on. | 1.3.6.1.4.1.4779.1.4.4.1 | not-accessible | mandatory | |
| sBTAControlUserIndex OBJECT-TYPE The index to the user entry. | 1.3.6.1.4.1.4779.1.4.4.1.1 | INTEGER | read-only | mandatory |
| sBTAControlUserName OBJECT-TYPE The username of the user. | 1.3.6.1.4.1.4779.1.4.4.1.2 | DisplayString | read-only | mandatory |
| sBTAControlUserAddress OBJECT-TYPE The IP address of the user. | 1.3.6.1.4.1.4779.1.4.4.1.3 | IpAddress | read-only | mandatory |
| sBTAControlUserConnection OBJECT-TYPE Type of connection. If unknown, user is logging out or the connection is invalid. | 1.3.6.1.4.1.4779.1.4.4.1.4 | INTEGER {serialport(0), telnet(1), ssh(2), unknown(4)} | read-only | mandatory |
| sBTAControlUserConnModule OBJECT-TYPE If the user is connected to a module, this value will report the module number connected to. If the value is 0 the user is not connected to a module. | 1.3.6.1.4.1.4779.1.4.4.1.5 | INTEGER | read-only | mandatory |
| sBTAControlUserConnPort OBJECT-TYPE The port number with in a module that the user is connected to. This usually only applies to connections to DS74 serial modules. Intelligent modules connections are always made on port 1. If value is 0 the user is not connected to a module. | 1.3.6.1.4.1.4779.1.4.4.1.6 | INTEGER | read-only | mandatory |
| sBTAControlUserTerminateUser OBJECT-TYPE Settings this OID to anything but 0 will terminate (log out) the user. A get of this OID will return 0. | 1.3.6.1.4.1.4779.1.4.4.1.7 | INTEGER {terminate(1)} | read-write | mandatory |
| sBTAFileTransfer OBJECT-IDENTITY | 1.3.6.1.4.1.4779.1.5 | |||
| sBTAFileTransferEnableUpgradeFTPFileTransfer OBJECT-TYPE Setting this OID to enableUpgradeFileTransferDownloadViaFTP (1) will start the FTP server and place the DS72 in upgrade mode. An FTP connection may then be established for the purpose of transmitting a firmware upgrade file. | 1.3.6.1.4.1.4779.1.5.1 | INTEGER {enableUpgradeFileTransferDownloadViaFTP(1)} | read-write | mandatory |
| sBTAEnvironmental OBJECT-IDENTITY | 1.3.6.1.4.1.4779.1.6 | |||
| sBTAModulesEnvironmentalObjectsTable OBJECT-TYPE Allows monitoring of individual outlet strips on RPCs. | 1.3.6.1.4.1.4779.1.6.1 | not-accessible | mandatory | |
| sBTAModulesEnvironmentalObjectsEntry OBJECT-TYPE Status organization by sensor. | 1.3.6.1.4.1.4779.1.6.1.1 | not-accessible | mandatory | |
| sBTAModulesEnvironmentalModulesIndex OBJECT-TYPE Module Index for Environemntal table | 1.3.6.1.4.1.4779.1.6.1.1.1 | INTEGER | read-only | mandatory |
| sBTAModulesEnvironmentalSensorsIndex OBJECT-TYPE Sensor Index for Environemntal table | 1.3.6.1.4.1.4779.1.6.1.1.2 | INTEGER | read-only | mandatory |
| sBTAModulesEnvironmentalType OBJECT-TYPE Environmental Object Type. | 1.3.6.1.4.1.4779.1.6.1.1.3 | INTEGER | read-only | mandatory |
| sBTAModulesEnvironmentalName OBJECT-TYPE The name for the environmental object. | 1.3.6.1.4.1.4779.1.6.1.1.4 | DisplayString | read-write | mandatory |
| sBTAModulesEnvironmentalMeasurement OBJECT-TYPE The measurement or state for the object. | 1.3.6.1.4.1.4779.1.6.1.1.5 | INTEGER | read-only | mandatory |
| sBTAModulesEnvironmentalHiThreshold OBJECT-TYPE Hi threshold for object. | 1.3.6.1.4.1.4779.1.6.1.1.6 | INTEGER | read-write | mandatory |
| sBTAModulesEnvironmentalLoThreshold OBJECT-TYPE Lo threshold for object. | 1.3.6.1.4.1.4779.1.6.1.1.7 | INTEGER | read-write | mandatory |
| sBTAModulesEnvironmentalMax OBJECT-TYPE Max value recorded for object since last reset. | 1.3.6.1.4.1.4779.1.6.1.1.8 | INTEGER | read-write | mandatory |
| sBTAModulesEnvironmentalMin OBJECT-TYPE Min value recorded for object since last reset. | 1.3.6.1.4.1.4779.1.6.1.1.9 | INTEGER | read-write | mandatory |
| sBTAModulesEnvironmentalHiThresholdEn OBJECT-TYPE Hi threshold enable for object. | 1.3.6.1.4.1.4779.1.6.1.1.10 | INTEGER | read-write | mandatory |
| sBTAModulesEnvironmentalLoThresholdEn OBJECT-TYPE Lo threshold enable for object. | 1.3.6.1.4.1.4779.1.6.1.1.11 | INTEGER | read-write | mandatory |
| sBTAModulesEnvironmentalStateTrapEn OBJECT-TYPE Trap enable for environmental sensors with contacts. | 1.3.6.1.4.1.4779.1.6.1.1.12 | INTEGER | read-write | mandatory |
| sRPCEnvironmentalObjectsTable OBJECT-TYPE Allows monitoring of individual outlet strips on RPCs. | 1.3.6.1.4.1.4779.1.6.2 | not-accessible | mandatory | |
| sRPCEnvironmentalObjectsEntry OBJECT-TYPE Status organization by sensor. | 1.3.6.1.4.1.4779.1.6.2.1 | not-accessible | mandatory | |
| sRPCEnvironmentalModuleIndex OBJECT-TYPE Module Index for Environemntal table | 1.3.6.1.4.1.4779.1.6.2.1.1 | INTEGER | read-only | mandatory |
| sRPCEnvironmentalPortIndex OBJECT-TYPE Port Index for Environemntal table | 1.3.6.1.4.1.4779.1.6.2.1.2 | INTEGER | read-only | mandatory |
| sRPCEnvironmentalSensorsIndex OBJECT-TYPE Sensor Index for Environemntal table | 1.3.6.1.4.1.4779.1.6.2.1.3 | INTEGER | read-only | mandatory |
| sRPCEnvironmentalType OBJECT-TYPE Environmental Object Type. | 1.3.6.1.4.1.4779.1.6.2.1.4 | INTEGER | read-only | mandatory |
| sRPCEnvironmentalName OBJECT-TYPE The name for the environmental object. | 1.3.6.1.4.1.4779.1.6.2.1.5 | DisplayString | read-write | mandatory |
| sRPCEnvironmentalMeasurement OBJECT-TYPE The measurement or state for the object. | 1.3.6.1.4.1.4779.1.6.2.1.6 | INTEGER | read-only | mandatory |
| sRPCEnvironmentalHiThreshold OBJECT-TYPE Hi threshold for object. | 1.3.6.1.4.1.4779.1.6.2.1.7 | INTEGER | read-write | mandatory |
| sRPCEnvironmentalLoThreshold OBJECT-TYPE Lo threshold for object. | 1.3.6.1.4.1.4779.1.6.2.1.8 | INTEGER | read-write | mandatory |
| sRPCEnvironmentalMax OBJECT-TYPE Max value recorded for object since last reset. | 1.3.6.1.4.1.4779.1.6.2.1.9 | INTEGER | read-write | mandatory |
| sRPCEnvironmentalMin OBJECT-TYPE Min value recorded for object since last reset. | 1.3.6.1.4.1.4779.1.6.2.1.10 | INTEGER | read-write | mandatory |
| sRPCEnvironmentalHiThresholdEn OBJECT-TYPE Hi threshold enable for object. | 1.3.6.1.4.1.4779.1.6.2.1.11 | INTEGER | read-write | mandatory |
| sRPCEnvironmentalLoThresholdEn OBJECT-TYPE Lo threshold enable for object. | 1.3.6.1.4.1.4779.1.6.2.1.12 | INTEGER | read-write | mandatory |
| sRPCEnvironmentalStateTrapEn OBJECT-TYPE Trap enable for environmental sensors with contacts. | 1.3.6.1.4.1.4779.1.6.2.1.13 | INTEGER | read-write | mandatory |
| sBTAEnvironmentalAllTemperatureSensorsHiThreshold OBJECT-TYPE Hi Threshold for all temperature sensors. | 1.3.6.1.4.1.4779.1.6.3 | INTEGER | read-write | mandatory |
| sBTAEnvironmentalAllTemperatureSensorsLoThreshold OBJECT-TYPE Lo Threshold for all temperature sensors. | 1.3.6.1.4.1.4779.1.6.4 | INTEGER | read-write | mandatory |
| sBTAEnvironmentalAllTemperatureSensorsHiThresholdTrapEnable OBJECT-TYPE Hi Threshold trap enable for all temperature sensors. | 1.3.6.1.4.1.4779.1.6.5 | INTEGER | read-write | mandatory |
| sBTAEnvironmentalAllTemperatureSensorsLoThresholdTrapEnable OBJECT-TYPE Lo Threshold trap enable for all temperature sensors. | 1.3.6.1.4.1.4779.1.6.6 | INTEGER | read-write | mandatory |
| sBTAEnvironmentalAllSensorsStateTrapEnable OBJECT-TYPE State change environmental sensor (ex: contact) trap enable. | 1.3.6.1.4.1.4779.1.6.7 | INTEGER | read-write | mandatory |
| sBTAEnvironmentalAllHumiditySensorsHiThreshold OBJECT-TYPE Hi Threshold for all humidity sensors. | 1.3.6.1.4.1.4779.1.6.8 | INTEGER | read-write | mandatory |
| sBTAEnvironmentalAllHumiditySensorsLoThreshold OBJECT-TYPE Lo Threshold for all humidity sensors. | 1.3.6.1.4.1.4779.1.6.9 | INTEGER | read-write | mandatory |
| sBTAEnvironmentalAllHumiditySensorsHiThresholdTrapEnable OBJECT-TYPE Hi Threshold trap enable for all humidity sensors. | 1.3.6.1.4.1.4779.1.6.10 | INTEGER | read-write | mandatory |
| sBTAEnvironmentalAllHumiditySensorsLoThresholdTrapEnable OBJECT-TYPE Lo Threshold trap enable for all humidity sensors. | 1.3.6.1.4.1.4779.1.6.11 | INTEGER | read-write | mandatory |
| sBTAEnvironmentalAllAirflowSensorsHiThreshold OBJECT-TYPE Hi Threshold for all airflow sensors. | 1.3.6.1.4.1.4779.1.6.12 | INTEGER | read-write | mandatory |
| sBTAEnvironmentalAllAirflowSensorsLoThreshold OBJECT-TYPE Lo Threshold for all airflow sensors. | 1.3.6.1.4.1.4779.1.6.13 | INTEGER | read-write | mandatory |
| sBTAEnvironmentalAllAirflowSensorsHiThresholdTrapEnable OBJECT-TYPE Hi Threshold trap enable for all airflow sensors. | 1.3.6.1.4.1.4779.1.6.14 | INTEGER | read-write | mandatory |
| sBTAEnvironmentalAllAirflowSensorsLoThresholdTrapEnable OBJECT-TYPE Lo Threshold trap enable for all airflow sensors. | 1.3.6.1.4.1.4779.1.6.15 | INTEGER | read-write | mandatory |
| mtrapargs OBJECT-IDENTITY | 1.3.6.1.4.1.4779.3 | |||
| mtrapargsInteger OBJECT-TYPE This OID allows baytech traps to be sent with an integer argument that may not be defined in the baytech MIB. A get of this OID will return 0. | 1.3.6.1.4.1.4779.3.1 | INTEGER | read-only | mandatory |
| mtrapargsIpAddress OBJECT-TYPE This OID allows bayteh traps to be sent with an IP address argument that may not be defined in the baytech MIB. A get of this OID will return 0.0.0.0. | 1.3.6.1.4.1.4779.3.2 | IpAddress | read-only | mandatory |
| mtrapargsString OBJECT-TYPE This OID allows baytech traps to be sent with an octet string argument that may not be defined in the baytech MIB. A get of this OID will return a NULL string. | 1.3.6.1.4.1.4779.3.3 | DisplayString | read-only | mandatory |
| mtrapargsGauge OBJECT-TYPE This OID allows baytech traps to be sent with a Gauge argument that may not be defined in the baytech MIB. A get of this OID will return 0. | 1.3.6.1.4.1.4779.3.4 | Gauge | read-only | mandatory |
| mtrapargsTimeTicks OBJECT-TYPE This OID allows baytech traps to be sent with a TimeTicks argument that may not be defined in the baytech MIB. A get of this OID will return 0. | 1.3.6.1.4.1.4779.3.5 | TimeTicks | read-only | mandatory |
| sBTAModuleIndex OBJECT-TYPE This OID allows baytech traps to be sent with an integer argument that may not be defined in the baytech MIB. This is an index to a specific DS module. Value will equal the slot of the module. A get of this OID will return 0. | 1.3.6.1.4.1.4779.3.6 | INTEGER | read-only | mandatory |
| sBTAOutletIndex OBJECT-TYPE This OID allows baytech traps to be sent with an integer argument that may not be defined in the baytech MIB. This is an index to a specific outlet in a DS module. Value is 1 to number of outlets controlled by the ds module. 0 represents all outlets. A get of this OID will return 0. | 1.3.6.1.4.1.4779.3.7 | INTEGER | read-only | mandatory |
| sBTAPortIndex OBJECT-TYPE This OID allows baytech traps to be sent with an integer argument that may not be defined in the baytech MIB. This is an index to a specific outlet in a DS module. Value is 1 to number of outlets controlled by the ds module. 0 represents all outlets. A get of this OID will return 0. | 1.3.6.1.4.1.4779.3.8 | INTEGER | read-only | mandatory |
| sBTAVoltageSource OBJECT-TYPE This OID allows baytech traps to be sent with an integer argument that may not be defined in the baytech MIB. This is the number associated with the voltage source in an RPC. Value is 1 or 2, depending on which voltage source is powering the RPC. A get of this OID will return 0. | 1.3.6.1.4.1.4779.3.9 | INTEGER | read-write | mandatory |
| sBTASourceSwitchCount OBJECT-TYPE This OID allows baytech traps to be sent with an integer argument that may not be defined in the baytech MIB. This is the number associated with the number of voltage source transitions in an RPC. Value is 0 to 255, an 8-bit w/rollover count of number of times voltage source has been switched from one source to another. A get of this OID will return 0. | 1.3.6.1.4.1.4779.3.10 | INTEGER | read-only | mandatory |
| sBTASensorIndex OBJECT-TYPE This OID allows baytech traps to be sent with an integer argument that may not be defined in the baytech MIB. This is an index to a specific sensor in a DS module. Value is 1 to number of sensors controlled by the ds module. A get of this OID will return 0. | 1.3.6.1.4.1.4779.3.11 | INTEGER | read-only | mandatory |
| sBTABreakerIndex OBJECT-TYPE This is an object which is sent along with a trap to designate a breaker number pertinent to a particular trap. This value will range from 1 to the total number of breakers inside the particular RPC. A get of this OID will return 0. | 1.3.6.1.4.1.4779.3.12 | INTEGER | read-only | mandatory |
Notifications
| Name | OID | Status |
|---|---|---|
| communicationLost NOTIFICATION-TYPE SEVERE: Communication to the unit has been lost. Steps to reestablish communication are in progress. Argument is timeTicks when communication was lost. | 1.3.6.1.4.1.4779.0.1 | |
| communicationEstablished NOTIFICATION-TYPE INFORMATION: Communication with the unit has been established. Argument is timeTicks when communication was established. | 1.3.6.1.4.1.4779.0.2 | |
| outletOn NOTIFICATION-TYPE WARNING: The specified RPC outlet has turned on. If sBTAOutletIndex equals zero, then all outlets have turned on. | 1.3.6.1.4.1.4779.0.3 | |
| outletOff NOTIFICATION-TYPE WARNING: The specified RPC outlet has turned off. If sBTAOutletIndex equals zero, then all outlets have turned off. | 1.3.6.1.4.1.4779.0.4 | |
| outletReboot NOTIFICATION-TYPE WARNING: The specified RPC outlet has rebooted. If sBTAOutletIndex equals zero, then all outlets have rebooted. | 1.3.6.1.4.1.4779.0.5 | |
| outletLocked NOTIFICATION-TYPE WARNING: The specified RPC outlet has been locked. If sBTAOutletIndex equals zero, then all outlets have been locked. | 1.3.6.1.4.1.4779.0.6 | |
| outletUnlocked NOTIFICATION-TYPE WARNING: The specified RPC outlet has been unlocked. If sBTAOutletIndex equals zero, then all outlets have been unlocked. | 1.3.6.1.4.1.4779.0.7 | |
| configChangeSNMP NOTIFICATION-TYPE WARNING: The SNMP configuration has been changed. | 1.3.6.1.4.1.4779.0.8 | |
| configChangeOutlet NOTIFICATION-TYPE WARNING: The specified outlet has changed configuration. | 1.3.6.1.4.1.4779.0.9 | |
| accessViolationConsole NOTIFICATION-TYPE WARNING: Someone has attempted to login via the console with the incorrect password. | 1.3.6.1.4.1.4779.0.10 | |
| accessViolationNetwork NOTIFICATION-TYPE WARNING: Someone has attempted to login via the network with the incorrect password. | 1.3.6.1.4.1.4779.0.11 | |
| userPasswordChange NOTIFICATION-TYPE WARNING: The password for the specified user has been changed. | 1.3.6.1.4.1.4779.0.12 | |
| userAdded NOTIFICATION-TYPE WARNING: The specified user has been added. | 1.3.6.1.4.1.4779.0.13 | |
| userLoggedIn NOTIFICATION-TYPE INFORMATIONAL: The specified user has logged in. | 1.3.6.1.4.1.4779.0.14 | |
| temperatureThresholdViolation NOTIFICATION-TYPE WARNING: A temperature threshold has been violated. The argument is the rpc index. | 1.3.6.1.4.1.4779.0.15 | |
| temperatureThresholdViolationCleared NOTIFICATION-TYPE INFORMATIONAL: A temperature threshold violated has been cleared. The argument is the rpc index. | 1.3.6.1.4.1.4779.0.16 | |
| currentThresholdViolation NOTIFICATION-TYPE WARNING: The preset current threshold has been violated. The argument is the rpc index. | 1.3.6.1.4.1.4779.0.17 | |
| currentThresholdViolationCleared NOTIFICATION-TYPE INFORMATIONAL: A current threshold violation has been cleared. The argument is the rpc index. | 1.3.6.1.4.1.4779.0.18 | |
| resetModulesEvent NOTIFICATION-TYPE WARNING: A reset modules (RM) command has been executed. | 1.3.6.1.4.1.4779.0.19 | |
| resetModulesComplete NOTIFICATION-TYPE WARNING: A reset modules (RM) command has been completed. | 1.3.6.1.4.1.4779.0.20 | |
| errorExecutingSNMPCommand NOTIFICATION-TYPE WARNING: unable to execute SNMP command. String contains reason and command. | 1.3.6.1.4.1.4779.0.21 | |
| fileTransferComplete NOTIFICATION-TYPE INFORMATIONAL: file transfer to unit complete. | 1.3.6.1.4.1.4779.0.22 | |
| userTerminated NOTIFICATION-TYPE WARNING: user terminated. Argument specifies user. | 1.3.6.1.4.1.4779.0.23 | |
| voltageOverThresholdViolation NOTIFICATION-TYPE WARNING: Over voltage. Argument specifies rpc. | 1.3.6.1.4.1.4779.0.24 | |
| voltageOverThresholdViolationCleared NOTIFICATION-TYPE INFORMATIONAL: Over voltage cleared. Argument specifies rpc. | 1.3.6.1.4.1.4779.0.25 | |
| voltageUnderThresholdViolation NOTIFICATION-TYPE WARNING: Under voltage. Argument specifies rpc. | 1.3.6.1.4.1.4779.0.26 | |
| voltageUnderThresholdViolationCleared NOTIFICATION-TYPE INFORMATIONAL: Under voltage cleared. Argument specifies rpc. | 1.3.6.1.4.1.4779.0.27 | |
| circuitBreakerAlarm NOTIFICATION-TYPE WARNING: Circuit breaker is blown. Argument specifies rpc. | 1.3.6.1.4.1.4779.0.28 | |
| rpcFailureAlarm NOTIFICATION-TYPE WARNING: Unable to communicate to an RPC. Argument specifies port number of RPC. | 1.3.6.1.4.1.4779.0.29 | |
| userDeleted NOTIFICATION-TYPE INFORMATIONAL: The specified user has logged in. | 1.3.6.1.4.1.4779.0.30 | |
| warningThresholdViolation NOTIFICATION-TYPE | 1.3.6.1.4.1.4779.0.31 | |
| warningThresholdViolationClear NOTIFICATION-TYPE | 1.3.6.1.4.1.4779.0.32 | |
| emergencyThresholdViolation NOTIFICATION-TYPE | 1.3.6.1.4.1.4779.0.33 | |
| emergencyThresholdViolationClear NOTIFICATION-TYPE | 1.3.6.1.4.1.4779.0.34 | |
| circuitBreakerAlarmClearTrap NOTIFICATION-TYPE Circuit breaker has been reset. Argument specifies rpc. | 1.3.6.1.4.1.4779.0.35 | |
| currentUnderThresholdViolation NOTIFICATION-TYPE WARNING: Low current. Argument specifies rpc. | 1.3.6.1.4.1.4779.0.36 | |
| currentUnderThresholdViolationCleared NOTIFICATION-TYPE INFORMATIONAL: Low current cleared. Argument specifies rpc. | 1.3.6.1.4.1.4779.0.37 | |
| voltageSourceChangeAlarm NOTIFICATION-TYPE WARNING: RPC voltage source has changed. Arguments specify modules index, current voltage source, and count of number of times source has been switched. | 1.3.6.1.4.1.4779.0.38 | |
| sensorTempThreshHiAlarmTrap NOTIFICATION-TYPE WARNING: Hi threshold exceeded. Arguments specify module, sensor number | 1.3.6.1.4.1.4779.0.39 | |
| sensorTempThreshHiAlarmClearedTrap NOTIFICATION-TYPE WARNING: Hi threshold alarm cleared. Arguments specify module, sensor number | 1.3.6.1.4.1.4779.0.40 | |
| sensorTempThreshLoAlarmTrap NOTIFICATION-TYPE WARNING: Lo threshold alarm cleared. Arguments specify module, sensor number | 1.3.6.1.4.1.4779.0.41 | |
| sensorTempThreshLoAlarmClearedTrap NOTIFICATION-TYPE WARNING: Lo threshold alarm cleared. Arguments specify module, sensor number | 1.3.6.1.4.1.4779.0.42 | |
| sensorStateChangeTrap NOTIFICATION-TYPE WARNING: Sensor state (contact, detector, etc) has changed. Arguments specify module, sensor number | 1.3.6.1.4.1.4779.0.43 | |
| configChangeSensor NOTIFICATION-TYPE WARNING: The specified environmental sensor has changed configuration. | 1.3.6.1.4.1.4779.0.44 | |
| sensorTypeChange NOTIFICATION-TYPE WARNING: The specified environmental sensor is now a different type. | 1.3.6.1.4.1.4779.0.45 |