Argus-Power-System-MIB
- Registered at
- 1.3.6.1.4.1.7309.6
- Last updated
- 2016-12-09 00:00
- Organization
- Alpha Technologies Ltd.
- Revisions
- 2016-12-09 00:00
- Namespace
- alpha
- Source file
Argus-Power-System-MIB- Digest
sha256:a7a90781ddbf967cd8a2408b55964e0738ca0f4209b9bc4a5ea2cf7913e9f554
Description
This MIB defines the information block(s) available in CXC RMU as defined by the following list: - upsDevice: the CXC-series of controllers
Contact
Alpha Technologies Ltd. 7700 Riverfront Gate Burnaby, BC V5J 5M4 Canada Tel: 1-604-436-5900 Fax: 1-604-436-1233
Imports
| From | Symbols |
|---|---|
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, enterprises, iso |
| SNMPv2-TC | DisplayString, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
Argus-Power-System-MIB SNMPv2-CONF SNMPv2-SMI SNMPv2-TC
Textual conventions
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| DisplayString type | ||||
| NonNegativeInteger TEXTUAL-CONVENTION This data type is a non-negative value. | current | |||
| PhysAddress type | ||||
| PositiveInteger TEXTUAL-CONVENTION This data type is a non-zero and non-negative value. | current |
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| upsPower OBJECT-IDENTITY | 1.3.6.1.4.1.7309.6 | |||
| upsDevice OBJECT-IDENTITY | 1.3.6.1.4.1.7309.6.1 | |||
| upsIdent OBJECT-IDENTITY | 1.3.6.1.4.1.7309.6.1.1 | |||
| upsIdentManufacturer OBJECT-TYPE The name of the UPS manufacturer. | 1.3.6.1.4.1.7309.6.1.1.1 | DisplayString (SIZE(0..255)) | read-only | current |
| upsIdentProductCode OBJECT-TYPE The UPS Model designation. | 1.3.6.1.4.1.7309.6.1.1.2 | DisplayString (SIZE(0..255)) | read-only | current |
| upsIdentModel OBJECT-TYPE The UPS Product code designation. | 1.3.6.1.4.1.7309.6.1.1.3 | DisplayString (SIZE(0..255)) | read-only | current |
| upsIdentUPSSoftwareVersion OBJECT-TYPE The UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations. | 1.3.6.1.4.1.7309.6.1.1.4 | DisplayString (SIZE(0..255)) | read-only | current |
| upsIdentAgentSoftwareVersion OBJECT-TYPE The UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations. | 1.3.6.1.4.1.7309.6.1.1.5 | DisplayString (SIZE(0..255)) | read-only | current |
| upsIdentName OBJECT-TYPE A string identifying the UPS. This object should be set by the administrator. | 1.3.6.1.4.1.7309.6.1.1.6 | DisplayString (SIZE(0..255)) | read-only | current |
| upsIdentAttachedDevices OBJECT-TYPE A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator. | 1.3.6.1.4.1.7309.6.1.1.7 | DisplayString (SIZE(0..255)) | read-only | current |
| upsIdentSiteName OBJECT-TYPE Site Name | 1.3.6.1.4.1.7309.6.1.1.8 | DisplayString (SIZE(0..255)) | read-write | current |
| upsIdentSiteCity OBJECT-TYPE Site City | 1.3.6.1.4.1.7309.6.1.1.9 | DisplayString (SIZE(0..255)) | read-write | current |
| upsIdentSiteRegion OBJECT-TYPE Site Region | 1.3.6.1.4.1.7309.6.1.1.10 | DisplayString (SIZE(0..255)) | read-write | current |
| upsIdentSiteCountry OBJECT-TYPE Site Country | 1.3.6.1.4.1.7309.6.1.1.11 | DisplayString (SIZE(0..255)) | read-write | current |
| upsIdentContactName OBJECT-TYPE Contact Name | 1.3.6.1.4.1.7309.6.1.1.12 | DisplayString (SIZE(0..255)) | read-write | current |
| upsIdentPhoneNumber OBJECT-TYPE Phone Number | 1.3.6.1.4.1.7309.6.1.1.13 | DisplayString (SIZE(0..255)) | read-write | current |
| upsIdentDate OBJECT-TYPE Date of the RMU-Novus | 1.3.6.1.4.1.7309.6.1.1.14 | DisplayString (SIZE(0..255)) | read-write | current |
| upsIdentTime OBJECT-TYPE Time of the RMU-Novus | 1.3.6.1.4.1.7309.6.1.1.15 | DisplayString (SIZE(0..255)) | read-write | current |
| upsBattery OBJECT-IDENTITY | 1.3.6.1.4.1.7309.6.1.2 | |||
| upsBatteryStatus OBJECT-TYPE The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output). | 1.3.6.1.4.1.7309.6.1.2.1 | INTEGER {unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4)} | read-only | current |
| upsMinutesOnBattery OBJECT-TYPE The accumulated elapsed time that the UPS system have been on battery. | 1.3.6.1.4.1.7309.6.1.2.2 | INTEGER | read-only | current |
| upsBatteryVoltage OBJECT-TYPE The magnitude of the present battery voltage. | 1.3.6.1.4.1.7309.6.1.2.3 | INTEGER | read-only | current |
| upsBatteryChargingCurrent OBJECT-TYPE The present battery charging current. | 1.3.6.1.4.1.7309.6.1.2.4 | INTEGER | read-only | current |
| upsBatteryCapacity OBJECT-TYPE The present battery capacity. | 1.3.6.1.4.1.7309.6.1.2.5 | INTEGER | read-only | current |
| upsBatteryTemperature OBJECT-TYPE The ambient temperature at or near the UPS Battery casing. | 1.3.6.1.4.1.7309.6.1.2.6 | INTEGER | read-only | current |
| upsBatteryLowWarning OBJECT-TYPE The set battery capacity percentage at which the unit will raise an alarm. | 1.3.6.1.4.1.7309.6.1.2.7 | INTEGER | read-write | current |
| upsInput OBJECT-IDENTITY | 1.3.6.1.4.1.7309.6.1.3 | |||
| upsInputNumLines OBJECT-TYPE The number of input lines utilized in this device. This variable indicates the number of rows in the input table. | 1.3.6.1.4.1.7309.6.1.3.1 | INTEGER | read-only | current |
| upsInputTable OBJECT-TYPE A list of input table entries. The number of entries is given by the value of upsInputNumLines. | 1.3.6.1.4.1.7309.6.1.3.2 | not-accessible | current | |
| upsInputEntry OBJECT-TYPE An entry containing information applicable to a particular input line. | 1.3.6.1.4.1.7309.6.1.3.2.1 | not-accessible | current | |
| upsInputLineIndex OBJECT-TYPE The input line identifier. | 1.3.6.1.4.1.7309.6.1.3.2.1.1 | INTEGER | not-accessible | current |
| upsInputFrequency OBJECT-TYPE The present input frequency. | 1.3.6.1.4.1.7309.6.1.3.2.1.2 | INTEGER | read-only | current |
| upsInputVoltage OBJECT-TYPE The magnitude of the present input voltage. | 1.3.6.1.4.1.7309.6.1.3.2.1.3 | INTEGER | read-only | current |
| upsOutput OBJECT-IDENTITY | 1.3.6.1.4.1.7309.6.1.4 | |||
| upsOutputSource OBJECT-TYPE The present source of output power. The enumeration line(2) indicates that the Novus is in line mode. | 1.3.6.1.4.1.7309.6.1.4.1 | INTEGER {standby(1), line(2), boost2(3), boost1(4), buck1(5), buck2(6), inverter(7), retransfer(8), transfer(9), shutdown(10), bypass(11)} | read-only | current |
| upsOutputFrequency OBJECT-TYPE The present output frequency. | 1.3.6.1.4.1.7309.6.1.4.2 | INTEGER | read-only | current |
| upsOutputNumLines OBJECT-TYPE The number of output lines utilized in this device. This variable indicates the number of rows in the output table. | 1.3.6.1.4.1.7309.6.1.4.3 | INTEGER | read-only | current |
| upsOutputTable OBJECT-TYPE A list of output table entries. The number of entries is given by the value of upsOutputNumLines. | 1.3.6.1.4.1.7309.6.1.4.4 | not-accessible | current | |
| upsOutputEntry OBJECT-TYPE An entry containing information applicable to a particular output line. | 1.3.6.1.4.1.7309.6.1.4.4.1 | not-accessible | current | |
| upsOutputLineIndex OBJECT-TYPE The output line identifier. | 1.3.6.1.4.1.7309.6.1.4.4.1.1 | INTEGER | not-accessible | current |
| upsOutputVoltage OBJECT-TYPE The present output voltage. | 1.3.6.1.4.1.7309.6.1.4.4.1.2 | INTEGER | read-only | current |
| upsOutputCurrent OBJECT-TYPE The present output current. | 1.3.6.1.4.1.7309.6.1.4.4.1.3 | INTEGER | read-only | current |
| upsOutputPowerVA OBJECT-TYPE The present output VA. | 1.3.6.1.4.1.7309.6.1.4.4.1.4 | INTEGER | read-only | current |
| upsOutputPowerWatt OBJECT-TYPE The present output true power. | 1.3.6.1.4.1.7309.6.1.4.4.1.5 | INTEGER | read-only | current |
| upsPowerFactor OBJECT-TYPE The present power factor. | 1.3.6.1.4.1.7309.6.1.4.4.1.6 | INTEGER | read-only | current |
| upsOutputPercentLoad OBJECT-TYPE The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA. | 1.3.6.1.4.1.7309.6.1.4.4.1.7 | INTEGER (0..200) | read-only | current |
| upsAlarm OBJECT-IDENTITY | 1.3.6.1.4.1.7309.6.1.5 | |||
| upsAlarmsPresent OBJECT-TYPE The present number of active alarm conditions. | 1.3.6.1.4.1.7309.6.1.5.1 | INTEGER | read-only | current |
| upsAlarmTable OBJECT-TYPE A list of alarm table entries. | 1.3.6.1.4.1.7309.6.1.5.2 | not-accessible | current | |
| upsAlarmEntry OBJECT-TYPE An entry containing information applicable to a particular alarm. | 1.3.6.1.4.1.7309.6.1.5.2.1 | not-accessible | current | |
| upsAlarmId OBJECT-TYPE A unique identifier for an alarm condition. This value must remain constant. | 1.3.6.1.4.1.7309.6.1.5.2.1.1 | INTEGER | not-accessible | current |
| upsAlarmDescr OBJECT-TYPE A unique description of the alarm. | 1.3.6.1.4.1.7309.6.1.5.2.1.2 | DisplayString (SIZE(0..255)) | read-only | current |
| upsAlarmStatus OBJECT-TYPE 1 - ON or 0 - OFF. | 1.3.6.1.4.1.7309.6.1.5.2.1.3 | INTEGER | read-only | current |
| upsConfig OBJECT-IDENTITY | 1.3.6.1.4.1.7309.6.1.6 | |||
| upsConfigLineQualifyTime OBJECT-TYPE This objects displays the line qualify time. | 1.3.6.1.4.1.7309.6.1.6.1 | INTEGER | read-only | current |
| upsConfigLineOutputVoltageHighLimit OBJECT-TYPE This object represents the Line output High Voltage Limit. | 1.3.6.1.4.1.7309.6.1.6.2 | INTEGER | read-only | current |
| upsConfigLineOutputVoltageLowLimit OBJECT-TYPE This object represents the Line output Low Voltage Limit. | 1.3.6.1.4.1.7309.6.1.6.3 | INTEGER | read-only | current |
| upsConfigFanOnTemperature OBJECT-TYPE This object represents the Fan on temperature. | 1.3.6.1.4.1.7309.6.1.6.4 | INTEGER | read-only | current |
| upsShutdownStatus OBJECT-TYPE This object tells us if output is disabled or enabled. | 1.3.6.1.4.1.7309.6.1.6.5 | INTEGER | read-write | current |
| upsInverterOffDelayTime OBJECT-TYPE This object represents the inverter off delay time. | 1.3.6.1.4.1.7309.6.1.6.6 | INTEGER | read-write | current |
| upsConfigIPAddress OBJECT-TYPE This objects displays the IP address of the RMU. | 1.3.6.1.4.1.7309.6.1.6.7 | DisplayString (SIZE(0..255)) | read-write | current |
| upsConfigNetMask OBJECT-TYPE This object displays the Net Mask of the RMU. | 1.3.6.1.4.1.7309.6.1.6.8 | DisplayString (SIZE(0..255)) | read-write | current |
| upsConfigGateway OBJECT-TYPE This object displays the Gateway of the RMU. | 1.3.6.1.4.1.7309.6.1.6.9 | DisplayString (SIZE(0..255)) | read-write | current |
| upsConfigSnmpCommunity OBJECT-TYPE This object displays the SNMP community | 1.3.6.1.4.1.7309.6.1.6.10 | DisplayString (SIZE(0..255)) | read-write | current |
| upsConfigSnmpTrapIPDestination OBJECT-TYPE This object displays the SNMP Trap IP destination. | 1.3.6.1.4.1.7309.6.1.6.11 | DisplayString (SIZE(0..255)) | read-write | current |
| upsTraps OBJECT-IDENTITY | 1.3.6.1.4.1.7309.6.1.7 | |||
| upsTrap OBJECT-IDENTITY | 1.3.6.1.4.1.7309.6.1.7.0 | |||
| upsExtra OBJECT-IDENTITY | 1.3.6.1.4.1.7309.6.1.8 | |||
| upsExtraCount OBJECT-TYPE Number of extra variables | 1.3.6.1.4.1.7309.6.1.8.1 | INTEGER (0..65535) | read-only | current |
| upsExtraTable OBJECT-TYPE A table of CXC upstem controller extra variables | 1.3.6.1.4.1.7309.6.1.8.2 | not-accessible | current | |
| upsExtraEntry OBJECT-TYPE An entry into the CXC upstem controller extra variable table | 1.3.6.1.4.1.7309.6.1.8.2.1 | not-accessible | current | |
| upsExtraIndex OBJECT-TYPE The index of the extra variable in the CXC upstem controller table | 1.3.6.1.4.1.7309.6.1.8.2.1.1 | INTEGER (0..65535) | read-only | current |
| upsExtraName OBJECT-TYPE The description of the extra variable as reported by the CXC upstem controller | 1.3.6.1.4.1.7309.6.1.8.2.1.2 | DisplayString (SIZE(0..30)) | read-only | current |
| upsExtraIntegerValue OBJECT-TYPE The integer value of the extra variable as reported by the CXC upstem controller | 1.3.6.1.4.1.7309.6.1.8.2.1.3 | INTEGER (-1000000000..1000000000) | read-only | current |
| upsExtraStringValue OBJECT-TYPE The string value of the extra variable as reported by the CXC upstem controller | 1.3.6.1.4.1.7309.6.1.8.2.1.4 | DisplayString (SIZE(0..255)) | read-only | current |
Notifications
| Name | OID | Status |
|---|---|---|
| upsAlarmTrap NOTIFICATION-TYPE A trap issued from a change in state in one of the Alarms on the Novus controller | 1.3.6.1.4.1.7309.6.1.7.0.1 | current |
| upsAgentStartupTrap NOTIFICATION-TYPE A trap to indicate that the agent software has started up. | 1.3.6.1.4.1.7309.6.1.7.0.2 | current |
| upsAgentShutdownTrap NOTIFICATION-TYPE A trap to indicate that the agent software has shutdown. | 1.3.6.1.4.1.7309.6.1.7.0.3 | current |
| upsAgentFaultTrap NOTIFICATION-TYPE A trap issued from a change in state in one of the Faults on the Novus controller | 1.3.6.1.4.1.7309.6.1.7.0.4 | current |
| upsAgentEventTrap NOTIFICATION-TYPE A trap issued from a change in state in one of the Events on the Novus controller | 1.3.6.1.4.1.7309.6.1.7.0.5 | current |