MIBs Depot

Argus-MIB

Registered at
1.3.6.1.4.1.7309.4
Last updated
2008-11-03 00:00
Organization
Argus Technologies
Namespace
alpha
Source file
Argus-MIB
Digest
sha256:d8008738ace4dfb56060c85919f1839863b6d3980951e24d31eb008893de3caf

Description

This MIB defines the information block(s) available in system controllers as defined by the following list: - dcPwrSysDevice: the SM-series of controllers

Contact

Randy Dahlgren Postal: Argus Technologies 5700 Sidley Street Vancouver, BC V5J 5E5 Canada Tel: 1-604-436-5900 Fax: 1-604-436-1233 E-mail: rdahlgren@argus.ca

Imports

FromSymbols
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP
SNMPv2-SMIMODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, enterprises, iso
SNMPv2-TCDisplayString, TEXTUAL-CONVENTION

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

Argus-MIB
SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC

Objects

NameOIDSyntaxAccessStatus
dcpower
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4
dcPwrSysDevice
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1
dcPwrSysVariable
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.1
dcPwrSysChargeVolts
OBJECT-TYPE
Battery Charge Voltage. The integer value represent a two digit fix decimal (Value = real voltage * 100) in Volt
1.3.6.1.4.1.7309.4.1.1.1INTEGER (-1000000000..1000000000)read-onlycurrent
dcPwrSysDischargeVolts
OBJECT-TYPE
Battery Discharge Voltage. The integer value represent a two digit fix decimal (Value = real voltage * 100) in Volt
1.3.6.1.4.1.7309.4.1.1.2INTEGER (-1000000000..1000000000)read-onlycurrent
dcPwrSysChargeAmps
OBJECT-TYPE
Battery Charge Current. The integer value represent a two digit fix decimal (Value = real current * 100) in Amp
1.3.6.1.4.1.7309.4.1.1.3INTEGER (-1000000000..1000000000)read-onlycurrent
dcPwrSysDischargeAmps
OBJECT-TYPE
Battery Discharge Current. The integer value represent a two digit fix decimal (Value = real current * 100) in Amp
1.3.6.1.4.1.7309.4.1.1.4INTEGER (-1000000000..1000000000)read-onlycurrent
dcPwrSysMajorAlarm
OBJECT-TYPE
Major Alarm
1.3.6.1.4.1.7309.4.1.1.5INTEGER (0..65535)read-onlycurrent
dcPwrSysMinorAlarm
OBJECT-TYPE
Minor Alarm
1.3.6.1.4.1.7309.4.1.1.6INTEGER (0..65535)read-onlycurrent
dcPwrSysString
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.2
dcPwrSysSiteName
OBJECT-TYPE
Site Name
1.3.6.1.4.1.7309.4.1.2.1DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysSiteCity
OBJECT-TYPE
Site City
1.3.6.1.4.1.7309.4.1.2.2DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysSiteRegion
OBJECT-TYPE
Site Region
1.3.6.1.4.1.7309.4.1.2.3DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysSiteCountry
OBJECT-TYPE
Site Country
1.3.6.1.4.1.7309.4.1.2.4DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysContactName
OBJECT-TYPE
Contact Name
1.3.6.1.4.1.7309.4.1.2.5DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysPhoneNumber
OBJECT-TYPE
Phone Number
1.3.6.1.4.1.7309.4.1.2.6DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysSiteNumber
OBJECT-TYPE
Site Number
1.3.6.1.4.1.7309.4.1.2.7DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysSystemType
OBJECT-TYPE
The type of system being monitored by the agent
1.3.6.1.4.1.7309.4.1.2.8DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysSystemSerial
OBJECT-TYPE
The serial number of the monitored system
1.3.6.1.4.1.7309.4.1.2.9DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysSystemNumber
OBJECT-TYPE
The number of the monitored system
1.3.6.1.4.1.7309.4.1.2.10DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysSoftwareVersion
OBJECT-TYPE
The version of software running on the monitored system
1.3.6.1.4.1.7309.4.1.2.11DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysSoftwareTimestamp
OBJECT-TYPE
The time stamp of the software running on the monitored system
1.3.6.1.4.1.7309.4.1.2.12DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysTraps
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.3
dcPwrSysTrap
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.3.0
dcPwrSysOutputsTbl
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.4
dcPwrSysRelayTbl
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.4.1
dcPwrSysRelayCount
OBJECT-TYPE
Number of relay variables in system controller relay table
1.3.6.1.4.1.7309.4.1.4.1.1INTEGER (0..65535)read-onlycurrent
dcPwrSysRelayTable
OBJECT-TYPE
A table of DC power system controller rectifier relay output variables
1.3.6.1.4.1.7309.4.1.4.1.2not-accessiblecurrent
dcPwrSysRelayEntry
OBJECT-TYPE
An entry into the DC power system controller relay output group
1.3.6.1.4.1.7309.4.1.4.1.2.1not-accessiblecurrent
dcPwrSysRelayIndex
OBJECT-TYPE
The index of the relay variable in the power system controller relay output group
1.3.6.1.4.1.7309.4.1.4.1.2.1.1INTEGER (0..65535)read-onlycurrent
dcPwrSysRelayName
OBJECT-TYPE
The description of the relay variable as reported by the DC power system controller relay output group
1.3.6.1.4.1.7309.4.1.4.1.2.1.2DisplayString (SIZE(0..30))read-onlycurrent
dcPwrSysRelayIntegerValue
OBJECT-TYPE
The integer value of the relay variable as reported by the DC power system controller relay output group
1.3.6.1.4.1.7309.4.1.4.1.2.1.3INTEGER (-1000000000..1000000000)read-onlycurrent
dcPwrSysRelayStringValue
OBJECT-TYPE
The string value of the relay variable as reported by the DC power system controller relay output group
1.3.6.1.4.1.7309.4.1.4.1.2.1.4DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysRelaySeverity
OBJECT-TYPE
The integer value of relay severity level of the extra variable as reported by the DC power system controller relay output group
1.3.6.1.4.1.7309.4.1.4.1.2.1.5INTEGER (0..65535)read-onlycurrent
dcPwrSysAnalogOpTbl
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.4.2
dcPwrSysAnalogOpCount
OBJECT-TYPE
Number of analog output variables in system controller analog output table
1.3.6.1.4.1.7309.4.1.4.2.1INTEGER (0..65535)read-onlycurrent
dcPwrSysAnalogOpTable
OBJECT-TYPE
A table of DC power system controller analog output variables
1.3.6.1.4.1.7309.4.1.4.2.2not-accessiblecurrent
dcPwrSysAnalogOpEntry
OBJECT-TYPE
An entry into the DC power system controller analog output group
1.3.6.1.4.1.7309.4.1.4.2.2.1not-accessiblecurrent
dcPwrSysAnalogOpIndex
OBJECT-TYPE
The index of the analog variable in the power system controller analog output group
1.3.6.1.4.1.7309.4.1.4.2.2.1.1INTEGER (0..65535)read-onlycurrent
dcPwrSysAnalogOpName
OBJECT-TYPE
The description of the analog variable as reported by the DC power system controller analog output group
1.3.6.1.4.1.7309.4.1.4.2.2.1.2DisplayString (SIZE(0..30))read-onlycurrent
dcPwrSysAnalogOpIntegerValue
OBJECT-TYPE
The integer value of the analog variable as reported by the DC power system controller analog output group
1.3.6.1.4.1.7309.4.1.4.2.2.1.3INTEGER (-1000000000..1000000000)read-onlycurrent
dcPwrSysAnalogOpStringValue
OBJECT-TYPE
The string value of the analog variable as reported by the DC power system controller analog output group
1.3.6.1.4.1.7309.4.1.4.2.2.1.4DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysAnalogOpSeverity
OBJECT-TYPE
The integer value of analog severity level of the extra variable as reported by the DC power system controller analog output group
1.3.6.1.4.1.7309.4.1.4.2.2.1.5INTEGER (0..65535)read-onlycurrent
dcPwrSysAlrmsTbl
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.5
dcPwrSysRectAlrmTbl
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.5.1
dcPwrSysRectAlrmCount
OBJECT-TYPE
Number of rectifier alarm variables in system controller alarm table
1.3.6.1.4.1.7309.4.1.5.1.1INTEGER (0..65535)read-onlycurrent
dcPwrSysRectAlrmTable
OBJECT-TYPE
A table of DC power system controller rectifier alarm variables
1.3.6.1.4.1.7309.4.1.5.1.2not-accessiblecurrent
dcPwrSysRectAlrmEntry
OBJECT-TYPE
An entry into the DC power system controller rectifier alarm group
1.3.6.1.4.1.7309.4.1.5.1.2.1not-accessiblecurrent
dcPwrSysRectAlrmIndex
OBJECT-TYPE
The index of the alarm variable in the DC power system controller table rectifier alarm group
1.3.6.1.4.1.7309.4.1.5.1.2.1.1INTEGER (0..65535)read-onlycurrent
dcPwrSysRectAlrmName
OBJECT-TYPE
The description of the alarm variable as reported by the DC power system controller rectifier alarm group
1.3.6.1.4.1.7309.4.1.5.1.2.1.2DisplayString (SIZE(0..30))read-onlycurrent
dcPwrSysRectAlrmIntegerValue
OBJECT-TYPE
The integer value of the alarm variable as reported by the DC power system controller rectifier alarm group
1.3.6.1.4.1.7309.4.1.5.1.2.1.3INTEGER (-1000000000..1000000000)read-onlycurrent
dcPwrSysRectAlrmStringValue
OBJECT-TYPE
The string value of the alarm variable as reported by the DC power system controller rectifier alarm group
1.3.6.1.4.1.7309.4.1.5.1.2.1.4DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysRectAlrmSeverity
OBJECT-TYPE
The integer value of alarm severity level of the extra variable as reported by the DC power system controller rectifier alarm group
1.3.6.1.4.1.7309.4.1.5.1.2.1.5INTEGER (0..65535)read-onlycurrent
dcPwrSysDigAlrmTbl
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.5.2
dcPwrSysDigAlrmCount
OBJECT-TYPE
Number of digital alarm variables in system controller alarm table
1.3.6.1.4.1.7309.4.1.5.2.1INTEGER (0..65535)read-onlycurrent
dcPwrSysDigAlrmTable
OBJECT-TYPE
A table of DC power system controller digital alarm variables
1.3.6.1.4.1.7309.4.1.5.2.2not-accessiblecurrent
dcPwrSysDigAlrmEntry
OBJECT-TYPE
An entry into the DC power system controller digital alarm group
1.3.6.1.4.1.7309.4.1.5.2.2.1not-accessiblecurrent
dcPwrSysDigAlrmIndex
OBJECT-TYPE
The index of the alarm variable in the DC power system controller table digital alarm group
1.3.6.1.4.1.7309.4.1.5.2.2.1.1INTEGER (0..65535)read-onlycurrent
dcPwrSysDigAlrmName
OBJECT-TYPE
The description of the alarm variable as reported by the DC power system controller digital alarm group
1.3.6.1.4.1.7309.4.1.5.2.2.1.2DisplayString (SIZE(0..30))read-onlycurrent
dcPwrSysDigAlrmIntegerValue
OBJECT-TYPE
The integer value of the alarm variable as reported by the DC power system controller digital alarm group
1.3.6.1.4.1.7309.4.1.5.2.2.1.3INTEGER (-1000000000..1000000000)read-onlycurrent
dcPwrSysDigAlrmStringValue
OBJECT-TYPE
The string value of the alarm variable as reported by the DC power system controller digital alarm group
1.3.6.1.4.1.7309.4.1.5.2.2.1.4DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysDigAlrmSeverity
OBJECT-TYPE
The integer value of alarm severity level of the extra variable as reported by the DC power system controller digital alarm group
1.3.6.1.4.1.7309.4.1.5.2.2.1.5INTEGER (0..65535)read-onlycurrent
dcPwrSysCurrAlrmTbl
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.5.3
dcPwrSysCurrAlrmCount
OBJECT-TYPE
Number of current alarm variables in system controller alarm table
1.3.6.1.4.1.7309.4.1.5.3.1INTEGER (0..65535)read-onlycurrent
dcPwrSysCurrAlrmTable
OBJECT-TYPE
A table of DC power system controller current alarm variables
1.3.6.1.4.1.7309.4.1.5.3.2not-accessiblecurrent
dcPwrSysCurrAlrmEntry
OBJECT-TYPE
An entry into the DC power system controller current alarm group
1.3.6.1.4.1.7309.4.1.5.3.2.1not-accessiblecurrent
dcPwrSysCurrAlrmIndex
OBJECT-TYPE
The index of the alarm variable in the DC power system controller table current alarm group
1.3.6.1.4.1.7309.4.1.5.3.2.1.1INTEGER (0..65535)read-onlycurrent
dcPwrSysCurrAlrmName
OBJECT-TYPE
The description of the alarm variable as reported by the DC power system controller current alarm group
1.3.6.1.4.1.7309.4.1.5.3.2.1.2DisplayString (SIZE(0..30))read-onlycurrent
dcPwrSysCurrAlrmIntegerValue
OBJECT-TYPE
The integer value of the alarm variable as reported by the DC power system controller current alarm group
1.3.6.1.4.1.7309.4.1.5.3.2.1.3INTEGER (-1000000000..1000000000)read-onlycurrent
dcPwrSysCurrAlrmStringValue
OBJECT-TYPE
The string value of the alarm variable as reported by the DC power system controller current alarm group
1.3.6.1.4.1.7309.4.1.5.3.2.1.4DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysCurrAlrmSeverity
OBJECT-TYPE
The integer value of alarm severity level of the extra variable as reported by the DC power system controller current alarm group
1.3.6.1.4.1.7309.4.1.5.3.2.1.5INTEGER (0..65535)read-onlycurrent
dcPwrSysVoltAlrmTbl
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.5.4
dcPwrSysVoltAlrmCount
OBJECT-TYPE
Number of voltage alarm variables in system controller alarm table
1.3.6.1.4.1.7309.4.1.5.4.1INTEGER (0..65535)read-onlycurrent
dcPwrSysVoltAlrmTable
OBJECT-TYPE
A table of DC power system controller voltage alarm variables
1.3.6.1.4.1.7309.4.1.5.4.2not-accessiblecurrent
dcPwrSysVoltAlrmEntry
OBJECT-TYPE
An entry into the DC power system controller voltage alarm group
1.3.6.1.4.1.7309.4.1.5.4.2.1not-accessiblecurrent
dcPwrSysVoltAlrmIndex
OBJECT-TYPE
The index of the alarm variable in the DC power system controller table voltage alarm group
1.3.6.1.4.1.7309.4.1.5.4.2.1.1INTEGER (0..65535)read-onlycurrent
dcPwrSysVoltAlrmName
OBJECT-TYPE
The description of the alarm variable as reported by the DC power system controller voltage alarm group
1.3.6.1.4.1.7309.4.1.5.4.2.1.2DisplayString (SIZE(0..30))read-onlycurrent
dcPwrSysVoltAlrmIntegerValue
OBJECT-TYPE
The integer value of the alarm variable as reported by the DC power system controller voltage alarm group
1.3.6.1.4.1.7309.4.1.5.4.2.1.3INTEGER (-1000000000..1000000000)read-onlycurrent
dcPwrSysVoltAlrmStringValue
OBJECT-TYPE
The string value of the alarm variable as reported by the DC power system controller voltage alarm group
1.3.6.1.4.1.7309.4.1.5.4.2.1.4DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysVoltAlrmSeverity
OBJECT-TYPE
The integer value of alarm severity level of the extra variable as reported by the DC power system controller voltage alarm group
1.3.6.1.4.1.7309.4.1.5.4.2.1.5INTEGER (0..65535)read-onlycurrent
dcPwrSysBattAlrmTbl
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.5.5
dcPwrSysBattAlrmCount
OBJECT-TYPE
Number of battery alarm variables in system controller alarm table
1.3.6.1.4.1.7309.4.1.5.5.1INTEGER (0..65535)read-onlycurrent
dcPwrSysBattAlrmTable
OBJECT-TYPE
A table of DC power system controller battery alarm variables
1.3.6.1.4.1.7309.4.1.5.5.2not-accessiblecurrent
dcPwrSysBattAlrmEntry
OBJECT-TYPE
An entry into the DC power system controller battery alarm group
1.3.6.1.4.1.7309.4.1.5.5.2.1not-accessiblecurrent
dcPwrSysBattAlrmIndex
OBJECT-TYPE
The index of the alarm variable in the DC power system controller table battery alarm group
1.3.6.1.4.1.7309.4.1.5.5.2.1.1INTEGER (0..65535)read-onlycurrent
dcPwrSysBattAlrmName
OBJECT-TYPE
The description of the alarm variable as reported by the DC power system controller battery alarm group
1.3.6.1.4.1.7309.4.1.5.5.2.1.2DisplayString (SIZE(0..30))read-onlycurrent
dcPwrSysBattAlrmIntegerValue
OBJECT-TYPE
The integer value of the alarm variable as reported by the DC power system controller battery alarm group
1.3.6.1.4.1.7309.4.1.5.5.2.1.3INTEGER (-1000000000..1000000000)read-onlycurrent
dcPwrSysBattAlrmStringValue
OBJECT-TYPE
The string value of the alarm variable as reported by the DC power system controller battery alarm group
1.3.6.1.4.1.7309.4.1.5.5.2.1.4DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysBattAlrmSeverity
OBJECT-TYPE
The integer value of alarm severity level of the extra variable as reported by the DC power system controller battery alarm group
1.3.6.1.4.1.7309.4.1.5.5.2.1.5INTEGER (0..65535)read-onlycurrent
dcPwrSysTempAlrmTbl
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.5.6
dcPwrSysTempAlrmCount
OBJECT-TYPE
Number of temperature alarm variables in system controller alarm table
1.3.6.1.4.1.7309.4.1.5.6.1INTEGER (0..65535)read-onlycurrent
dcPwrSysTempAlrmTable
OBJECT-TYPE
A table of DC power system controller temperature alarm variables
1.3.6.1.4.1.7309.4.1.5.6.2not-accessiblecurrent
dcPwrSysTempAlrmEntry
OBJECT-TYPE
An entry into the DC power system controller temperature alarm group
1.3.6.1.4.1.7309.4.1.5.6.2.1not-accessiblecurrent
dcPwrSysTempAlrmIndex
OBJECT-TYPE
The index of the alarm variable in the DC power system controller table temperature alarm group
1.3.6.1.4.1.7309.4.1.5.6.2.1.1INTEGER (0..65535)read-onlycurrent
dcPwrSysTempAlrmName
OBJECT-TYPE
The description of the alarm variable as reported by the DC power system controller temperature alarm group
1.3.6.1.4.1.7309.4.1.5.6.2.1.2DisplayString (SIZE(0..30))read-onlycurrent
dcPwrSysTempAlrmIntegerValue
OBJECT-TYPE
The integer value of the alarm variable as reported by the DC power system controller temperature alarm group
1.3.6.1.4.1.7309.4.1.5.6.2.1.3INTEGER (-1000000000..1000000000)read-onlycurrent
dcPwrSysTempAlrmStringValue
OBJECT-TYPE
The string value of the alarm variable as reported by the DC power system controller temperature alarm group
1.3.6.1.4.1.7309.4.1.5.6.2.1.4DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysTempAlrmSeverity
OBJECT-TYPE
The integer value of alarm severity level of the extra variable as reported by the DC power system controller temperature alarm group
1.3.6.1.4.1.7309.4.1.5.6.2.1.5INTEGER (0..65535)read-onlycurrent
dcPwrSysCustomAlrmTbl
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.5.7
dcPwrSysCustomAlrmCount
OBJECT-TYPE
Number of custom alarm variables in system controller alarm table
1.3.6.1.4.1.7309.4.1.5.7.1INTEGER (0..65535)read-onlycurrent
dcPwrSysCustomAlrmTable
OBJECT-TYPE
A table of DC power system controller custom alarm variables
1.3.6.1.4.1.7309.4.1.5.7.2not-accessiblecurrent
dcPwrSysCustomAlrmEntry
OBJECT-TYPE
An entry into the DC power system controller custom alarm group
1.3.6.1.4.1.7309.4.1.5.7.2.1not-accessiblecurrent
dcPwrSysCustomAlrmIndex
OBJECT-TYPE
The index of the alarm variable in the DC power system controller table custom alarm group
1.3.6.1.4.1.7309.4.1.5.7.2.1.1INTEGER (0..65535)read-onlycurrent
dcPwrSysCustomAlrmName
OBJECT-TYPE
The description of the alarm variable as reported by the DC power system controller custom alarm group
1.3.6.1.4.1.7309.4.1.5.7.2.1.2DisplayString (SIZE(0..30))read-onlycurrent
dcPwrSysCustomAlrmIntegerValue
OBJECT-TYPE
The integer value of the alarm variable as reported by the DC power system controller custom alarm group
1.3.6.1.4.1.7309.4.1.5.7.2.1.3INTEGER (-1000000000..1000000000)read-onlycurrent
dcPwrSysCustomAlrmStringValue
OBJECT-TYPE
The string value of the alarm variable as reported by the DC power system controller custom alarm group
1.3.6.1.4.1.7309.4.1.5.7.2.1.4DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysCustomAlrmSeverity
OBJECT-TYPE
The integer value of alarm severity level of the extra variable as reported by the DC power system controller custom alarm group
1.3.6.1.4.1.7309.4.1.5.7.2.1.5INTEGER (0..65535)read-onlycurrent
dcPwrSysMiscAlrmTbl
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.5.8
dcPwrSysMiscAlrmCount
OBJECT-TYPE
Number of misc alarm variables in system controller alarm table
1.3.6.1.4.1.7309.4.1.5.8.1INTEGER (0..65535)read-onlycurrent
dcPwrSysMiscAlrmTable
OBJECT-TYPE
A table of DC power system controller misc alarm variables
1.3.6.1.4.1.7309.4.1.5.8.2not-accessiblecurrent
dcPwrSysMiscAlrmEntry
OBJECT-TYPE
An entry into the DC power system controller misc alarm group
1.3.6.1.4.1.7309.4.1.5.8.2.1not-accessiblecurrent
dcPwrSysMiscAlrmIndex
OBJECT-TYPE
The index of the alarm variable in the DC power system controller table misc alarm group
1.3.6.1.4.1.7309.4.1.5.8.2.1.1INTEGER (0..65535)read-onlycurrent
dcPwrSysMiscAlrmName
OBJECT-TYPE
The description of the alarm variable as reported by the DC power system controller misc alarm group
1.3.6.1.4.1.7309.4.1.5.8.2.1.2DisplayString (SIZE(0..30))read-onlycurrent
dcPwrSysMiscAlrmIntegerValue
OBJECT-TYPE
The integer value of the alarm variable as reported by the DC power system controller misc alarm group
1.3.6.1.4.1.7309.4.1.5.8.2.1.3INTEGER (-1000000000..1000000000)read-onlycurrent
dcPwrSysMiscAlrmStringValue
OBJECT-TYPE
The string value of the alarm variable as reported by the DC power system controller misc alarm group
1.3.6.1.4.1.7309.4.1.5.8.2.1.4DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysMiscAlrmSeverity
OBJECT-TYPE
The integer value of alarm severity level of the extra variable as reported by the DC power system controller misc alarm group
1.3.6.1.4.1.7309.4.1.5.8.2.1.5INTEGER (0..65535)read-onlycurrent
dcPwrSysCtrlAlrmTbl
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.5.9
dcPwrSysCtrlAlrmCount
OBJECT-TYPE
Number of control alarm variables in system controller alarm table
1.3.6.1.4.1.7309.4.1.5.9.1INTEGER (0..65535)read-onlycurrent
dcPwrSysCtrlAlrmTable
OBJECT-TYPE
A table of DC power system controller control alarm variables
1.3.6.1.4.1.7309.4.1.5.9.2not-accessiblecurrent
dcPwrSysCtrlAlrmEntry
OBJECT-TYPE
An entry into the DC power system controller control alarm group
1.3.6.1.4.1.7309.4.1.5.9.2.1not-accessiblecurrent
dcPwrSysCtrlAlrmIndex
OBJECT-TYPE
The index of the alarm variable in the DC power system controller table control alarm group
1.3.6.1.4.1.7309.4.1.5.9.2.1.1INTEGER (0..65535)read-onlycurrent
dcPwrSysCtrlAlrmName
OBJECT-TYPE
The description of the alarm variable as reported by the DC power system controller control alarm group
1.3.6.1.4.1.7309.4.1.5.9.2.1.2DisplayString (SIZE(0..30))read-onlycurrent
dcPwrSysCtrlAlrmIntegerValue
OBJECT-TYPE
The integer value of the alarm variable as reported by the DC power system controller control alarm group
1.3.6.1.4.1.7309.4.1.5.9.2.1.3INTEGER (-1000000000..1000000000)read-onlycurrent
dcPwrSysCtrlAlrmStringValue
OBJECT-TYPE
The string value of the alarm variable as reported by the DC power system controller control alarm group
1.3.6.1.4.1.7309.4.1.5.9.2.1.4DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysCtrlAlrmSeverity
OBJECT-TYPE
The integer value of alarm severity level of the extra variable as reported by the DC power system controller control alarm group
1.3.6.1.4.1.7309.4.1.5.9.2.1.5INTEGER (0..65535)read-onlycurrent
dcPwrSysAdioAlrmTbl
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.5.10
dcPwrSysAdioAlrmCount
OBJECT-TYPE
Number of control alarm variables in Adio alarm table
1.3.6.1.4.1.7309.4.1.5.10.1INTEGER (0..65535)read-onlycurrent
dcPwrSysAdioAlrmTable
OBJECT-TYPE
A table of DC power system controller Adio alarm variables
1.3.6.1.4.1.7309.4.1.5.10.2not-accessiblecurrent
dcPwrSysAdioAlrmEntry
OBJECT-TYPE
An entry into the DC power system controller Adio alarm group
1.3.6.1.4.1.7309.4.1.5.10.2.1not-accessiblecurrent
dcPwrSysAdioAlrmIndex
OBJECT-TYPE
The index of the alarm variable in the DC power system controller table Adio alarm group
1.3.6.1.4.1.7309.4.1.5.10.2.1.1INTEGER (0..65535)read-onlycurrent
dcPwrSysAdioAlrmName
OBJECT-TYPE
The description of the alarm variable as reported by the DC power system controller Adio alarm group
1.3.6.1.4.1.7309.4.1.5.10.2.1.2DisplayString (SIZE(0..30))read-onlycurrent
dcPwrSysAdioAlrmIntegerValue
OBJECT-TYPE
The integer value of the alarm variable as reported by the DC power system controller Adio alarm group
1.3.6.1.4.1.7309.4.1.5.10.2.1.3INTEGER (-1000000000..1000000000)read-onlycurrent
dcPwrSysAdioAlrmStringValue
OBJECT-TYPE
The string value of the alarm variable as reported by the DC power system controller Adio alarm group
1.3.6.1.4.1.7309.4.1.5.10.2.1.4DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysAdioAlrmSeverity
OBJECT-TYPE
The integer value of alarm severity level of the extra variable as reported by the DC Adio system controller control alarm group
1.3.6.1.4.1.7309.4.1.5.10.2.1.5INTEGER (0..65535)read-onlycurrent
dcPwrSysConvAlrmTbl
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.5.11
dcPwrSysConvAlrmCount
OBJECT-TYPE
Number of Converter alarm variables in system controller alarm table
1.3.6.1.4.1.7309.4.1.5.11.1INTEGER (0..65535)read-onlycurrent
dcPwrSysConvAlrmTable
OBJECT-TYPE
A table of DC power system controller Converter alarm variables
1.3.6.1.4.1.7309.4.1.5.11.2not-accessiblecurrent
dcPwrSysConvAlrmEntry
OBJECT-TYPE
An entry into the DC power system controller Converter alarm group
1.3.6.1.4.1.7309.4.1.5.11.2.1not-accessiblecurrent
dcPwrSysConvAlrmIndex
OBJECT-TYPE
The index of the alarm variable in the DC power system controller table Converter alarm group
1.3.6.1.4.1.7309.4.1.5.11.2.1.1INTEGER (0..65535)read-onlycurrent
dcPwrSysConvAlrmName
OBJECT-TYPE
The description of the alarm variable as reported by the DC power system controller Converter alarm group
1.3.6.1.4.1.7309.4.1.5.11.2.1.2DisplayString (SIZE(0..30))read-onlycurrent
dcPwrSysConvAlrmIntegerValue
OBJECT-TYPE
The integer value of the alarm variable as reported by the DC power system controller Converter alarm group
1.3.6.1.4.1.7309.4.1.5.11.2.1.3INTEGER (-1000000000..1000000000)read-onlycurrent
dcPwrSysConvAlrmStringValue
OBJECT-TYPE
The string value of the alarm variable as reported by the DC power system controller Converter alarm group
1.3.6.1.4.1.7309.4.1.5.11.2.1.4DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysConvAlrmSeverity
OBJECT-TYPE
The integer value of alarm severity level of the extra variable as reported by the DC power system controller Converter alarm group
1.3.6.1.4.1.7309.4.1.5.11.2.1.5INTEGER (0..65535)read-onlycurrent
dcPwrSysInputsTbl
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.6
dcPwrSysDigIpTbl
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.6.1
dcPwrSysDigIpCount
OBJECT-TYPE
Number of digital input variables in system controller digital input table
1.3.6.1.4.1.7309.4.1.6.1.1INTEGER (0..65535)read-onlycurrent
dcPwrSysDigIpTable
OBJECT-TYPE
A table of DC power system controller digital input variables
1.3.6.1.4.1.7309.4.1.6.1.2not-accessiblecurrent
dcPwrSysDigIpEntry
OBJECT-TYPE
An entry into the DC power system controller digital input group
1.3.6.1.4.1.7309.4.1.6.1.2.1not-accessiblecurrent
dcPwrSysDigIpIndex
OBJECT-TYPE
The index of the digital input variable in the DC power system controller table digital input group
1.3.6.1.4.1.7309.4.1.6.1.2.1.1INTEGER (0..65535)read-onlycurrent
dcPwrSysDigIpName
OBJECT-TYPE
The description of the digital input variable as reported by the DC power system controller digital input group
1.3.6.1.4.1.7309.4.1.6.1.2.1.2DisplayString (SIZE(0..30))read-onlycurrent
dcPwrSysDigIpIntegerValue
OBJECT-TYPE
The integer value of the digital input variable as reported by the DC power system controller digital input group
1.3.6.1.4.1.7309.4.1.6.1.2.1.3INTEGER (-1000000000..1000000000)read-onlycurrent
dcPwrSysDigIpStringValue
OBJECT-TYPE
The string value of the digital input variable as reported by the DC power system controller digital input group
1.3.6.1.4.1.7309.4.1.6.1.2.1.4DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysCntrlrIpTbl
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.6.2
dcPwrSysCntrlrIpCount
OBJECT-TYPE
Number of controller input variables in system controller controller input table
1.3.6.1.4.1.7309.4.1.6.2.1INTEGER (0..65535)read-onlycurrent
dcPwrSysCntrlrIpTable
OBJECT-TYPE
A table of DC power system controller controller input variables
1.3.6.1.4.1.7309.4.1.6.2.2not-accessiblecurrent
dcPwrSysCntrlrIpEntry
OBJECT-TYPE
An entry into the DC power system controller controller input group
1.3.6.1.4.1.7309.4.1.6.2.2.1not-accessiblecurrent
dcPwrSysCntrlrIpIndex
OBJECT-TYPE
The index of the controller input variable in the DC power system controller table controller input group
1.3.6.1.4.1.7309.4.1.6.2.2.1.1INTEGER (0..65535)read-onlycurrent
dcPwrSysCntrlrIpName
OBJECT-TYPE
The description of the controller input variable as reported by the DC power system controller controller input group
1.3.6.1.4.1.7309.4.1.6.2.2.1.2DisplayString (SIZE(0..30))read-onlycurrent
dcPwrSysCntrlrIpIntegerValue
OBJECT-TYPE
The integer value of the controller input variable as reported by the DC power system controller controller input group
1.3.6.1.4.1.7309.4.1.6.2.2.1.3INTEGER (-1000000000..1000000000)read-onlycurrent
dcPwrSysCntrlrIpStringValue
OBJECT-TYPE
The string value of the controller input variable as reported by the DC power system controller controller input group
1.3.6.1.4.1.7309.4.1.6.2.2.1.4DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysRectIpTbl
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.6.3
dcPwrSysRectIpCount
OBJECT-TYPE
Number of rectifier input variables in system controller rectifier input table
1.3.6.1.4.1.7309.4.1.6.3.1INTEGER (0..65535)read-onlycurrent
dcPwrSysRectIpTable
OBJECT-TYPE
A table of DC power system controller rectifier input variables
1.3.6.1.4.1.7309.4.1.6.3.2not-accessiblecurrent
dcPwrSysRectIpEntry
OBJECT-TYPE
An entry into the DC power system controller rectifier input group
1.3.6.1.4.1.7309.4.1.6.3.2.1not-accessiblecurrent
dcPwrSysRectIpIndex
OBJECT-TYPE
The index of the rectifier input variable in the DC power system controller table rectifier input group
1.3.6.1.4.1.7309.4.1.6.3.2.1.1INTEGER (0..65535)read-onlycurrent
dcPwrSysRectIpName
OBJECT-TYPE
The description of the rectifier input variable as reported by the DC power system controller rectifier input group
1.3.6.1.4.1.7309.4.1.6.3.2.1.2DisplayString (SIZE(0..30))read-onlycurrent
dcPwrSysRectIpIntegerValue
OBJECT-TYPE
The integer value of the rectifier input variable as reported by the DC power system controller rectifier input group
1.3.6.1.4.1.7309.4.1.6.3.2.1.3INTEGER (-1000000000..1000000000)read-onlycurrent
dcPwrSysRectIpStringValue
OBJECT-TYPE
The string value of the rectifier input variable as reported by the DC power system controller rectifier input group
1.3.6.1.4.1.7309.4.1.6.3.2.1.4DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysCustomIpTbl
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.6.4
dcPwrSysCustomIpCount
OBJECT-TYPE
Number of custom input variables in system controller custom input table
1.3.6.1.4.1.7309.4.1.6.4.1INTEGER (0..65535)read-onlycurrent
dcPwrSysCustomIpTable
OBJECT-TYPE
A table of DC power system controller digital custom variables
1.3.6.1.4.1.7309.4.1.6.4.2not-accessiblecurrent
dcPwrSysCustomIpEntry
OBJECT-TYPE
An entry into the DC power system controller custom input group
1.3.6.1.4.1.7309.4.1.6.4.2.1not-accessiblecurrent
dcPwrSysCustomIpIndex
OBJECT-TYPE
The index of the custom input variable in the DC power system controller table custom input group
1.3.6.1.4.1.7309.4.1.6.4.2.1.1INTEGER (0..65535)read-onlycurrent
dcPwrSysCustomIpName
OBJECT-TYPE
The description of the custom input variable as reported by the DC power system controller custom input group
1.3.6.1.4.1.7309.4.1.6.4.2.1.2DisplayString (SIZE(0..30))read-onlycurrent
dcPwrSysgCustomIpIntegerValue
OBJECT-TYPE
The integer value of the custom input variable as reported by the DC power system controller custom input group
1.3.6.1.4.1.7309.4.1.6.4.2.1.3INTEGER (-1000000000..1000000000)read-onlycurrent
dcPwrSysCustomIpStringValue
OBJECT-TYPE
The string value of the custom input variable as reported by the DC power system controller custom input group
1.3.6.1.4.1.7309.4.1.6.4.2.1.4DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysConvIpTbl
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.6.5
dcPwrSysConvIpCount
OBJECT-TYPE
Number of Converter input variables in system controller Converter input table
1.3.6.1.4.1.7309.4.1.6.5.1INTEGER (0..65535)read-onlycurrent
dcPwrSysConvIpTable
OBJECT-TYPE
A table of DC power system controller Converter input variables
1.3.6.1.4.1.7309.4.1.6.5.2not-accessiblecurrent
dcPwrSysConvIpEntry
OBJECT-TYPE
An entry into the DC power system controller Converter input group
1.3.6.1.4.1.7309.4.1.6.5.2.1not-accessiblecurrent
dcPwrSysConvIpIndex
OBJECT-TYPE
The index of the Converter input variable in the DC power system controller table Converter input group
1.3.6.1.4.1.7309.4.1.6.5.2.1.1INTEGER (0..65535)read-onlycurrent
dcPwrSysConvIpName
OBJECT-TYPE
The description of the Converter input variable as reported by the DC power system controller Converter input group
1.3.6.1.4.1.7309.4.1.6.5.2.1.2DisplayString (SIZE(0..30))read-onlycurrent
dcPwrSysConvIpIntegerValue
OBJECT-TYPE
The integer value of the Converter input variable as reported by the DC power system controller Converter input group
1.3.6.1.4.1.7309.4.1.6.5.2.1.3INTEGER (-1000000000..1000000000)read-onlycurrent
dcPwrSysConvIpStringValue
OBJECT-TYPE
The string value of the Converter input variable as reported by the DC power system controller Converter input group
1.3.6.1.4.1.7309.4.1.6.5.2.1.4DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysTimerIpTbl
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.6.6
dcPwrSysTimerIpCount
OBJECT-TYPE
Number of Timererter input variables in system controller Timererter input table
1.3.6.1.4.1.7309.4.1.6.6.1INTEGER (0..65535)read-onlycurrent
dcPwrSysTimerIpTable
OBJECT-TYPE
A table of DC power system controller Timererter input variables
1.3.6.1.4.1.7309.4.1.6.6.2not-accessiblecurrent
dcPwrSysTimerIpEntry
OBJECT-TYPE
An entry into the DC power system controller Timererter input group
1.3.6.1.4.1.7309.4.1.6.6.2.1not-accessiblecurrent
dcPwrSysTimerIpIndex
OBJECT-TYPE
The index of the Timererter input variable in the DC power system controller table Timererter input group
1.3.6.1.4.1.7309.4.1.6.6.2.1.1INTEGER (0..65535)read-onlycurrent
dcPwrSysTimerIpName
OBJECT-TYPE
The description of the Timererter input variable as reported by the DC power system controller Timererter input group
1.3.6.1.4.1.7309.4.1.6.6.2.1.2DisplayString (SIZE(0..30))read-onlycurrent
dcPwrSysTimerIpIntegerValue
OBJECT-TYPE
The integer value of the Timererter input variable as reported by the DC power system controller Timererter input group
1.3.6.1.4.1.7309.4.1.6.6.2.1.3INTEGER (-1000000000..1000000000)read-onlycurrent
dcPwrSysTimerIpStringValue
OBJECT-TYPE
The string value of the Timererter input variable as reported by the DC power system controller Timererter input group
1.3.6.1.4.1.7309.4.1.6.6.2.1.4DisplayString (SIZE(0..255))read-onlycurrent
dcPwrSysCounterIpTbl
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.6.7
dcPwrSysCounterIpCount
OBJECT-TYPE
Number of Countererter input variables in system controller Countererter input table
1.3.6.1.4.1.7309.4.1.6.7.1INTEGER (0..65535)read-onlycurrent
dcPwrSysCounterIpTable
OBJECT-TYPE
A table of DC power system controller Countererter input variables
1.3.6.1.4.1.7309.4.1.6.7.2not-accessiblecurrent
dcPwrSysCounterIpEntry
OBJECT-TYPE
An entry into the DC power system controller Countererter input group
1.3.6.1.4.1.7309.4.1.6.7.2.1not-accessiblecurrent
dcPwrSysCounterIpIndex
OBJECT-TYPE
The index of the Countererter input variable in the DC power system controller table Countererter input group
1.3.6.1.4.1.7309.4.1.6.7.2.1.1INTEGER (0..65535)read-onlycurrent
dcPwrSysCounterIpName
OBJECT-TYPE
The description of the Countererter input variable as reported by the DC power system controller Countererter input group
1.3.6.1.4.1.7309.4.1.6.7.2.1.2DisplayString (SIZE(0..30))read-onlycurrent
dcPwrSysCounterIpIntegerValue
OBJECT-TYPE
The integer value of the Countererter input variable as reported by the DC power system controller Countererter input group
1.3.6.1.4.1.7309.4.1.6.7.2.1.3INTEGER (-1000000000..1000000000)read-onlycurrent
dcPwrSysCounterIpStringValue
OBJECT-TYPE
The string value of the Countererter input variable as reported by the DC power system controller Countererter input group
1.3.6.1.4.1.7309.4.1.6.7.2.1.4DisplayString (SIZE(0..255))read-onlycurrent
dcPwrExternalControls
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.8
dcPwrSysResyncAlarms
OBJECT-TYPE
Send/Resend all active alarms that were previously sent through SNMP notification.
1.3.6.1.4.1.7309.4.1.8.1INTEGER (0..65535)read-writecurrent
dcPwrVarbindNameReference
OBJECT-IDENTITY
1.3.6.1.4.1.7309.4.1.9
dcPwrSysAlarmTriggerValue
OBJECT-TYPE
1.3.6.1.4.1.7309.4.1.9.1INTEGER (0..65535)read-onlycurrent
dcPwrSysTimeStamp
OBJECT-TYPE
1.3.6.1.4.1.7309.4.1.9.2DisplayString (SIZE(0..255))read-onlycurrent

Notifications

NameOIDStatus
dcPwrSysAlarmActiveTrap
NOTIFICATION-TYPE
A trap issued when one of the alarms on the DC power system controller became active
1.3.6.1.4.1.7309.4.1.3.0.1current
dcPwrSysAlarmClearedTrap
NOTIFICATION-TYPE
A trap issued when one of the active alarms on the DC power system controller is cleared
1.3.6.1.4.1.7309.4.1.3.0.2current
dcPwrSysRelayTrap
NOTIFICATION-TYPE
A trap issued from a change in state in one of the relays on the DC power system controller
1.3.6.1.4.1.7309.4.1.3.0.3current
dcPwrSysComOKTrap
NOTIFICATION-TYPE
A trap to indicate that communications with a DC power system controller has been established.
1.3.6.1.4.1.7309.4.1.3.0.4current
dcPwrSysComErrTrap
NOTIFICATION-TYPE
A trap to indicate that communications with a DC power system controller has been lost.
1.3.6.1.4.1.7309.4.1.3.0.5current
dcPwrSysAgentStartupTrap
NOTIFICATION-TYPE
A trap to indicate that the agent software has started up.
1.3.6.1.4.1.7309.4.1.3.0.6current
dcPwrSysAgentShutdownTrap
NOTIFICATION-TYPE
A trap to indicate that the agent software has shutdown.
1.3.6.1.4.1.7309.4.1.3.0.7current
dcPwrSysMajorAlarmActiveTrap
NOTIFICATION-TYPE
A trap issued as a summary of DC power system status. It is sent when the system goes into in Major Alarm
1.3.6.1.4.1.7309.4.1.3.0.8current
dcPwrSysMajorAlarmClearedTrap
NOTIFICATION-TYPE
A trap issued as a summary of DC power system status. It is sent when the system comes out of Major Alarm
1.3.6.1.4.1.7309.4.1.3.0.9current
dcPwrSysMinorAlarmActiveTrap
NOTIFICATION-TYPE
A trap issued as a summary of DC power system status. It is sent when the system goes into in Minor Alarm
1.3.6.1.4.1.7309.4.1.3.0.10current
dcPwrSysMinorAlarmClearedTrap
NOTIFICATION-TYPE
A trap issued as a summary of DC power system status. It is sent when the system comes out of Minor Alarm
1.3.6.1.4.1.7309.4.1.3.0.11current