MIBs Depot

ATEN-PE-CFG

Registered at
1.3.6.1.4.1.21317
Last updated
2013-10-31 11:10
Organization
ATEN
Revisions
2013-10-31 11:10
Namespace
aten
Source file
ATEN-PE-CFG
Digest
sha256:05d1fd32028eb4460ae91399caef58bd0d6091af7f370b11532a2f68b6031e4d

Description

ATEN PE MIB

Contact

Aten, Inc.

Imports

FromSymbols
SNMP-USER-BASED-SM-MIBKeyChange
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP
SNMPv2-SMIGauge32, IpAddress, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, TimeTicks, enterprises, iso
SNMPv2-TCDisplayString, TEXTUAL-CONVENTION

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

ATEN-PE-CFG
SNMP-FRAMEWORK-MIB
SNMP-USER-BASED-SM-MIB
SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC

Objects

NameOIDSyntaxAccessStatus
atenProducts
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1
overip
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3
poweroverip
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2
pe
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2
userManagement
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.1
usrListTable
OBJECT-TYPE
A list of user. The number of user is given by the value of usrcfgNumber.
1.3.6.1.4.1.21317.1.3.2.2.1.1not-accessiblecurrent
usrListEntry
OBJECT-TYPE
Status and parameter values for a pe8208 user.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1not-accessiblecurrent
usrIndex
OBJECT-TYPE
The value of usrIndex for the user. We have 1 administrator and 8 users. The index 9 will be the administrator.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.1INTEGER (1..9)read-onlycurrent
usrType
OBJECT-TYPE
The user's type.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.2INTEGER {administrator(1), user(2)}read-onlycurrent
usrName
OBJECT-TYPE
A textual string containing name of the user. string length: 1~16
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.3DisplayString (SIZE(1..16))read-writecurrent
usrPassword
OBJECT-TYPE
A textual string containing password of the user. string length: 1~16
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.4DisplayString (SIZE(1..16))read-writecurrent
usrPort1Auth
OBJECT-TYPE
Display or set this user's outlet 1 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.5INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort2Auth
OBJECT-TYPE
Display or set this user's outlet 2 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.6INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort3Auth
OBJECT-TYPE
Display or set this user's outlet 3 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.7INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort4Auth
OBJECT-TYPE
Display or set this user's outlet 4 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.8INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort5Auth
OBJECT-TYPE
Display or set this user's outlet 5 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.9INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort6Auth
OBJECT-TYPE
Dispaly or set this user's outlet 6 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.10INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort7Auth
OBJECT-TYPE
Display or set this user's outlet 7 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.11INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort8Auth
OBJECT-TYPE
Display or set this user's outlet 8 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.12INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort9Auth
OBJECT-TYPE
Display or set this user's outlet 9 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.13INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort10Auth
OBJECT-TYPE
Display or set this user's outlet 10 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.14INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort11Auth
OBJECT-TYPE
Display or set this user's outlet 11 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.15INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort12Auth
OBJECT-TYPE
Display or set this user's outlet 12 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.16INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort13Auth
OBJECT-TYPE
Display or set this user's outlet 13 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.17INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort14Auth
OBJECT-TYPE
Display or set this user's outlet 14 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.18INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort15Auth
OBJECT-TYPE
Display or set this user's outlet 15 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.19INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort16Auth
OBJECT-TYPE
Display or set this user's outlet 16 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.20INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort17Auth
OBJECT-TYPE
Display or set this user's outlet 17 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.21INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort18Auth
OBJECT-TYPE
Display or set this user's outlet 18 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.22INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort19Auth
OBJECT-TYPE
Display or set this user's outlet 19 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.23INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort20Auth
OBJECT-TYPE
Display or set this user's outlet 20 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.24INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort21Auth
OBJECT-TYPE
Display or set this user's outlet 21 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.25INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort22Auth
OBJECT-TYPE
Display or set this user's outlet 22 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.26INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort23Auth
OBJECT-TYPE
Display or set this user's outlet 23 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.27INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort24Auth
OBJECT-TYPE
Display or set this user's outlet 24 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.28INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort25Auth
OBJECT-TYPE
Display or set this user's outlet 25 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.29INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort26Auth
OBJECT-TYPE
Display or set this user's outlet 26 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.30INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort27Auth
OBJECT-TYPE
Display or set this user's outlet 27 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.31INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort28Auth
OBJECT-TYPE
Display or set this user's outlet 28 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.32INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort29Auth
OBJECT-TYPE
Display or set this user's outlet 29 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.33INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort30Auth
OBJECT-TYPE
Display or set this user's outlet 30 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.34INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort31Auth
OBJECT-TYPE
Display or set this user's outlet 31 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.35INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort32Auth
OBJECT-TYPE
Display or set this user's outlet 32 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.36INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort33Auth
OBJECT-TYPE
Display or set this user's outlet 33 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.37INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort34Auth
OBJECT-TYPE
Display or set this user's outlet 34 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.38INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort35Auth
OBJECT-TYPE
Display or set this user's outlet 35 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.39INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort36Auth
OBJECT-TYPE
Display or set this user's outlet 36 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.40INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort37Auth
OBJECT-TYPE
Display or set this user's outlet 37 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.41INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort38Auth
OBJECT-TYPE
Display or set this user's outlet 38 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.42INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort39Auth
OBJECT-TYPE
Display or set this user's outlet 39 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.43INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort40Auth
OBJECT-TYPE
Display or set this user's outlet 40 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.44INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort41Auth
OBJECT-TYPE
Display or set this user's outlet 41 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.45INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrPort42Auth
OBJECT-TYPE
Display or set this user's outlet 42 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu.
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.46INTEGER {disable(1), view(2), modify(3), not-support(4)}read-writecurrent
usrEnable
OBJECT-TYPE
Display or set this user is enable or not
1.3.6.1.4.1.21317.1.3.2.2.1.1.1.47INTEGER {disable(1), enable(2)}read-writecurrent
control
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.2
device
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.2.1
modelName
OBJECT-TYPE
Indicate PE device model name.
1.3.6.1.4.1.21317.1.3.2.2.2.1.1DisplayStringread-onlycurrent
deviceName
OBJECT-TYPE
The name of PE device. string length: 1~39 NOTE: Input string as /empty to set this object to NULL.
1.3.6.1.4.1.21317.1.3.2.2.2.1.2DisplayStringread-writecurrent
deviceValueTable
OBJECT-TYPE
Device value table. This table displays device's current, voltage, power and power dissipation.
1.3.6.1.4.1.21317.1.3.2.2.2.1.3not-accessiblecurrent
deviceValueEntry
OBJECT-TYPE
Single deviceValue entry containing device info.
1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1not-accessiblecurrent
deviceValueIndex
OBJECT-TYPE
Index of deviceValue.
1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.1INTEGER (1)read-onlycurrent
inputMaxVoltage
OBJECT-TYPE
Device input Voltage value. unit:(V) If the device does not support this OID, we show value 0.
1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.6INTEGERread-onlycurrent
inputMaxCurrent
OBJECT-TYPE
Device input Current value. unit:(A) If the device does not support this OID, we show value 0.
1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.7INTEGERread-onlycurrent
powerCapacity
OBJECT-TYPE
Device power Capacity value.unit:(VA) If the device does not support this OID, we show value 0.
1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.8INTEGERread-onlycurrent
devicePowerFactor
OBJECT-TYPE
Device power Factor value. If the device does not support this OID, it returns: not-support.
1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.9DisplayStringread-onlycurrent
deviceOutletStatusTable
OBJECT-TYPE
Device outlet status value table.
1.3.6.1.4.1.21317.1.3.2.2.2.1.5not-accessiblecurrent
deviceOutletStatusEntry
OBJECT-TYPE
Single deviceOutletStatus entry containing device info.
1.3.6.1.4.1.21317.1.3.2.2.2.1.5.1not-accessiblecurrent
deviceOutletStatusIndex
OBJECT-TYPE
Index of deviceOutletStatus
1.3.6.1.4.1.21317.1.3.2.2.2.1.5.1.1INTEGER (1..30)read-onlycurrent
displayOutletStatus
OBJECT-TYPE
Display outlet status.
1.3.6.1.4.1.21317.1.3.2.2.2.1.5.1.2INTEGER {off(1), on(2), pending(3), fault(4), noauth(5), not-support(6), pop(7)}read-onlycurrent
deviceConfigTable
OBJECT-TYPE
Device configuration table
1.3.6.1.4.1.21317.1.3.2.2.2.1.6not-accessiblecurrent
deviceConfigEntry
OBJECT-TYPE
Single deviceConfig entry containing device info.
1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1not-accessiblecurrent
deviceConfigIndex
OBJECT-TYPE
Index of deviceConfig
1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.1INTEGER (1)read-onlycurrent
deviceMinCurMT
OBJECT-TYPE
Display or set device minimum electric current measurement threshold. Example: range 0.0~32.0 represents 0~320. NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.2INTEGERread-writecurrent
deviceMaxCurMT
OBJECT-TYPE
Display or set device maximum electric current measurement threshold. Example: range 0.0~32.0 represents 0~320 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.3INTEGERread-writecurrent
deviceMinVolMT
OBJECT-TYPE
Display or set device minimum voltage measurement threshold. Exapmple: range 90.0~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.4INTEGER (900..2600 | -3000)read-writecurrent
deviceMaxVolMT
OBJECT-TYPE
Display or set device maximum voltage measurement threshold. Example: range 90.0~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.5INTEGER (900..2600 | -3000)read-writecurrent
deviceMinPMT
OBJECT-TYPE
Display or set device minimum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.6INTEGER (0..99999 | -3000)read-writecurrent
deviceMaxPMT
OBJECT-TYPE
Display or set device maximum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.7INTEGER (0..99999 | -3000)read-writecurrent
deviceMaxPDMT
OBJECT-TYPE
Display or set device maximum power dissipation measurement threshold. Example: range 0.0 ~ 99999.0 represents 0~999990 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.8INTEGER (0..999990 | -3000)read-writecurrent
deviceSensorTresholdTable
OBJECT-TYPE
Device environment value table
1.3.6.1.4.1.21317.1.3.2.2.2.1.7not-accessiblecurrent
deviceSensorTresholdEntry
OBJECT-TYPE
Device's sensor Environment entry containing sensor info.
1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1not-accessiblecurrent
deviceSensorTresholdIndex
OBJECT-TYPE
Index of sensor number
1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.1INTEGER (1..6)read-onlycurrent
sensorMinTempMT
OBJECT-TYPE
Display or set sensor minimum temperature measurement threshold. Example: range -20.0 ~ 60.0 represents -200~600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.2INTEGER (-200..600 | -3000)read-writecurrent
sensorMaxTempMT
OBJECT-TYPE
Display or set sensor maximum temperature measurement threshold. Example: range -20.0 ~ 60.0 represents -200~600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.3INTEGER (-200..600 | -3000)read-writecurrent
sensorMinHumMT
OBJECT-TYPE
Display or set sensor minimum humidity measurement threshold. Example: range 15.0 ~ 95.0 represents 150~950 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.4INTEGER (150..950 | -3000)read-writecurrent
sensorMaxHumMT
OBJECT-TYPE
Display or set sensor maximum humidity measurement threshold. Example: range 15.0 ~ 95.0 represents 150~950 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.5INTEGER (150..950 | -3000)read-writecurrent
sensorMinPressMT
OBJECT-TYPE
Display or set sensor minimum pressure measurement threshold. Example: range -250.0 ~ 250.0 represents -2500 ~ 2500 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.6INTEGER (-2500..2500 | -3000)read-writecurrent
sensorMaxPressMT
OBJECT-TYPE
Display or set sensor maximum pressure measurement threshold. Example: range -250.0 ~ 250.0 represents -2500 ~ 2500 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.7INTEGER (-2500..2500 | -3000)read-writecurrent
deviceOutletControl
OBJECT-TYPE
This function is used for all outlet ports control. Set off(1) to turn off for all outlet ports. Set on(2) to turn on for all outlet ports. Get this object always return nostatus(3), because there is no device status.
1.3.6.1.4.1.21317.1.3.2.2.2.1.8INTEGER {off(1), on(2), nostatus(3), not-support(4)}read-writecurrent
deviceOutletReboot
OBJECT-TYPE
This function is used for all outlet ports to reboot. Only when outlet status is ON can do outlet reboot action to all ports. Set yes(2) to reboot all outlet ports. Get this object always return no(1).
1.3.6.1.4.1.21317.1.3.2.2.2.1.9INTEGER {no(1), yes(2), not-support(4)}read-writecurrent
switchable
OBJECT-TYPE
Outlet is switchable or not.
1.3.6.1.4.1.21317.1.3.2.2.2.1.10INTEGER {no(1), yes(2), mix(3)}read-onlycurrent
perportreading
OBJECT-TYPE
Outlet is per-port reading or not.
1.3.6.1.4.1.21317.1.3.2.2.2.1.11INTEGER {no(1), yes(2)}read-onlycurrent
sensornumber
OBJECT-TYPE
Sensor number.
1.3.6.1.4.1.21317.1.3.2.2.2.1.12INTEGERread-onlycurrent
outletnumber
OBJECT-TYPE
Outlet number.
1.3.6.1.4.1.21317.1.3.2.2.2.1.13INTEGERread-onlycurrent
banknumber
OBJECT-TYPE
Bank number.
1.3.6.1.4.1.21317.1.3.2.2.2.1.14INTEGERread-onlycurrent
doorSensor
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.2.1.16
doorSensorStatus
OBJECT-TYPE
Display door sensor status. close(0) represents door close. open(1) represents door open. not-attached(2) represents door sensor don't attach to device.
1.3.6.1.4.1.21317.1.3.2.2.2.1.16.1INTEGER {close(0), open(1), not-attached(2), not-support(4)}read-onlycurrent
doorSensorType
OBJECT-TYPE
Door Sensor Type Selection
1.3.6.1.4.1.21317.1.3.2.2.2.1.16.2INTEGER {notinstalled(0), photo(1), inductiveproximity(2), reed(3)}read-writecurrent
pop
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.2.1.17
enablePOPmode
OBJECT-TYPE
Enable/Disable POP mode.
1.3.6.1.4.1.21317.1.3.2.2.2.1.17.1INTEGER {no(1), yes(2)}read-writecurrent
popThreshold
OBJECT-TYPE
(-1)means default value same as Bank Max Current 16 A. Example: range 0.0~32.0 represents 0~320 You can define the POP threshold or set as default(-1) value.
1.3.6.1.4.1.21317.1.3.2.2.2.1.17.2INTEGERread-writecurrent
enableOutletPOPmode
OBJECT-TYPE
Enable/Disable Outlet POP mode.
1.3.6.1.4.1.21317.1.3.2.2.2.1.17.3INTEGER {no(1), yes(2), not-support(3)}read-writecurrent
enableLIFOPOPmode
OBJECT-TYPE
Enable/Disable LIFO POP mode.
1.3.6.1.4.1.21317.1.3.2.2.2.1.17.4INTEGER {no(1), yes(2), not-support(3)}read-writecurrent
enablePriorityPOPmode
OBJECT-TYPE
Enable/Disable Priority POP mode.
1.3.6.1.4.1.21317.1.3.2.2.2.1.17.5INTEGER {no(1), yes(2), not-support(3)}read-writecurrent
cap
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.2.1.18
enableCAPmode
OBJECT-TYPE
Enable/Disable CAP mode.
1.3.6.1.4.1.21317.1.3.2.2.2.1.18.1INTEGER {no(1), yes(2)}read-writecurrent
outletCAPTable
OBJECT-TYPE
Outlet CAP table
1.3.6.1.4.1.21317.1.3.2.2.2.1.18.2not-accessiblecurrent
outletCAPEntry
OBJECT-TYPE
Outlet CAP entry containing CAP info.
1.3.6.1.4.1.21317.1.3.2.2.2.1.18.2.1not-accessiblecurrent
outletCAPIndex
OBJECT-TYPE
Index of outlet's CAP configuration
1.3.6.1.4.1.21317.1.3.2.2.2.1.18.2.1.1INTEGER (1..40)read-onlycurrent
outletCAPPriority
OBJECT-TYPE
Display or set the CAP Priority of outlet. Priority 0 means this outlet does not support this OID.
1.3.6.1.4.1.21317.1.3.2.2.2.1.18.2.1.2INTEGER (0..99)read-writecurrent
outletInitMode
OBJECT-TYPE
choose outlet init mode you want.
1.3.6.1.4.1.21317.1.3.2.2.2.1.19INTEGER {no-delaytime(1), delaytime(2), not-support(3)}read-writecurrent
deviceIntegerValueTable
OBJECT-TYPE
Device value table. This table displays device's current, voltage, power and power dissipation.
1.3.6.1.4.1.21317.1.3.2.2.2.1.99not-accessiblecurrent
deviceIntegerValueEntry
OBJECT-TYPE
Single deviceValue entry containing device info.
1.3.6.1.4.1.21317.1.3.2.2.2.1.99.1not-accessiblecurrent
deviceIntegerValueIndex
OBJECT-TYPE
Index of deviceValue.
1.3.6.1.4.1.21317.1.3.2.2.2.1.99.1.1INTEGER (1)read-onlycurrent
deviceIntegerCurrent
OBJECT-TYPE
Device electric current value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.1.99.1.2INTEGERread-onlycurrent
deviceIntegerVoltage
OBJECT-TYPE
Device voltage value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.1.99.1.3INTEGERread-onlycurrent
deviceIntegerPower
OBJECT-TYPE
Device power value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.1.99.1.4INTEGERread-onlycurrent
deviceIntegerPowerDissipation
OBJECT-TYPE
Device power dissipation value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.1.99.1.5INTEGERread-onlycurrent
sensorIntegerValueTable
OBJECT-TYPE
Device's sensor value table. This table displays sensor's temperature, humidity and pressure.
1.3.6.1.4.1.21317.1.3.2.2.2.1.100not-accessiblecurrent
sensorIntegerValueEntry
OBJECT-TYPE
Single device's sensor value entry containing device info.
1.3.6.1.4.1.21317.1.3.2.2.2.1.100.1not-accessiblecurrent
sensorIntegerValueIndex
OBJECT-TYPE
Index of sensor number.
1.3.6.1.4.1.21317.1.3.2.2.2.1.100.1.1INTEGER (1..6)read-onlycurrent
sensorIntegerTemperature
OBJECT-TYPE
Sensor's Temperature value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.1.100.1.2INTEGERread-onlycurrent
sensorIntegerHumidity
OBJECT-TYPE
Sensor's Humidity value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.1.100.1.3INTEGERread-onlycurrent
sensorIntegerPressure
OBJECT-TYPE
Sensor's Pressure value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.1.100.1.4INTEGERread-onlycurrent
outlet
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.2.2
outletValueTable
OBJECT-TYPE
Display total outlet value table
1.3.6.1.4.1.21317.1.3.2.2.2.2.1not-accessiblecurrent
outletValueEntry
OBJECT-TYPE
Single outletValue entry containing outlet info.
1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1not-accessiblecurrent
outletValueIndex
OBJECT-TYPE
Index of outlet number
1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.1INTEGER (1..30)read-onlycurrent
outletMaxCurrent
OBJECT-TYPE
Outlet Max Current value. unit: (A). If the device does not support this OID, we show value 0.
1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.6INTEGERread-onlycurrent
outletPowerFactor
OBJECT-TYPE
Outlet Power Factor value. If the device does not support this OID, it returns: not-support.
1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.7DisplayStringread-onlycurrent
outlet1Status
OBJECT-TYPE
Display and control outlet 1 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.2INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet2Status
OBJECT-TYPE
Display and control outlet 2 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.3INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet3Status
OBJECT-TYPE
Display and control outlet 3 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.4INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet4Status
OBJECT-TYPE
Display and control outlet 4 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.5INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet5Status
OBJECT-TYPE
Display and control outlet 5 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.6INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet6Status
OBJECT-TYPE
Display and control outlet 6 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.7INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet7Status
OBJECT-TYPE
Display and control outlet 7 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.8INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet8Status
OBJECT-TYPE
Display and control outlet 8 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.9INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outletConfigTable
OBJECT-TYPE
Outlet configuration table
1.3.6.1.4.1.21317.1.3.2.2.2.2.10not-accessiblecurrent
outletConfigEntry
OBJECT-TYPE
Outlet Config entry containing outlet info.
1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1not-accessiblecurrent
outletConfigIndex
OBJECT-TYPE
Index of outlet number
1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.1INTEGER (1..30)read-onlycurrent
outletName
OBJECT-TYPE
Display or set the name of outlet. If the device does not support this OID, we show n/a. string length: 0~15 NOTE: Input string as /empty to set this object to NULL.
1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.2DisplayStringread-writecurrent
outletConfirmation
OBJECT-TYPE
Display or set the confirmation of outlet.
1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.3INTEGER {no(1), yes(2), noauth(3), not-support(4)}read-writecurrent
outletOnDelayTime
OBJECT-TYPE
Display or set the ON delay time of outlet. When this model does not support the OID, we show value -1.
1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.4INTEGER (0..999 | -1)read-writecurrent
outletOffDelayTime
OBJECT-TYPE
Display or set the OFF delay time of outlet. When this model does not support the OID, we show value -1.
1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.5INTEGER (0..999 | -1)read-writecurrent
outletShutdownMethod
OBJECT-TYPE
Display or set the shutdown mehtod of outlet.
1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.6INTEGER {kill-the-power(1), wake-on-lan(2), after-ac-back(3), not-support(4)}read-writecurrent
outletMAC
OBJECT-TYPE
Display or set the MAC address of ShutdownMethod. If the device does not support this OID, we show n/a. string length: 12
1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.7DisplayStringread-writecurrent
outletMinCurMT
OBJECT-TYPE
Display or set the outlet minimum electric current measurment threshold. Example: range 0.0 ~16.0 rerpresnts 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.8INTEGERread-writecurrent
outletMaxCurMT
OBJECT-TYPE
Display or set the outlet maximum electric current measurment threshold. Example: range 0.0 ~16.0 represents 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.9INTEGERread-writecurrent
outletMinVolMT
OBJECT-TYPE
Display or set the outlet minimum voltage measurment threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.10INTEGER (900..2600 | -3000 | -2000000)read-writecurrent
outletMaxVolMT
OBJECT-TYPE
Display or set the outlet maximum voltage measurment threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.11INTEGER (900..2600 | -3000 | -2000000)read-writecurrent
outletMinPMT
OBJECT-TYPE
Display or set the outlet minimum power measurment threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.12INTEGER (0..99999 | -3000 | -2000000)read-writecurrent
outletMaxPMT
OBJECT-TYPE
Display or set the outlet maximum power measurment threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.13INTEGER (0..99999 | -3000 | -2000000)read-writecurrent
outletMaxPDMT
OBJECT-TYPE
Display or set the outlet maximum power dissipation measurment threshold. Example: range 0.0 ~ 99999.0 represents 0~999990 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.14INTEGER (0..999990 | -3000 | -2000000)read-writecurrent
outlet9Status
OBJECT-TYPE
Display and control outlet 9 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.11INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet10Status
OBJECT-TYPE
Display and control outlet 10 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.12INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet11Status
OBJECT-TYPE
Display and control outlet 11 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.13INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet12Status
OBJECT-TYPE
Display and control outlet 12 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.14INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet13Status
OBJECT-TYPE
Display and control outlet 13 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.15INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet14Status
OBJECT-TYPE
Display and control outlet 14 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.16INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet15Status
OBJECT-TYPE
Display and control outlet 15 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.17INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet16Status
OBJECT-TYPE
Display and control outlet 16 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.18INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet17Status
OBJECT-TYPE
Display and control outlet 17 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.19INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet18Status
OBJECT-TYPE
Display and control outlet 18 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.20INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet19Status
OBJECT-TYPE
Display and control outlet 19 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.21INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet20Status
OBJECT-TYPE
Display and control outlet 20 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.22INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet21Status
OBJECT-TYPE
Display and control outlet 21 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.23INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet22Status
OBJECT-TYPE
Display and control outlet 22 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.24INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet23Status
OBJECT-TYPE
Display and control outlet 23 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.25INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet24Status
OBJECT-TYPE
Display and control outlet 24 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.26INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet25Status
OBJECT-TYPE
Display and control outlet 25 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.27INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet26Status
OBJECT-TYPE
Display and control outlet 26 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.28INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet27Status
OBJECT-TYPE
Display and control outlet 27 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.29INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet28Status
OBJECT-TYPE
Display and control outlet 28 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.30INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet29Status
OBJECT-TYPE
Display and control outlet 29 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.31INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet30Status
OBJECT-TYPE
Display and control outlet 30 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.32INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet31Status
OBJECT-TYPE
Display and control outlet 31 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.33INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet32Status
OBJECT-TYPE
Display and control outlet 32 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.34INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet33Status
OBJECT-TYPE
Display and control outlet 33 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.35INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet34Status
OBJECT-TYPE
Display and control outlet 34 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.36INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet35Status
OBJECT-TYPE
Display and control outlet 35 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.37INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet36Status
OBJECT-TYPE
Display and control outlet 36 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.38INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet37Status
OBJECT-TYPE
Display and control outlet 37 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.39INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet38Status
OBJECT-TYPE
Display and control outlet 38 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.40INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet39Status
OBJECT-TYPE
Display and control outlet 39 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.41INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet40Status
OBJECT-TYPE
Display and control outlet 40 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.42INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet41Status
OBJECT-TYPE
Display and control outlet 41 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.43INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outlet42Status
OBJECT-TYPE
Display and control outlet 42 status. Can't set pending status.
1.3.6.1.4.1.21317.1.3.2.2.2.2.44INTEGER {off(1), on(2), pending(3), reboot(4), fault(5), noauth(6), not-support(7), pop(8)}read-writecurrent
outletSwitchableTable
OBJECT-TYPE
1.3.6.1.4.1.21317.1.3.2.2.2.2.70not-accessiblecurrent
outletSwitchableEntry
OBJECT-TYPE
1.3.6.1.4.1.21317.1.3.2.2.2.2.70.1not-accessiblecurrent
outletSwitchableIndex
OBJECT-TYPE
Index of outlet number.
1.3.6.1.4.1.21317.1.3.2.2.2.2.70.1.1INTEGER (1..30)read-onlycurrent
outletSwitchable
OBJECT-TYPE
1.3.6.1.4.1.21317.1.3.2.2.2.2.70.1.2INTEGER {no(1), yes(2)}read-onlycurrent
outletIntegerValueTable
OBJECT-TYPE
Display total outlet value table
1.3.6.1.4.1.21317.1.3.2.2.2.2.99not-accessiblecurrent
outletIntegerValueEntry
OBJECT-TYPE
Single outletValue entry containing outlet info.
1.3.6.1.4.1.21317.1.3.2.2.2.2.99.1not-accessiblecurrent
outletIntegerValueIndex
OBJECT-TYPE
Index of outlet number.
1.3.6.1.4.1.21317.1.3.2.2.2.2.99.1.1INTEGER (1..30)read-onlycurrent
outletIntegerCurrent
OBJECT-TYPE
Outlet electric current value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.2.99.1.2INTEGERread-onlycurrent
outletIntegerVoltage
OBJECT-TYPE
Outlet voltage value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.2.99.1.3INTEGERread-onlycurrent
outletIntegerPower
OBJECT-TYPE
Outlet power value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.2.99.1.4INTEGERread-onlycurrent
outletIntegerPowerDissipation
OBJECT-TYPE
Outlet power dissipation value. This value indicates that 1,000 times. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.2.99.1.5INTEGERread-onlycurrent
bank
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.2.3
breakerStatusTable
OBJECT-TYPE
Display total bank value table
1.3.6.1.4.1.21317.1.3.2.2.2.3.1not-accessiblecurrent
breakerStatusEntry
OBJECT-TYPE
Single bankValue entry containing bank info.
1.3.6.1.4.1.21317.1.3.2.2.2.3.1.1not-accessiblecurrent
breakerStatusIndex
OBJECT-TYPE
Index of breaker number.
1.3.6.1.4.1.21317.1.3.2.2.2.3.1.1.1INTEGER (1..30)read-onlycurrent
breakerStatus
OBJECT-TYPE
Breaker status.
1.3.6.1.4.1.21317.1.3.2.2.2.3.1.1.2INTEGER {off(1), on(2), not-support(3)}read-onlycurrent
bankValueTable
OBJECT-TYPE
Display total bank value table
1.3.6.1.4.1.21317.1.3.2.2.2.3.2not-accessiblecurrent
bankValueEntry
OBJECT-TYPE
Single bankValue entry containing bank info.
1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1not-accessiblecurrent
bankValueIndex
OBJECT-TYPE
Index of bank number
1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.1INTEGER (1..30)read-onlycurrent
bankMaxCurrent
OBJECT-TYPE
The Bank Max Current value. unit: (A) EC1000:0A~320A
1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.6INTEGERread-onlycurrent
bankAttachStatus
OBJECT-TYPE
The status of Energy sensor Bank attached status.
1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.7INTEGER {noattached(1), attached(2), error(3), noexisted(4)}read-onlycurrent
bankPowerFactor
OBJECT-TYPE
Bank Power Factor value. If the device does not support this OID, it returns: not-support.
1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.8DisplayStringread-onlycurrent
bankConfigTable
OBJECT-TYPE
Bank configuration table
1.3.6.1.4.1.21317.1.3.2.2.2.3.3not-accessiblecurrent
bankConfigEntry
OBJECT-TYPE
Bank Config entry containing Bank info.
1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1not-accessiblecurrent
bankConfigIndex
OBJECT-TYPE
Index of bank number
1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.1INTEGER (1..30)read-onlycurrent
bankName
OBJECT-TYPE
Display or set the name of bank. When this model does not support the OID, we show n/a. string length: 0~15 NOTE: Input string as /empty to set this object to NULL.
1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.2DisplayStringread-writecurrent
bankMinCurMT
OBJECT-TYPE
Display or set the outlet minimum electric current measurment threshold. Example: range 0.0 ~16.0 rerpresnts 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.3INTEGERread-writecurrent
bankMaxCurMT
OBJECT-TYPE
Display or set the outlet maximum electric current measurment threshold. Example: range 0.0 ~16.0 represents 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.4INTEGERread-writecurrent
bankMinVolMT
OBJECT-TYPE
Display or set the outlet minimum voltage measurment threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.5INTEGER (900..2600 | -3000 | -2000000)read-writecurrent
bankMaxVolMT
OBJECT-TYPE
Display or set the outlet maximum voltage measurment threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.6INTEGER (900..2600 | -3000 | -2000000)read-writecurrent
bankMinPMT
OBJECT-TYPE
Display or set the outlet minimum power measurment threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.7INTEGER (0..99999 | -3000 | -2000000)read-writecurrent
bankMaxPMT
OBJECT-TYPE
Display or set the outlet maximum power measurment threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.8INTEGER (0..99999 | -3000 | -2000000)read-writecurrent
bankMaxPDMT
OBJECT-TYPE
Display or set the outlet maximum power dissipation measurment threshold. Example: range 0.0 ~ 99999.0 represents 0~999990 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.9INTEGER (0..999990 | -3000 | -2000000)read-writecurrent
bankControlTable
OBJECT-TYPE
Bank Control table
1.3.6.1.4.1.21317.1.3.2.2.2.3.4not-accessiblecurrent
bankControlEntry
OBJECT-TYPE
Bank control entry.
1.3.6.1.4.1.21317.1.3.2.2.2.3.4.1not-accessiblecurrent
bankControlIndex
OBJECT-TYPE
Index of bank number
1.3.6.1.4.1.21317.1.3.2.2.2.3.4.1.1INTEGER (1..4)read-onlycurrent
bankControlStatus
OBJECT-TYPE
This function is used for outlet control of bank. Set off(1) to turn off for outlet control of bank. Set on(2) to turn on for all outlet control of bank. Set reboot(3) to turn on for outlet control of bank. Get this object always return nostatus(3), because there is no bank status.
1.3.6.1.4.1.21317.1.3.2.2.2.3.4.1.2INTEGER {off(1), on(2), reboot(3), nostatus(4), not-support(5)}read-writecurrent
bankIntegerValueTable
OBJECT-TYPE
Display total bank value table
1.3.6.1.4.1.21317.1.3.2.2.2.3.99not-accessiblecurrent
bankIntegerValueEntry
OBJECT-TYPE
Single bankValue entry containing bank info.
1.3.6.1.4.1.21317.1.3.2.2.2.3.99.1not-accessiblecurrent
bankIntegerValueIndex
OBJECT-TYPE
Index of bank number.
1.3.6.1.4.1.21317.1.3.2.2.2.3.99.1.1INTEGER (1..30)read-onlycurrent
bankIntegerCurrent
OBJECT-TYPE
Bank electric current value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.3.99.1.2INTEGERread-onlycurrent
bankIntegerVoltage
OBJECT-TYPE
Bank voltage value. This value indicates that 1,000 times. We put this OID to write access type for user to set the reference voltage on EC1000 model. And the setting should be the numbers. You can set 0 to clear the setting. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.3.99.1.3INTEGERread-onlycurrent
bankIntegerPower
OBJECT-TYPE
Bank power value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.3.99.1.4INTEGERread-onlycurrent
bankIntegerPowerDissipation
OBJECT-TYPE
Bank power dissipation value. This value indicates that 1,000 times. If this measurement value is not available, it returns value -1000000. If the device does not support this OID, it returns value -2000000.
1.3.6.1.4.1.21317.1.3.2.2.2.3.99.1.5INTEGERread-onlycurrent
deviceManagement
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.3
config
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.3.4
deviceMAC
OBJECT-TYPE
Display device MAC address.
1.3.6.1.4.1.21317.1.3.2.2.3.4.1DisplayStringread-onlycurrent
deviceIPv4
OBJECT-TYPE
Display device IP address.
1.3.6.1.4.1.21317.1.3.2.2.3.4.2IpAddressread-onlycurrent
deviceFWversion
OBJECT-TYPE
Display device FW version.
1.3.6.1.4.1.21317.1.3.2.2.3.4.3DisplayStringread-onlycurrent
dashBoard
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.3.4.4
dashboardRow
OBJECT-TYPE
Display or set device's dashboard row number.
1.3.6.1.4.1.21317.1.3.2.2.3.4.4.1INTEGER (1..26)read-writecurrent
dashboardColumn
OBJECT-TYPE
Display or set device's dashboard column number.
1.3.6.1.4.1.21317.1.3.2.2.3.4.4.2INTEGER (1..26)read-writecurrent
dashboardRackName
OBJECT-TYPE
Display or set device's dashboard rack name. string length: 1~32 NOTE: Input string as /empty to set this object to NULL.
1.3.6.1.4.1.21317.1.3.2.2.3.4.4.3DisplayStringread-writecurrent
servicePorts
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.3.4.5
httpPort
OBJECT-TYPE
Display or set the HTTP port of PE device.
1.3.6.1.4.1.21317.1.3.2.2.3.4.5.1INTEGER (1..65535)read-writecurrent
httpsPort
OBJECT-TYPE
Display or set the HTTPs port of PE device.
1.3.6.1.4.1.21317.1.3.2.2.3.4.5.2INTEGER (1..65535)read-writecurrent
httpsOnlyEnable
OBJECT-TYPE
Enable to use Webpage HTTPs only or disable to use Webpage HTTP/HTTPs
1.3.6.1.4.1.21317.1.3.2.2.3.4.5.3INTEGER {yes(1), no(2)}read-writecurrent
ipv4config
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.3.4.6
staticIPEnabled
OBJECT-TYPE
Display or set IPv4 address automatically or not
1.3.6.1.4.1.21317.1.3.2.2.3.4.6.1INTEGER {no(1), yes(2)}read-writecurrent
fixedIPv4
OBJECT-TYPE
Display or set fixed IPv4 address
1.3.6.1.4.1.21317.1.3.2.2.3.4.6.2IpAddressread-writecurrent
subnetMask
OBJECT-TYPE
Display or set subnet mask address
1.3.6.1.4.1.21317.1.3.2.2.3.4.6.3IpAddressread-writecurrent
gateway
OBJECT-TYPE
Display or set gateway address
1.3.6.1.4.1.21317.1.3.2.2.3.4.6.4IpAddressread-writecurrent
staticDNSEnabled
OBJECT-TYPE
Display or set DNS address automatically or not
1.3.6.1.4.1.21317.1.3.2.2.3.4.6.5INTEGER {no(1), yes(2)}read-writecurrent
dnsPreferIPv4
OBJECT-TYPE
Display or set prefer DNS address
1.3.6.1.4.1.21317.1.3.2.2.3.4.6.6IpAddressread-writecurrent
dnsAlternateIPv4
OBJECT-TYPE
Display or set alternate DNS address
1.3.6.1.4.1.21317.1.3.2.2.3.4.6.7IpAddressread-writecurrent
eventNotification
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.3.4.7
devicesnmp
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1
trapEnabled
OBJECT-TYPE
Indicates if this trap entry is enabled or not. You should set the username/auth-password/priv-password first, when choosing snmpv3. You should set the community string first, when choosing snmpv1/v2c.
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.1INTEGER {no(1), yes(2)}read-writecurrent
trapVersion
OBJECT-TYPE
Choose SNMP Trap version to send trap. You should set the username/auth-password/priv-password first, when choosing snmpv3. You should set the community string first, when choosing snmpv1/v2c.
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.2INTEGER {v1(1), v2c(2), v3(3)}read-writecurrent
snmpTrapTable
OBJECT-TYPE
PE SNMP agent trap setup table. If users want to use trap, they must set enable trap, ip and community first.
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3not-accessiblecurrent
snmpTrapEntry
OBJECT-TYPE
Single trap entry containing trap receiver info.
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1not-accessiblecurrent
trapReceiverNumber
OBJECT-TYPE
Index of trap receiver
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.1INTEGER (1..2)read-onlycurrent
trapReceiverIPAddress
OBJECT-TYPE
Trap receiver IP address
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.2IpAddressread-writecurrent
trapPort
OBJECT-TYPE
NMS trap port to be used by agent to send trap
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.3INTEGER (1..65535)read-writecurrent
trapCommunity
OBJECT-TYPE
If use SNMPv1/v2c to receive trap should set this Community string. MAX string length: 20 NOTE: Input string as /empty to set this object to NULL.
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.4DisplayString (SIZE(0..20))read-writecurrent
trapUsername
OBJECT-TYPE
If use SNMPv3 to receive trap should set this string. NOTE: Input string as /empty to set this object to NULL. MAX string length: 20
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.5DisplayString (SIZE(0..20))read-writecurrent
trapAuthpassword
OBJECT-TYPE
If use SNMPv3 to receive trap should set this string. MAX string length: 20 NOTE: Input string as /empty to set this object to NULL.
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.6DisplayString (SIZE(8..20))read-writecurrent
trapPrivpassword
OBJECT-TYPE
If use SNMPv3 to receive trap should set this string. MAX string length: 20 NOTE: Input string as /empty to set this object to NULL.
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.7DisplayString (SIZE(8..20))read-writecurrent
syslog
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.2
sysLogServerEnabled
OBJECT-TYPE
Display or set syslog server address automatically or not
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.2.1INTEGER {no(1), yes(2)}read-writecurrent
sysLogServerIPv4
OBJECT-TYPE
Display or set syslog server address
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.2.2IpAddressread-writecurrent
sysLogServerPort
OBJECT-TYPE
Display or set syslog server port
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.2.3INTEGER (1..65535)read-writecurrent
smtp
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3
smtpServerEnabled
OBJECT-TYPE
Display or set SMTP server enable status.
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.1INTEGER {no(1), yes(2)}read-writecurrent
smtpServerName
OBJECT-TYPE
Display or set a SMTP server name. NOTE: Input string as /empty to set this object to NULL.
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.2DisplayStringread-writecurrent
smtpAuthEnabled
OBJECT-TYPE
Display or set authentication of SMTP server.
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.3INTEGER {no(1), yes(2)}read-writecurrent
smtpAccountName
OBJECT-TYPE
Display or set a user's name of SMTP server. NOTE: Input string as /empty to set this object to NULL.
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.4DisplayStringread-writecurrent
smtpAccountPwd
OBJECT-TYPE
Display or set a user's password of SMTP server. NOTE: Input string as /empty to set this object to NULL.
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.5DisplayStringread-writecurrent
smtpMailFrom
OBJECT-TYPE
Display or set a mail of SMTP server. NOTE: Input string as /empty to set this object to NULL.
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.6DisplayStringread-writecurrent
smtpMailTo
OBJECT-TYPE
Display or set a mail of SMTP server. NOTE: Input string as /empty to set this object to NULL.
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.7DisplayStringread-writecurrent
configurationNotification
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.9
configurationNotifyEnabled
OBJECT-TYPE
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.9.1INTEGER {no(1), yes(2)}read-writecurrent
dateTime
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.3.4.8
timeZone
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.3.4.8.1
timeZoneSetting
OBJECT-TYPE
Display or set the time zone of PE device. (0) [GMT-12:00] Eniwetok Kwajalein (1) [GMT-11:00] Midway Island Samoa (2) [GMT-10:00] Hawaii (3) [GMT-09:00] Alaska (4) [GMT-08:00] Pacific Time (US & Canada); Tijuana (5) [GMT-07:00] Mountain Time (US & Canada) (6) [GMT-07:00] Arizona (7) [GMT-06:00] Central Time (US & Canada) (8) [GMT-06:00] Mexico City (9) [GMT-06:00] Saskatchewan (10)[GMT-06:00] Central America (11)[GMT-05:00] Eastern Time (US & Canada) (12)[GMT-05:00] Indiana (East) (13)[GMT-05:00] Bogota Lima Quito (14)[GMT-04:00] Atlantic Time (Canada) (15)[GMT-04:00] Caracas La Paz (16)[GMT-04:00] Santiago (17)[GMT-03:30] Newfoundland (18)[GMT-03:00] Buenos Aires Georgetown (19)[GMT-03:00] Brasilia (20)[GMT-03:00] Greenland (21)[GMT-02:00] Mid-Atlantic (22)[GMT-01:00] Azores (23)[GMT-01:00] Cape Verde Is (24)[GMT] Casablanca Monrovia (25)[GMT] Greenwich Mean Time: Dublin Edinburgh Lisbon London (26)[GMT+01:00] Amsterdam Copenhagen Madrid Paris Vilnius (27)[GMT+01:00] West Central Africa (28)[GMT+01:00] Belgrade Sarajevo Skopje Sofija Zagreb (29)[GMT+01:00] Bratislava Budapest Ljubljana Prague Warsaw (30)[GMT+01:00] Brussels Berlin Bern Rome Stockholm Vienna (31)[GMT+02:00] Cairo (32)[GMT+02:00] Harare Pretoria (33)[GMT+02:00] Jerusalem (34)[GMT+02:00] Bucharest (35)[GMT+02:00] Helsinki Riga Tallinn (36)[GMT+02:00] Athens Istanbul Minsk (37)[GMT+03:00] Kuwait Riyadh (38)[GMT+03:00] Nairobi (39)[GMT+03:00] Baghdad (40)[GMT+03:00] Moscow St. Petersburg Volgograd (41)[GMT+03:30] Tehran (42)[GMT+04:00] Abu Dhabi Muscat (43)[GMT+04:00] Baku Tbilisi Yerevan (44)[GMT+04:30] Kabul (45)[GMT+05:00] Islamabad Karachi Tashkent (46)[GMT+05:00] Ekaterinburg (47)[GMT+05:30] Calcutta Chennai Mumbai New Delhi (48)[GMT+05:45] Kathmandu (49)[GMT+06:00] Astana Dhaka (50)[GMT+06:00] Sri Jayawardenepura (51)[GMT+06:00] Almaty Novosibirsk (52)[GMT+06:30] Rangoon (53)[GMT+07:00] Bangkok Hanoi Jakarta (54)[GMT+07:00] Krasnoyarsk (55)[GMT+08:00] Beijing Chongqing Hong Kong Urumqi (56)[GMT+08:00] Perth (57)[GMT+08:00] Kuala Lumpur Singapore (58)[GMT+08:00] Taipei (59)[GMT+08:00] Irkutsk Ulaan Bataar (60)[GMT+09:00] Osaka Sapporo Tokyo (61)[GMT+09:00] Seoul (62)[GMT+09:00] Yakutsk (63)[GMT+09:30] Darwin (64)[GMT+09:30] Adelaide (65)[GMT+10:00] Canberra Melbourne Sydney (66)[GMT+10:00] Brisbane (67)[GMT+10:00] Guam Port Moresby (68)[GMT+10:00] Hobart (69)[GMT+10:00] Vladivostok (70)[GMT+11:00] Magadan Solomon Is New Caledonia (71)[GMT+12:00] Fiji Kamchatka Marshall Is. (72)[GMT+12:00] Auckland Wellington (73)[GMT+13:00] Nuku'alofa
1.3.6.1.4.1.21317.1.3.2.2.3.4.8.1.1INTEGERread-writecurrent
dstEnabled
OBJECT-TYPE
Display or set daylight savings time .
1.3.6.1.4.1.21317.1.3.2.2.3.4.8.1.2INTEGER {no(1), yes(2)}read-writecurrent
manualInput
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.3.4.8.2
dateSetting
OBJECT-TYPE
Display or set date in a manual way.(This is Greenwich Mean Time, GMT) string length: 10 This value format must match the following form: YYYY-MM-DD ex. 2011-01-01 Note: range of year: 2000-2099 range of month: 01-12 range of day: 01-31
1.3.6.1.4.1.21317.1.3.2.2.3.4.8.2.1DisplayStringread-writecurrent
timeSetting
OBJECT-TYPE
Display or set time in a manual way.(This is Greenwich Mean Time, GMT) string length: 8 This value format must match the following form: HH:MM:SS ex. 02:02:02 Note: range of hour: 00-24 range of minute: 00-60 range of second: 00-60
1.3.6.1.4.1.21317.1.3.2.2.3.4.8.2.2DisplayStringread-writecurrent
networkTime
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3
autoAdjustEnabled
OBJECT-TYPE
Display or set date time useing auto adjustment way.
1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.1INTEGER {no(1), yes(2)}read-writecurrent
preferNTP
OBJECT-TYPE
Display or set prefer NTP server. AU | ntp1.cs.mu.OZ.AU(0), AU | ntp0.cs.mu.OZ.AU(1), BE | ntp2.oma.be(2), BE | ntp1.oma.be(3), BR | ntps1.pads.ufrj.br(4), CH | swisstime.ethz.ch(5), CL | ntp.shoa.cl(6), CZ | ntp.nic.cz(7), DE | ntp.stairweb.de(8), DE | ntps1-0.cs.tu-berlin.de(9), DE | ptbtime1.ptb.de(10), DE | ntp1.fau.de(11), DE | ptbtime2.ptb.de(12), DE | time1.one4vision.de(13), DE | rustime01.rus.uni-stuttgart.de(14), DE | ntp.probe-networks.de(15), DE | ntp2.fau.de(16), ES | hora.roa.es(17), HK | stdtime.gov.hk(18), IE | ntp-galway.hea.net(19), IT | ntp1.inrim.it(20), IT | ntp2.inrim.it(21), JP | clock.tl.fukuoka-u.ac.jp(22), JP | ntp.nict.jp(23), JP | clock.nc.fukuoka-u.ac.jp(24), KR | ntp.xbsd.kr(25), MX | cronos.cenam.mx(26), NL | ntp0.nl.uu.net(27), NL | ntp1.nl.uu.net(28), NL | ntp.remco.org(29), NL | ntp0.nl.net(30), PL | vega.cbk.poznan.pl(31), PL | ntp.ntp-servers.com(32), RO | ntp3.usv.ro(33), RO | ntp2.usv.ro(34), RU | ntp1.vniiftri.ru; ntp1.imvp.ru(35), RU | ntp2.vniiftri.ru; ntp2.imvp.ru(36), SE | ntp1.mmo.netnod.se(37), SE | ntp1.sth.netnod.se(38), SE | ntp2.mmo.netnod.se(39), SE | ntp2.sth.netnod.se(40), SE | time2.stupi.se(41), SE | ntp1.sp.se(42), SE | timehost.lysator.liu.se(43), SI | ntp.mostovna.com(44), US CA | timekeeper.isi.edu(45), US CA | clock.sjc.he.net(46), US CA | nist1.symmetricom.com(47), US CA | clock.via.net(48), US CA | nist1.aol-ca.truetime.com(49), US CA | clock.isc.org(50), US CA | clepsydra.dec.com(51), US CA | gps.layer42.net(52), US CA | time.no-such-agency.net(53), US CA | nist1-sj.WiTime.net(54), US CA | clock.fmt.he.net(55), US CO | time-b.timefreq.bldrdoc.gov(56), US CO | time-a.timefreq.bldrdoc.gov(57), US CO | utcnist.colorado.edu(58), US CO | time-c.timefreq.bldrdoc.gov(59), US DE | rackety.udel.edu(60), US DE | mizbeaver.udel.edu(61), US GA | nist1.columbiacountyga.gov(62), US IL | ntp.your.org(63), US MA | bonehed.lcs.mit.edu(64), US MA | time.keneli.org(65), US MA | ntp0.broad.mit.edu(66), US MD | time-a.nist.gov(67), US MD | time-b.nist.gov(68), US MI | nist.netservicesgroup.com(69), US NY | nist1-ny.WiTime.net(70), US NY | clock.nyc.he.net(71), US UT | time.xmission.com(72), US VA | nist1-dc.WiTime.net(73), US VA | nist1.aol-va.truetime.com(74), US WA | time-nw.nist.gov(75), FR | utp.univ-lyon1.fr(76), FR | ntp-sop.inria.fr(77), FR | ntp.tuxfamily.net(78), UK | bear.zoo.bt.co.uk(79)
1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.2INTEGERread-writecurrent
preferServerIPenable
OBJECT-TYPE
Enable or disable prefer custom server IP.
1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.3INTEGER {no(1), yes(2)}read-writecurrent
preferNTPIp
OBJECT-TYPE
Display or set prefer NTP server IP.
1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.4IpAddressread-writecurrent
alternateNtpEnabled
OBJECT-TYPE
Display or set date time using alternate NTP server.
1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.5INTEGER {no(1), yes(2)}read-writecurrent
alternateNtp
OBJECT-TYPE
Display or set alternative NTP server. AU | ntp1.cs.mu.OZ.AU(0), AU | ntp0.cs.mu.OZ.AU(1), BE | ntp2.oma.be(2), BE | ntp1.oma.be(3), BR | ntps1.pads.ufrj.br(4), CH | swisstime.ethz.ch(5), CL | ntp.shoa.cl(6), CZ | ntp.nic.cz(7), DE | ntp.stairweb.de(8), DE | ntps1-0.cs.tu-berlin.de(9), DE | ptbtime1.ptb.de(10), DE | ntp1.fau.de(11), DE | ptbtime2.ptb.de(12), DE | time1.one4vision.de(13), DE | rustime01.rus.uni-stuttgart.de(14), DE | ntp.probe-networks.de(15), DE | ntp2.fau.de(16), ES | hora.roa.es(17), HK | stdtime.gov.hk(18), IE | ntp-galway.hea.net(19), IT | ntp1.inrim.it(20), IT | ntp2.inrim.it(21), JP | clock.tl.fukuoka-u.ac.jp(22), JP | ntp.nict.jp(23), JP | clock.nc.fukuoka-u.ac.jp(24), KR | ntp.xbsd.kr(25), MX | cronos.cenam.mx(26), NL | ntp0.nl.uu.net(27), NL | ntp1.nl.uu.net(28), NL | ntp.remco.org(29), NL | ntp0.nl.net(30), PL | vega.cbk.poznan.pl(31), PL | ntp.ntp-servers.com(32), RO | ntp3.usv.ro(33), RO | ntp2.usv.ro(34), RU | ntp1.vniiftri.ru; ntp1.imvp.ru(35), RU | ntp2.vniiftri.ru; ntp2.imvp.ru(36), SE | ntp1.mmo.netnod.se(37), SE | ntp1.sth.netnod.se(38), SE | ntp2.mmo.netnod.se(39), SE | ntp2.sth.netnod.se(40), SE | time2.stupi.se(41), SE | ntp1.sp.se(42), SE | timehost.lysator.liu.se(43), SI | ntp.mostovna.com(44), US CA | timekeeper.isi.edu(45), US CA | clock.sjc.he.net(46), US CA | nist1.symmetricom.com(47), US CA | clock.via.net(48), US CA | nist1.aol-ca.truetime.com(49), US CA | clock.isc.org(50), US CA | clepsydra.dec.com(51), US CA | gps.layer42.net(52), US CA | time.no-such-agency.net(53), US CA | nist1-sj.WiTime.net(54), US CA | clock.fmt.he.net(55), US CO | time-b.timefreq.bldrdoc.gov(56), US CO | time-a.timefreq.bldrdoc.gov(57), US CO | utcnist.colorado.edu(58), US CO | time-c.timefreq.bldrdoc.gov(59), US DE | rackety.udel.edu(60), US DE | mizbeaver.udel.edu(61), US GA | nist1.columbiacountyga.gov(62), US IL | ntp.your.org(63), US MA | bonehed.lcs.mit.edu(64), US MA | time.keneli.org(65), US MA | ntp0.broad.mit.edu(66), US MD | time-a.nist.gov(67), US MD | time-b.nist.gov(68), US MI | nist.netservicesgroup.com(69), US NY | nist1-ny.WiTime.net(70), US NY | clock.nyc.he.net(71), US UT | time.xmission.com(72), US VA | nist1-dc.WiTime.net(73), US VA | nist1.aol-va.truetime.com(74), US WA | time-nw.nist.gov(75), FR | utp.univ-lyon1.fr(76), FR | ntp-sop.inria.fr(77), FR | ntp.tuxfamily.net(78), UK | bear.zoo.bt.co.uk(79)
1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.6INTEGERread-writecurrent
alternateServerIPenable
OBJECT-TYPE
Enable or disable alternate custom server IP.
1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.7INTEGER {no(1), yes(2)}read-writecurrent
alternateNtpIp
OBJECT-TYPE
Display or set alternative NTP server IP.
1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.8IpAddressread-writecurrent
adjustTimeEveryDays
OBJECT-TYPE
Display or set frequency of adjustment in days.
1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.9INTEGERread-writecurrent
devicesecurity
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.3.5
loginFailures
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.3.5.1
loginAllowTimes
OBJECT-TYPE
Display or set time of login faliure.
1.3.6.1.4.1.21317.1.3.2.2.3.5.1.1INTEGER (1..99)read-writecurrent
loginTimeOut
OBJECT-TYPE
Display or set login time out.
1.3.6.1.4.1.21317.1.3.2.2.3.5.1.2INTEGER (1..240)read-writecurrent
workingMode
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.3.5.2
icmpEnabled
OBJECT-TYPE
Display or set status of ICMP.
1.3.6.1.4.1.21317.1.3.2.2.3.5.2.1INTEGER {no(1), yes(2)}read-writecurrent
accountPolicy
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.3.5.3
minUserNameLen
OBJECT-TYPE
Display or set minimum length of user name.
1.3.6.1.4.1.21317.1.3.2.2.3.5.3.1INTEGER (1..16)read-writecurrent
minUserPwdLen
OBJECT-TYPE
Display or set minimum length of user password.
1.3.6.1.4.1.21317.1.3.2.2.3.5.3.2INTEGER (1..16)read-writecurrent
upperCaseEnabled
OBJECT-TYPE
Display or set one upper case rule in user password.
1.3.6.1.4.1.21317.1.3.2.2.3.5.3.3INTEGER {no(1), yes(2)}read-writecurrent
lowerCaseEnabled
OBJECT-TYPE
Display or set one lower case rule in user password.
1.3.6.1.4.1.21317.1.3.2.2.3.5.3.4INTEGER {no(1), yes(2)}read-writecurrent
numberEnabled
OBJECT-TYPE
Display or set one number rule in user password.
1.3.6.1.4.1.21317.1.3.2.2.3.5.3.5INTEGER {no(1), yes(2)}read-writecurrent
disableDuplicateLogin
OBJECT-TYPE
Display or set status of disabled duplicate login rule.
1.3.6.1.4.1.21317.1.3.2.2.3.5.3.6INTEGER {no(1), yes(2)}read-writecurrent
loginRestriction
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.3.5.4
loginString
OBJECT-TYPE
Display or set a login string. string length: 0~32 NOTE: Input string as /empty to set this object to NULL.
1.3.6.1.4.1.21317.1.3.2.2.3.5.4.1DisplayStringread-writecurrent
ipFilter
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2
ipFilterEnabled
OBJECT-TYPE
Display or set status of ip filter.
1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.1INTEGER {no(1), yes(2)}read-writecurrent
ipFilterRule
OBJECT-TYPE
Display or set status of ip filter rule.
1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.2INTEGER {include(1), exclude(2)}read-writecurrent
ipFilterTable
OBJECT-TYPE
A list of restricted ip.
1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.3not-accessiblecurrent
ipFilterEntry
OBJECT-TYPE
Status and parameter values for a PE's restricted IP.
1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.3.1not-accessiblecurrent
ipFilterIndex
OBJECT-TYPE
The value of index for the ip filter.
1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.3.1.1INTEGER (1..5)read-onlycurrent
ipFilterFrom
OBJECT-TYPE
A set of restricted ip. ex. 192.168.0.1 Note: Users must follow in order to set the ip address. Note: To clear the settings to set the ip 0.0.0.0
1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.3.1.2IpAddressread-writecurrent
ipFilterTo
OBJECT-TYPE
A set of restricted ip. ex. 192.168.0.255 Note: Users must follow in order to set the ip address. Note: To clear the settings to set the ip 0.0.0.0
1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.3.1.3IpAddressread-writecurrent
macFilter
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3
macFilterEnabled
OBJECT-TYPE
Display or set status of mac filter.
1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.1INTEGER {no(1), yes(2)}read-writecurrent
macFilterRule
OBJECT-TYPE
Display or set status of mac filter rule.
1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.2INTEGER {include(1), exclude(2)}read-writecurrent
macFilterTable
OBJECT-TYPE
A list of restricted mac.
1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.3not-accessiblecurrent
macFilterEntry
OBJECT-TYPE
Status and parameter values for a PE's restricted MAC.
1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.3.1not-accessiblecurrent
macFilterIndex
OBJECT-TYPE
The value of index for the mac filter.
1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.3.1.1INTEGER (1..5)read-onlycurrent
macFilterSet
OBJECT-TYPE
A set of restricted mac. string length: 12 ex. 004854655511 Note: Users must follow in order to set the MAC address. Note: To clear the settings to set the MAC 000000000000
1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.3.1.2DisplayStringread-writecurrent
authentication
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.3.5.5
radius
OBJECT-IDENTITY
1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1
radiusEnabled
OBJECT-TYPE
Display or set status of RADIUS server.
1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.1INTEGER {no(1), yes(2)}read-writecurrent
preferRadiusIp
OBJECT-TYPE
Display or set prefer RADIUS server IP.
1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.2IpAddressread-writecurrent
preferRadiusPort
OBJECT-TYPE
Display or set prefer RADIUS server port.
1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.3INTEGER (1..65535)read-writecurrent
alternateRadiusIp
OBJECT-TYPE
Display or set alternative RADIUS server IP.
1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.4IpAddressread-writecurrent
alternateRadiusPort
OBJECT-TYPE
Display or set alternative RADIUS server port.
1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.5INTEGER (1..65535)read-writecurrent
radiusTimeOut
OBJECT-TYPE
Display or set time out of authentication using RADIUS server. The unit is sec.
1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.6INTEGER (1..60)read-writecurrent
radiusRetry
OBJECT-TYPE
Display or set retry times of authentication using RADIUS server.
1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.7INTEGER (0..10)read-writecurrent
radiusSecret
OBJECT-TYPE
Display or set shared secret of RADIUS server. string length: 6~15 At least 6 characters. NOTE: Input string as /empty to set this object to NULL.
1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.8DisplayStringread-writecurrent
rebootDevice
OBJECT-TYPE
Reboot PE Device
1.3.6.1.4.1.21317.1.3.2.2.6INTEGER {no(1), yes(2)}read-writecurrent

Notifications

NameOIDStatus
configurationNotifyTrapMSG
NOTIFICATION-TYPE
1.3.6.1.4.1.21317.1.3.2.2.3.4.7.9.2current
customTrapMSG
NOTIFICATION-TYPE
Display custom trap message.
1.3.6.1.4.1.21317.1.3.2.2.5current