MIBs Depot

APNL-MODULAR-PDU-MIB

Registered at
1.3.6.1.4.1.29640
Last updated
2013-01-24 10:00
Organization
AP Nederland
Revisions
2013-01-24 13:05
Namespace
apnederland
Source file
APNL-MODULAR-PDU-MIB
Digest
sha256:bd53240bbb789f80fb3d94fd9162bf3f507c9f0e1b8a7db3f6ced27275105f3d

Description

This MIB module defines the modular PDU version of AP Nederland.

Contact

Vincent Veltens <v.veltens@apnederland.nl>

Imports

FromSymbols
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP
SNMPv2-SMIInteger32, IpAddress, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, Unsigned32, enterprises, iso
SNMPv2-TCDateAndTime, DisplayString, TEXTUAL-CONVENTION

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

APNL-MODULAR-PDU-MIB
SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC

Objects

NameOIDSyntaxAccessStatus
apnlDirectory
OBJECT-IDENTITY
1.3.6.1.4.1.29640.1
apnlMib
OBJECT-IDENTITY
1.3.6.1.4.1.29640.2
apnlTmp
OBJECT-IDENTITY
1.3.6.1.4.1.29640.3
apnlModules
OBJECT-IDENTITY
1.3.6.1.4.1.29640.4
cm
OBJECT-IDENTITY
1.3.6.1.4.1.29640.4.1
cmTraps
OBJECT-IDENTITY
1.3.6.1.4.1.29640.4.2
pdu
OBJECT-IDENTITY
1.3.6.1.4.1.29640.4.3
pduType
OBJECT-TYPE
Type of the Pdu. PduModular (0) Modulaire OEC2 PDU communication through SNMPV3, MOD-BUS or AP-BUS in emulation mode. PduGateway1 (1) Gateway to connect OEC1 products with external AP-BUS protocol to OEC2 Manager (SNMPV3). PduGateway2 (2) Gateway to connect OEC2 products with external MOD-BUS to OEC Manager (SNMPV3).
1.3.6.1.4.1.29640.4.3.1INTEGER {pduModular(0), pduGateway1(1), pduGateway2(2)}read-onlycurrent
pduProductIdentifier
OBJECT-TYPE
Unique serial number to identify a pdu, the number is between 1 and 65535.
1.3.6.1.4.1.29640.4.3.2Integer32read-onlycurrent
pduSerialNumber
OBJECT-TYPE
PDU onboard Serial Number.
1.3.6.1.4.1.29640.4.3.3DisplayString (SIZE(1..16))read-onlycurrent
pduStatus
OBJECT-TYPE
Status of the Pdu. pduBusy (0) Indicates that an admin command is in progress. pduReady (1) The execution of an admin command was successfull. pduAlarm (2) This state is not in use. pduError (3) The execution of an admin command failed.
1.3.6.1.4.1.29640.4.3.4INTEGER {pduBusy(0), pduReady1(1), pduAlarm(2), pduError(3)}read-onlycurrent
pduPower
OBJECT-TYPE
The total measured pdu power in Kilo Watt's*Hour.
1.3.6.1.4.1.29640.4.3.5Unsigned32read-onlycurrent
pduPowerL1
OBJECT-TYPE
The total measured pdu power in Kilo Watt's*Hour for phase 1.
1.3.6.1.4.1.29640.4.3.6Unsigned32read-onlycurrent
pduPowerL2
OBJECT-TYPE
The total measured pdu power in Kilo Watt's*Hour for phase 2.
1.3.6.1.4.1.29640.4.3.7Unsigned32read-onlycurrent
pduPowerL3
OBJECT-TYPE
The total measured pdu power in Kilo Watt's*Hour for phase 3.
1.3.6.1.4.1.29640.4.3.8Unsigned32read-onlycurrent
pduKvar
OBJECT-TYPE
The total Reactive Power of the pdu. It is the power that magnetic equipment (transformer, motor and relay) needs to produce the magnetizing flux.
1.3.6.1.4.1.29640.4.3.9Unsigned32read-onlycurrent
pduKvarL1
OBJECT-TYPE
The total Reactive Power of the pdu for phase 1. It is the power that magnetic equipment (transformer, motor and relay) needs to produce the magnetizing flux.
1.3.6.1.4.1.29640.4.3.10Unsigned32read-onlycurrent
pduKvarL2
OBJECT-TYPE
The total Reactive Power of the pdu for phase 2. It is the power that magnetic equipment (transformer, motor and relay) needs to produce the magnetizing flux.
1.3.6.1.4.1.29640.4.3.11Unsigned32read-onlycurrent
pduKvarL3
OBJECT-TYPE
The total Reactive Power of the pdu for phase 3. It is the power that magnetic equipment (transformer, motor and relay) needs to produce the magnetizing flux.
1.3.6.1.4.1.29640.4.3.12Unsigned32read-onlycurrent
pdulAcurrent
OBJECT-TYPE
The total measured ac current for the pdu (in 1/10th Amperes) .
1.3.6.1.4.1.29640.4.3.13Unsigned32read-onlycurrent
pduAcurrentL1
OBJECT-TYPE
The total measured ac current for phase 1 (in 1/10th Amperes).
1.3.6.1.4.1.29640.4.3.14Unsigned32read-onlycurrent
pduAcurrentL2
OBJECT-TYPE
The total measured ac current for phase 2 (in 1/10th Amperes).
1.3.6.1.4.1.29640.4.3.15Unsigned32read-onlycurrent
pduAcurrentL3
OBJECT-TYPE
The total measured ac current for phase 3 (in 1/10th Amperes).
1.3.6.1.4.1.29640.4.3.16Unsigned32read-onlycurrent
pduCurIpAddress
OBJECT-TYPE
The current PDU IPv4 Address by which TCP/IP access is available.
1.3.6.1.4.1.29640.4.3.17IpAddressread-onlycurrent
pduCurSubNetMask
OBJECT-TYPE
The current PDU IPv4 Subnet Mask used by the Ipstack (e.g: 255.255.255.0).
1.3.6.1.4.1.29640.4.3.18IpAddressread-onlycurrent
pduCurDefGwAddress
OBJECT-TYPE
The current PDU IPv4 default gateway address used by the Ipstack (e.g: 192.168.1.1).
1.3.6.1.4.1.29640.4.3.19IpAddressread-onlycurrent
pduNumberOfNodes
OBJECT-TYPE
Number of items in the node table.
1.3.6.1.4.1.29640.4.3.20Integer32read-onlycurrent
pduNumberOfSensors
OBJECT-TYPE
Number of items in the sensor table.
1.3.6.1.4.1.29640.4.3.21Integer32read-onlycurrent
pduSoftwareVersion
OBJECT-TYPE
PDU software version number.
1.3.6.1.4.1.29640.4.3.22DisplayString (SIZE(1..10))read-onlycurrent
pduFirmwareVersion
OBJECT-TYPE
PDU firmware version number.
1.3.6.1.4.1.29640.4.3.23DisplayString (SIZE(1..10))read-onlycurrent
pduBusProtocol
OBJECT-TYPE
Selected protocol used on the external bus of the pdu. AP-BUS (0) Protocol used by OEC1 products or by OEC2 products in emulation mode. MOD-BUS (1) Protocol used by OEC2 products.
1.3.6.1.4.1.29640.4.3.24INTEGER {apbus(0), modbus(1)}read-onlycurrent
pduAdminCommand
OBJECT-TYPE
PDU admin management Commands: noOp (0) No operation. rebootPdu (1) Reboot the PDU (to execute new settings). rediscover (2) Not supported. updateSofware (3) Not supported. resetConfig (4) Node and group tables will be cleared . resetSNMPv3Config (5) Not supported. resetNetworkSetting (6) Reset network params: ip address, defualt gatewy, subnet mask. readDataFromBusPdu (7) Read data from a PDU connected to the external bus (address is set in pduBusAddress). writeDataToBusPdu (8) With this command modified data is writen back to the bus PDU (address is set in pduBusAddress).
1.3.6.1.4.1.29640.4.3.25INTEGER {noOp(0), rebootPdu(1), rediscover(2), updateSofware(3), resetConfig(4), resetSNMPv3Config(5), resetNetworkSetting(6), readDataFromBusPdu(7), writeDataToBusPdu(8)}read-writecurrent
pduStartupIpAddress
OBJECT-TYPE
Not supported.
1.3.6.1.4.1.29640.4.3.26IpAddressread-writecurrent
pduStartupSubNetMask
OBJECT-TYPE
Not supported.
1.3.6.1.4.1.29640.4.3.27IpAddressread-writecurrent
pduStartupDefGwAddress
OBJECT-TYPE
Not supported.
1.3.6.1.4.1.29640.4.3.28IpAddressread-writecurrent
pduRealTimeClock
OBJECT-TYPE
PDU Real-Time Clock. Maybe set by the manager.
1.3.6.1.4.1.29640.4.3.29DateAndTimeread-writecurrent
pduEnableFeatures
OBJECT-TYPE
Array of bits each one an specific feature within the pdu: globalWebEnabled (0) This bit enables the PDU webpages. globalUsbEnabled (1) This bit enables the USB menu. globalSwitchEnabled (2) This bit enables switching in general. displaySwitchEnabled (3) This bit enables switching through the presentation module. webSwitchEnabled (4) This bit enables switching throuhg the web inteface.
1.3.6.1.4.1.29640.4.3.30Bits {globalWebEnabled(0), globalUsbEnabled(1), globalSwitchEnabled(2), displaySwitchEnabled(3), webSwitchEnabled(4)}read-writecurrent
pduBusAddress
OBJECT-TYPE
Address used to access this PDU via the external bus. When MOD-BUS protocol is used the address is valid between 1-247. When AP-BUS protocol is used the address is valid between 1-65535.
1.3.6.1.4.1.29640.4.3.31Integer32read-writecurrent
pduName
OBJECT-TYPE
Name of the PDU.
1.3.6.1.4.1.29640.4.3.32DisplayString (SIZE(1..32))read-writecurrent
nodeTable
OBJECT-TYPE
A table of the modules on the PDU. Each entry represents an module unit.
1.3.6.1.4.1.29640.4.3.33not-accessiblecurrent
nodeEntry
OBJECT-TYPE
An port entry in the port table.
1.3.6.1.4.1.29640.4.3.33.1not-accessiblecurrent
nodeIndex
OBJECT-TYPE
The node table Index.
1.3.6.1.4.1.29640.4.3.33.1.1Unsigned32 (1..30)not-accessiblecurrent
nodeType
OBJECT-TYPE
Type of the node. TypeUnknown (0) Unknown node. TypePresModChar (1) PM LCD Character Module. TypePresModMono (2) PM Mono Graphics Module. TypePresModGraph (3) PM Color Graphics Module. TypePowerMeter (4) Power meter. TypePowerMeterSwitch (5) Switchable power meter. TypeSwitch (6) Switch only.
1.3.6.1.4.1.29640.4.3.33.1.2INTEGER {typeUnknown(0), typePresModChar(1), typePresModMono(2), typePresModGraph(3), typePowerMeter(4), typePowerMeterSwitch(5), typeSwitch(6)}read-onlycurrent
nodeOutlet
OBJECT-TYPE
The number associated with the physical outlet of the node. The special value of 0 indicates that this entry is not associated with a physical port.
1.3.6.1.4.1.29640.4.3.33.1.3Unsigned32read-onlycurrent
nodeAlarmStatus
OBJECT-TYPE
Array of bits each one indicates an alarm activated in the alarm selector value. TrapCurrHi (0) The current is to high against the high current threshold. TrapCurrLo (1) The current is to low against the low current threshold. TrapVoltHi (2) The voltage is to high against the high voltage threshold. TrapVoltLo (3) The volage is to low against the low voltage threshold. SwitchOn (4) The switch is on against the switch on bitfield. SwitchOff (5) The switch is off against the switch off bitfield.
1.3.6.1.4.1.29640.4.3.33.1.4Bits {trapCurrHi(0), trapCurrLo(1), trapVoltHi(2), trapVoltLo(3), switchOn(4), switchOff(5)}read-onlycurrent
nodePower
OBJECT-TYPE
The measured node power in Kilo Watt's*Hour.
1.3.6.1.4.1.29640.4.3.33.1.5Unsigned32read-onlycurrent
nodeAcurrent
OBJECT-TYPE
The measured ac current at the node (in 1/10th Amperes).
1.3.6.1.4.1.29640.4.3.33.1.6Unsigned32read-onlycurrent
nodePeakCurrent
OBJECT-TYPE
The measured max current since last reset of the node (in 1/10th Amperes).
1.3.6.1.4.1.29640.4.3.33.1.7Unsigned32read-onlycurrent
nodeVoltage
OBJECT-TYPE
The measured voltage on the node.
1.3.6.1.4.1.29640.4.3.33.1.8Unsigned32read-onlycurrent
nodeMinVoltage
OBJECT-TYPE
The measured minimum voltage at the node since last reset.
1.3.6.1.4.1.29640.4.3.33.1.9Unsigned32read-onlycurrent
nodeKvar
OBJECT-TYPE
The Reactive Power. It is the power that magnetic equipment (transformer, motor and relay) needs to produce the magnetizing flux.
1.3.6.1.4.1.29640.4.3.33.1.10Unsigned32read-onlycurrent
nodeFrequency
OBJECT-TYPE
The frequency of alternating current in Hertz. e.g 50 in Europe or 60 in USA.
1.3.6.1.4.1.29640.4.3.33.1.11Unsigned32read-onlycurrent
nodePowerFactor
OBJECT-TYPE
The effective power facton (Cosinus Phi) in percents of the node.
1.3.6.1.4.1.29640.4.3.33.1.12Unsigned32read-onlycurrent
nodeSwitchOperStatus
OBJECT-TYPE
The actual operational Status of the node. Unknown (0) not known status. Off (1) switch is off. On (2) switch is on.
1.3.6.1.4.1.29640.4.3.33.1.13INTEGER {unknown(0), off(1), on(2)}read-onlycurrent
nodeSwitchAdminStatus
OBJECT-TYPE
The desired admin Status of the switch. Unknown (0) not known. Off (1) switch is off. On (2) switch is on.
1.3.6.1.4.1.29640.4.3.33.1.14INTEGER {unknown(0), off(1), on(2)}read-writecurrent
nodeCurrHiThresh
OBJECT-TYPE
The current high threshold (in 1/10th Amperes).
1.3.6.1.4.1.29640.4.3.33.1.15Unsigned32read-writecurrent
nodeCurrLoThresh
OBJECT-TYPE
The current low threshold (in 1/10th Amperes).
1.3.6.1.4.1.29640.4.3.33.1.16Unsigned32read-writecurrent
nodeVoltHiThresh
OBJECT-TYPE
The voltage high threshold.
1.3.6.1.4.1.29640.4.3.33.1.17Unsigned32read-writecurrent
nodeVoltLoThresh
OBJECT-TYPE
The voltage low threshold.
1.3.6.1.4.1.29640.4.3.33.1.18Unsigned32read-writecurrent
nodeAlarmSelector
OBJECT-TYPE
Array of bits each one controls one alarm. TrapCurrHi (0) Enable/disable the high current alarm. TrapCurrLo (1) Enable/disable the low current alarm. TrapVoltHi (2) Enable/disable the high voltage alarm. TrapVoltLo (3) Enable/disable the low voltage alarm. SwitchOn (4) Enable/disable the specific switch on alarm. SwitchOff (5) Enable/disable the specific switch off alarm.
1.3.6.1.4.1.29640.4.3.33.1.19Bits {trapCurrHi(0), trapCurrLo(1), trapVoltHi(2), trapVoltLo(3), switchOn(4), switchOff(5)}read-writecurrent
nodeName
OBJECT-TYPE
The node name. My be set by manager.
1.3.6.1.4.1.29640.4.3.33.1.20DisplayString (SIZE(1..14))read-writecurrent
nodePhase
OBJECT-TYPE
The measured phase of the node. Maybe assigned when not configured in production. PhaseUnknown (0). PhaseL1 (1). PhaseL2 (2). PhaseL3 (3).
1.3.6.1.4.1.29640.4.3.33.1.21INTEGER {phaseUnknown(0), phaseL1(1), phaseL2(2), phaseL3(3)}read-writecurrent
sensorTable
OBJECT-TYPE
A table of the Sensors on the PDU. Each entry represents an an Sensor unit.
1.3.6.1.4.1.29640.4.3.34not-accessiblecurrent
sensorEntry
OBJECT-TYPE
An Sensor Entry in the Sensor table
1.3.6.1.4.1.29640.4.3.34.1not-accessiblecurrent
sensorIndex
OBJECT-TYPE
The Sensor table Index.
1.3.6.1.4.1.29640.4.3.34.1.1Unsigned32 (1..4)not-accessiblecurrent
sensorType
OBJECT-TYPE
Sensor Typ: Measured values are used according to sensor type. Other (0) unknown sensor type. Temperature (1) . Humidity (2). Smoke (3). CO1 (4). Vibration (5). Doorstatus (6).
1.3.6.1.4.1.29640.4.3.34.1.2INTEGER {other(0), temperature(1), humidity(2), smoke(3), co1(4), vibration(5), doorStatus(6)}read-onlycurrent
sensorAlarmStatus
OBJECT-TYPE
Array of bits each one indicates an alarm activated in the alarm selector value.
1.3.6.1.4.1.29640.4.3.34.1.3Bits {trapHi(0), trapLo(1), switchOn(2), switchOff(3), beeperHi(4), beeperLo(5)}read-onlycurrent
sensorValue
OBJECT-TYPE
The measured value of the sensor, units are depending on sensor type.
1.3.6.1.4.1.29640.4.3.34.1.4Integer32read-onlycurrent
sensorSwitchOperStatus
OBJECT-TYPE
The actual operational Status of the switch.
1.3.6.1.4.1.29640.4.3.34.1.5INTEGER {unknown(0), off(1), on(2)}read-onlycurrent
sensorSwitchAdminStatus
OBJECT-TYPE
The desired admin Status of the switch.
1.3.6.1.4.1.29640.4.3.34.1.6INTEGER {unknown(0), off(1), on(2)}read-writecurrent
sensorHiThresh
OBJECT-TYPE
High threshold.
1.3.6.1.4.1.29640.4.3.34.1.7Integer32read-writecurrent
sensorLoThresh
OBJECT-TYPE
Low threshold.
1.3.6.1.4.1.29640.4.3.34.1.8Integer32read-writecurrent
sensorAlarmSelector
OBJECT-TYPE
Array of bits each one controls one alarm. E.g trap, beeper etc.
1.3.6.1.4.1.29640.4.3.34.1.9Bits {trapHi(0), trapLo(1), switchOn(2), switchOff(3), beeperHi(4), beeperLo(5)}read-writecurrent
sensorName
OBJECT-TYPE
The sensor name. May be set by the manager.
1.3.6.1.4.1.29640.4.3.34.1.10DisplayString (SIZE(1..12))read-writecurrent
pduTraps
OBJECT-IDENTITY
1.3.6.1.4.1.29640.4.4
trapType
OBJECT-TYPE
An enumation value to indicate an Alarm trap: pduPduAlarm.
1.3.6.1.4.1.29640.4.4.1INTEGER {voltageHiAlarm(0), voltageLoAlarm(1), currentHiAlarm(2), currentLoAlarm(3), tempHiAlarm(4), tempLoAlarm(5), humidityHiAlarm(6), humidityLoAlarm(7), switchOnAlarm(8), switchOffAlarm(9), powerHiAlarm(10), blackBoxColdTrap(11)}accessible-for-notifycurrent
pduTableType
OBJECT-TYPE
The table type.
1.3.6.1.4.1.29640.4.4.2INTEGER {pduNodeTable(0), pduSensorTable(1)}accessible-for-notifycurrent
trapTableIndex
OBJECT-TYPE
The index of the table entry for which the trap is issued.
1.3.6.1.4.1.29640.4.4.3Integer32accessible-for-notifycurrent
trapThreshHoldType
OBJECT-TYPE
The threshold type for which the trap is made.
1.3.6.1.4.1.29640.4.4.4INTEGER {trapThresholdOther(0), trapThresholdHi(1), trapThresholdLo(2)}accessible-for-notifycurrent
trapThreshHold
OBJECT-TYPE
The threshold reference value.
1.3.6.1.4.1.29640.4.4.5Integer32accessible-for-notifycurrent
apnlTest
OBJECT-IDENTITY
1.3.6.1.4.1.29640.5
apnlDemo
OBJECT-IDENTITY
1.3.6.1.4.1.29640.6
apnlMIBConformance
OBJECT-IDENTITY
1.3.6.1.4.1.29640.7

Notifications

NameOIDStatus
pduVoltageAlarm
NOTIFICATION-TYPE
Voltage alarm.
1.3.6.1.4.1.29640.4.4.6current
pduCurrentAlarm
NOTIFICATION-TYPE
Current alaram.
1.3.6.1.4.1.29640.4.4.7current
pduPowerAlarm
NOTIFICATION-TYPE
Power alarm.
1.3.6.1.4.1.29640.4.4.8current
sensorAlarm
NOTIFICATION-TYPE
Sensor Alarm: Temperature, Humidity or another type. The sensorType indicates the type of alarm. The sensorValue indicate the measured value.
1.3.6.1.4.1.29640.4.4.9current
pduSwitchAlarm
NOTIFICATION-TYPE
Not supported.
1.3.6.1.4.1.29640.4.4.10current