MIBs Depot

ALGPOWER-v2-MIB

Registered at
1.3.6.1.4.1.49136
Namespace
algcom
Source file
ALGPOWER-v2-MIB
Digest
sha256:257337f3e1754d8b7eb27beb66864d06d0adc39af12b88e34738049c7bb02be8

Imports

FromSymbols
SNMPv2-CONFMODULE-COMPLIANCE, NOTIFICATION-GROUP
SNMPv2-SMIMODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, enterprises, iso
SNMPv2-TCDisplayString, TEXTUAL-CONVENTION

Imported by

Nothing in this corpus imports this module.

Load order

Every file a consumer needs in order to load this module, dependencies first.

ALGPOWER-v2-MIB
SNMPv2-CONF
SNMPv2-SMI
SNMPv2-TC

Objects

NameOIDSyntaxAccessStatus
algcom
OBJECT-IDENTITY
1.3.6.1.4.1.49136
upsObjects
OBJECT-IDENTITY
1.3.6.1.4.1.49136.1
output
OBJECT-IDENTITY
1.3.6.1.4.1.49136.1.1
outputVoltage
OBJECT-TYPE
Numeric value of instantaneous output voltage from the source in tenths of a volt. To get the value actual in volt should be divided by 10. Example: Read value 241, actual value 24.1V.
1.3.6.1.4.1.49136.1.1.1INTEGERread-onlymandatory
outputCurrent
OBJECT-TYPE
Numeric value of current output of converter AC/DC. Real value reading in milli ampere. Example: Read value 1087, Actual value 1.087 milli ampere or 1.087A. If the output is '0' the AC/DC is off and the output for the equipments is provide from batteries
1.3.6.1.4.1.49136.1.1.2INTEGERread-onlymandatory
oidNotUsed0
OBJECT-TYPE
OID not used.
1.3.6.1.4.1.49136.1.1.3INTEGERread-onlymandatory
oidNotUsed1
OBJECT-TYPE
OID not used.
1.3.6.1.4.1.49136.1.1.4INTEGERread-onlymandatory
battery
OBJECT-IDENTITY
1.3.6.1.4.1.49136.1.2
batteryVoltage
OBJECT-TYPE
Numeric value of instantaneous voltage of battery bank. To get the actual value in volt must be divided by 10. Example: Read value 240, actual value 24.0V.
1.3.6.1.4.1.49136.1.2.1INTEGERread-onlymandatory
batteryCurrent
OBJECT-TYPE
Numeric value of current in Battery bank. Real value reading in milli ampere. If the value is negative the Battery bank is provide energy for the output. If the value is positive the Battery bank is under charger Example: Read value -2230, Actual value 2,230 ampere and the battery bank is provide this current. Read value 3000, Actual value 3.000 milli ampere and the battery bank is absorve this current.
1.3.6.1.4.1.49136.1.2.2INTEGERread-onlymandatory
chargerStatus
OBJECT-TYPE
Show the status of battery charger: 0 - The battery is not connected in DC UPS; 1 - The battery is voltage incompatible with DC UPS; 2 - The DC UPS is in nobreak mode; 3 - The charger of Battery is in Bulk stage; 4 - The charger of Battery is Absorption stage; 5 - The charger of Battery is Float stage; 6 - The Battery will be disconnected in 30s due to low voltage and the DC-UPS output will be turned off. 7 - The Battery is under test
1.3.6.1.4.1.49136.1.2.3INTEGERread-onlymandatory
input
OBJECT-IDENTITY
1.3.6.1.4.1.49136.1.3
alarmOnBattery
OBJECT-TYPE
Shows the operation mode of DC-UPS: 0 - The DC-UPS output is provide by AC energy. 1 - The DC-UPS output is provide by Battery
1.3.6.1.4.1.49136.1.3.1INTEGERread-onlymandatory
acFail
OBJECT-TYPE
Alarm that alert about AC outages in the last 10 minutes: 0 - DC-UPS in normal operation. 1 - Occur a AC fail in the last 10 minutes.
1.3.6.1.4.1.49136.1.3.2INTEGERread-onlymandatory
batteryCharging
OBJECT-TYPE
Show the status of charging Battery: 1 - The battery is on charging. 0 - The battery is on discharging.
1.3.6.1.4.1.49136.1.3.3INTEGERread-onlymandatory
batteryDischarging
OBJECT-TYPE
Show the status of discharging Battery: 1 - The battery is on discharging. 0 - The battery is on charging.
1.3.6.1.4.1.49136.1.3.4INTEGERread-onlymandatory
overheat
OBJECT-TYPE
Alarm that alert about overtemperature of DC-UPS 1 - The DC-UPS is in condition of overtemperature. 0 - The DC-UPS is in normal condition.
1.3.6.1.4.1.49136.1.3.5INTEGERread-onlymandatory
overload
OBJECT-TYPE
Alarm that alert about overload of DC-UPS 1 - The DC-UPS is in condition of overload. 0 - The DC-UPS is in normal condition.
1.3.6.1.4.1.49136.1.3.6INTEGERread-onlymandatory
fanAfail
OBJECT-TYPE
Alarm that alert about fail in internal FAN A 1 - Internal FAN with fail. 0 - Internal FAN ok
1.3.6.1.4.1.49136.1.3.7INTEGERread-onlymandatory
fanBfail
OBJECT-TYPE
Alarm that alert about fail in internal FAN B 1 - Internal FAN with fail. 0 - Internal FAN ok
1.3.6.1.4.1.49136.1.3.8INTEGERread-onlymandatory
oidNotUsed2
OBJECT-TYPE
OID not used.
1.3.6.1.4.1.49136.1.3.9INTEGERread-onlymandatory
oidNotUsed3
OBJECT-TYPE
OID not used.
1.3.6.1.4.1.49136.1.3.10INTEGERread-onlymandatory
upTime
OBJECT-TYPE
System Up time in hours
1.3.6.1.4.1.49136.1.3.11INTEGERread-onlymandatory
temperature
OBJECT-IDENTITY
1.3.6.1.4.1.49136.1.4
innerTemperature
OBJECT-TYPE
Show the internal temperature of power supply. Uses the unit degree Celsius. Example Read value: 25, temperature is 25degC.
1.3.6.1.4.1.49136.1.4.1INTEGERread-onlymandatory
outerTemperature
OBJECT-TYPE
Show the temperature of external sensor (cable that comes with power supply). Uses the unit degree Celsius. Example Read value: 25, temperature is 25degC.
1.3.6.1.4.1.49136.1.4.2INTEGERread-onlymandatory
heatSinkTemperature
OBJECT-TYPE
Show the temperature of sensor in the heatsink of power supply use the unit degree Celsius. Example Read value: 25, temperature is 25degC.
1.3.6.1.4.1.49136.1.4.3INTEGERread-onlymandatory
watchdog
OBJECT-IDENTITY
1.3.6.1.4.1.49136.1.5
watchdogPing1
OBJECT-TYPE
Alarm indicating the action of watchdog 1 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 1 acted on the output the last 10 minutes. 0 - The Watchdog 1 has not acted in the last 10 minutes.
1.3.6.1.4.1.49136.1.5.1INTEGERread-onlymandatory
watchdogPing2
OBJECT-TYPE
Alarm indicating the action of watchdog 2 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 2 acted on the output the last 10 minutes. 0 - The Watchdog 2 has not acted in the last 10 minutes.
1.3.6.1.4.1.49136.1.5.2INTEGERread-onlymandatory
watchdogPing3
OBJECT-TYPE
Alarm indicating the action of watchdog 3 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 3 acted on the output the last 10 minutes. 0 - The Watchdog 3 has not acted in the last 10 minutes.
1.3.6.1.4.1.49136.1.5.3INTEGERread-onlymandatory
watchdogPing4
OBJECT-TYPE
Alarm indicating the action of watchdog 4 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 4 acted on the output the last 10 minutes. 0 - The Watchdog 4 has not acted in the last 10 minutes.
1.3.6.1.4.1.49136.1.5.4INTEGERread-onlymandatory
watchdogPing5
OBJECT-TYPE
Alarm indicating the action of watchdog 5 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 5 acted on the output the last 10 minutes. 0 - The Watchdog 5 has not acted in the last 10 minutes.
1.3.6.1.4.1.49136.1.5.5INTEGERread-onlymandatory
watchdogPing6
OBJECT-TYPE
Alarm indicating the action of watchdog 6 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 6 acted on the output the last 10 minutes. 0 - The Watchdog 6 has not acted in the last 10 minutes.
1.3.6.1.4.1.49136.1.5.6INTEGERread-onlymandatory
watchdogPing7
OBJECT-TYPE
Alarm indicating the action of watchdog 7 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 7 acted on the output the last 10 minutes. 0 - The Watchdog 7 has not acted in the last 10 minutes.
1.3.6.1.4.1.49136.1.5.7INTEGERread-onlymandatory
watchdogPing8
OBJECT-TYPE
Alarm indicating the action of watchdog 8 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 8 acted on the output the last 10 minutes. 0 - The Watchdog 8 has not acted in the last 10 minutes.
1.3.6.1.4.1.49136.1.5.8INTEGERread-onlymandatory
watchdogPing9
OBJECT-TYPE
Alarm indicating the action of watchdog 9 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 9 acted on the output the last 10 minutes. 0 - The Watchdog 9 has not acted in the last 10 minutes.
1.3.6.1.4.1.49136.1.5.9INTEGERread-onlymandatory
watchdogPing10
OBJECT-TYPE
Alarm indicating the action of watchdog 10 programmed in the last 10 minutes. The watchdog acts on the output by turning it off when not receive response from IP ping command configured. 1 - The watchdog 10 acted on the output the last 10 minutes. 0 - The Watchdog 10 has not acted in the last 10 minutes.
1.3.6.1.4.1.49136.1.5.10INTEGERread-onlymandatory
supply
OBJECT-IDENTITY
1.3.6.1.4.1.49136.1.6
supplyVoltage
OBJECT-TYPE
The supply AC voltage decivolt [dV] Numeric value of instantaneous input voltage. An optional sensor is required to read this value. To get the actual value in volt it should be divided by 10. Example: Read value 2410, actual value 241 Vac.
1.3.6.1.4.1.49136.1.6.1INTEGERread-onlymandatory
installation
OBJECT-IDENTITY
1.3.6.1.4.1.49136.1.7
popName
OBJECT-TYPE
PoP name
1.3.6.1.4.1.49136.1.7.1DisplayString (SIZE(30))read-onlymandatory
facilityAddr
OBJECT-TYPE
Facility address
1.3.6.1.4.1.49136.1.7.2DisplayString (SIZE(40))read-onlymandatory
facilityCity
OBJECT-TYPE
Facility city
1.3.6.1.4.1.49136.1.7.3DisplayString (SIZE(30))read-onlymandatory
instDate
OBJECT-TYPE
Installation date
1.3.6.1.4.1.49136.1.7.4DisplayString (SIZE(10))read-onlymandatory
batCapacity
OBJECT-TYPE
Battery capacity
1.3.6.1.4.1.49136.1.7.5INTEGERread-onlymandatory
batBrand
OBJECT-TYPE
Battery brand
1.3.6.1.4.1.49136.1.7.6DisplayString (SIZE(30))read-onlymandatory
batInstDate
OBJECT-TYPE
Battery installation date
1.3.6.1.4.1.49136.1.7.7DisplayString (SIZE(10))read-onlymandatory
respPers
OBJECT-TYPE
Responsible person
1.3.6.1.4.1.49136.1.7.8DisplayString (SIZE(50))read-onlymandatory
bat_tst
OBJECT-IDENTITY
1.3.6.1.4.1.49136.1.8
btst_date
OBJECT-TYPE
Battery test execution date (dd/mm/yyyy)
1.3.6.1.4.1.49136.1.8.1DisplayString (SIZE(10))read-onlymandatory
btst_status
OBJECT-TYPE
Battery test status 0 - NEVER DONE 1 - Passed 2 - Running 3 - Aborted 4 - Failed
1.3.6.1.4.1.49136.1.8.2INTEGERread-onlymandatory
btst_duration
OBJECT-TYPE
Programmed test duration in minutes * 999 - Perform the test until battery is fully discharged
1.3.6.1.4.1.49136.1.8.3INTEGERread-onlymandatory
btst_elapsed
OBJECT-TYPE
Elapsed time in current\last battery test
1.3.6.1.4.1.49136.1.8.4INTEGERread-onlymandatory
btst_volt_i
OBJECT-TYPE
The battery initial voltage [dV] Numeric value of battery voltage when starting the battery test. Example: Read value 241, actual value 24.1 V.
1.3.6.1.4.1.49136.1.8.5INTEGERread-onlymandatory
btst_amp_i
OBJECT-TYPE
The battery initial cuurent [mA] Numeric value of battery current when starting the battery test. Example: Read value 1522, actual value 1.55 A.
1.3.6.1.4.1.49136.1.8.6INTEGERread-onlymandatory
btst_volt_f
OBJECT-TYPE
The battery final voltage [dV] Numeric value of battery voltage when the battery test is done. Example: Read value 225, actual value 22.5 V.
1.3.6.1.4.1.49136.1.8.7INTEGERread-onlymandatory
btst_amp_f
OBJECT-TYPE
The battery initial cuurent [mA] Numeric value of battery current when the battery test is done. Example: Read value 1485, actual value 1.48 A.
1.3.6.1.4.1.49136.1.8.8INTEGERread-onlymandatory