ACS-MIB
- Registered at
- 1.3.6.1.4.1.10418.16
- Last updated
- 2010-10-10 00:00
- Organization
- Avocent Corporation
- Revisions
- 2010-10-10 00:00, 2009-12-11 00:00, 2007-09-17 00:00
- Namespace
- avocent
- Source file
ACS-MIB- Digest
sha256:cac9134bc4a681218463547e6c96fbe008a85f01ea574abafad674bad95b6564
Description
This module defines the Avocent MIB extensions to ACS60xx products.
Contact
postal : Avocent Corporation 47281 Bayside Parkway Fremont, CA 94538, USA e-mail : Technical Support techsupport@avocent.com
Imports
| From | Symbols |
|---|---|
| IF-MIB | InterfaceIndex, InterfaceIndexOrZero |
| SNMPv2-CONF | MODULE-COMPLIANCE, NOTIFICATION-GROUP |
| SNMPv2-SMI | Counter32, Gauge32, Integer32, IpAddress, MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-IDENTITY, OBJECT-TYPE, TRAP-TYPE, TimeTicks, enterprises, iso |
| SNMPv2-TC | DisplayString, PhysAddress, TEXTUAL-CONVENTION |
Imported by
Nothing in this corpus imports this module.
Load order
Every file a consumer needs in order to load this module, dependencies first.
ACS-MIB IANAifType-MIB IF-MIB SNMPv2-CONF SNMPv2-MIB SNMPv2-SMI SNMPv2-TC
Textual conventions
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| PowerSupplyState type | ||||
| SerialPortPinOut type | ||||
| SerialPortSignalState type | ||||
| SerialPortSpeed type |
Objects
| Name | OID | Syntax | Access | Status |
|---|---|---|---|---|
| acsProducts OBJECT-IDENTITY | 1.3.6.1.4.1.10418.16.1 | |||
| acs6016 OBJECT-IDENTITY | 1.3.6.1.4.1.10418.16.1.1 | |||
| acs6032 OBJECT-IDENTITY | 1.3.6.1.4.1.10418.16.1.2 | |||
| acs6048 OBJECT-IDENTITY | 1.3.6.1.4.1.10418.16.1.3 | |||
| acs6004 OBJECT-IDENTITY | 1.3.6.1.4.1.10418.16.1.4 | |||
| acs6008 OBJECT-IDENTITY | 1.3.6.1.4.1.10418.16.1.5 | |||
| acsManagement OBJECT-IDENTITY | 1.3.6.1.4.1.10418.16.2 | |||
| acsAppliance OBJECT-IDENTITY | 1.3.6.1.4.1.10418.16.2.1 | |||
| acsHostName OBJECT-TYPE The appliance name | 1.3.6.1.4.1.10418.16.2.1.1 | DisplayString (SIZE(0..32)) | read-only | current |
| acsProductModel OBJECT-TYPE The appliance product model | 1.3.6.1.4.1.10418.16.2.1.2 | DisplayString (SIZE(0..50)) | read-only | current |
| acsPartNumber OBJECT-TYPE The part number of this appliance as shown on the label attached or imprinted on the appliance. | 1.3.6.1.4.1.10418.16.2.1.3 | DisplayString (SIZE(0..32)) | read-only | current |
| acsSerialNumber OBJECT-TYPE The serial number of this appliance as shown on the label attached or imprinted on the appliance. | 1.3.6.1.4.1.10418.16.2.1.4 | DisplayString (SIZE(0..32)) | read-only | current |
| acsEIDNumber OBJECT-TYPE The electronic ID number (EID) of this appliance as shown on the label attached or imprinted on the appliance. | 1.3.6.1.4.1.10418.16.2.1.5 | DisplayString (SIZE(0..32)) | read-only | current |
| acsBootcodeVersion OBJECT-TYPE The version of the bootcode of this appliance. | 1.3.6.1.4.1.10418.16.2.1.6 | DisplayString (SIZE(0..32)) | read-only | current |
| acsFirmwareVersion OBJECT-TYPE The version of the firmware of this appliance. | 1.3.6.1.4.1.10418.16.2.1.7 | DisplayString (SIZE(0..32)) | read-only | current |
| acsPowerSupply OBJECT-IDENTITY It gives information about Power Supply of this appliance | 1.3.6.1.4.1.10418.16.2.1.8 | current | ||
| acsPowerSupplyNumber OBJECT-TYPE Number of the power supplies of this appliance | 1.3.6.1.4.1.10418.16.2.1.8.1 | Integer32 | read-only | current |
| acsPowerSupplyStatePw1 OBJECT-TYPE State of the first power supply | 1.3.6.1.4.1.10418.16.2.1.8.2 | PowerSupplyState | read-only | current |
| acsPowerSupplyStatePw2 OBJECT-TYPE State of the second power supply | 1.3.6.1.4.1.10418.16.2.1.8.3 | PowerSupplyState | read-only | current |
| acsReboot OBJECT-TYPE A set value of reboot(2) will reboot the appliance. noAction(1) = always returned in a GET. Does nothing if SET. reboot(2) = when SET the appliance immediately reboots. | 1.3.6.1.4.1.10418.16.2.1.9 | INTEGER {noAction(1), reboot(2)} | read-write | current |
| acsSessions OBJECT-IDENTITY | 1.3.6.1.4.1.10418.16.2.2 | |||
| acsActiveSessionsNumberOfSession OBJECT-TYPE Number of active sessions. | 1.3.6.1.4.1.10418.16.2.2.1 | Integer32 | read-only | current |
| acsActiveSessionsTable OBJECT-TYPE This table contains the list of active sessions. | 1.3.6.1.4.1.10418.16.2.2.2 | not-accessible | current | |
| acsActiveSessionsTableEntry OBJECT-TYPE each entry has the information about the active session | 1.3.6.1.4.1.10418.16.2.2.2.1 | not-accessible | current | |
| acsActiveSessionsTableIndex OBJECT-TYPE A unique index representing an entry in this table. | 1.3.6.1.4.1.10418.16.2.2.2.1.1 | InterfaceIndexOrZero | read-only | current |
| acsActiveSessionsTableUser OBJECT-TYPE The name of the user that opens this session. | 1.3.6.1.4.1.10418.16.2.2.2.1.2 | DisplayString (SIZE(0..32)) | read-only | current |
| acsActiveSessionsTableGroup OBJECT-TYPE The name of the group that the user belongs to. | 1.3.6.1.4.1.10418.16.2.2.2.1.3 | DisplayString (SIZE(0..32)) | read-only | current |
| acsActiveSessionsTableType OBJECT-TYPE The session type. | 1.3.6.1.4.1.10418.16.2.2.2.1.4 | DisplayString (SIZE(0..32)) | read-only | current |
| acsActiveSessionsTableConnection OBJECT-TYPE Connection type. | 1.3.6.1.4.1.10418.16.2.2.2.1.5 | DisplayString (SIZE(0..32)) | read-only | current |
| acsActiveSessionsTableSessionTime OBJECT-TYPE Time of the session | 1.3.6.1.4.1.10418.16.2.2.2.1.6 | DisplayString (SIZE(0..32)) | read-only | current |
| acsActiveSessionsTableFrom OBJECT-TYPE The source IP address of the session. | 1.3.6.1.4.1.10418.16.2.2.2.1.7 | DisplayString (SIZE(0..32)) | read-only | current |
| acsActiveSessionsTableKill OBJECT-TYPE A set value of killSession(2) will kill the session. noAction(1) = always returned in a GET. Does nothing if SET. killSession(2)= when SET the appliance immediately kills the session. | 1.3.6.1.4.1.10418.16.2.2.2.1.8 | INTEGER {noAction(1), killSession(2)} | read-write | current |
| acsSerialPort OBJECT-IDENTITY | 1.3.6.1.4.1.10418.16.2.3 | |||
| acsSerialPortNumberOfPorts OBJECT-TYPE Number of Serial Ports (physical serial port plus Aux Port. | 1.3.6.1.4.1.10418.16.2.3.1 | Integer32 | read-only | current |
| acsSerialPortTable OBJECT-TYPE This table contains information about serial ports. | 1.3.6.1.4.1.10418.16.2.3.2 | not-accessible | current | |
| acsSerialPortTableEntry OBJECT-TYPE each entry has the information about specific serial port. | 1.3.6.1.4.1.10418.16.2.3.2.1 | not-accessible | current | |
| acsSerialPortTableNumber OBJECT-TYPE A unique index representing an entry in this table. It is the number of the serial port. For AUX port, the number will be the number of physical serial ports plus 1. | 1.3.6.1.4.1.10418.16.2.3.2.1.1 | Integer32 (1..49) | read-only | current |
| acsSerialPortTableDeviceName OBJECT-TYPE The associated device name for the serial port. | 1.3.6.1.4.1.10418.16.2.3.2.1.2 | DisplayString (SIZE(0..25)) | read-only | current |
| acsSerialPortTableStatus OBJECT-TYPE The status of the serial port: disabled(1) = it was configured as disable. idle(2) = there is not any session opened in this port. inUse(3) = there is session(s) opened in this port. | 1.3.6.1.4.1.10418.16.2.3.2.1.3 | INTEGER {disabled(1), idle(2), inUse(3)} | read-only | current |
| acsSerialPortTableName OBJECT-TYPE Name associated with this serial port. | 1.3.6.1.4.1.10418.16.2.3.2.1.4 | DisplayString (SIZE(0..25)) | read-only | current |
| acsSerialPortTableProfile OBJECT-TYPE Configured profile for this serial port. | 1.3.6.1.4.1.10418.16.2.3.2.1.5 | INTEGER {casProfile(1), tsProfile(2), dialInProfile(3), powerProfile(4)} | read-only | current |
| acsSerialPortTablePinOut OBJECT-TYPE RJ45 Pin-out configured for this serial port. | 1.3.6.1.4.1.10418.16.2.3.2.1.6 | SerialPortPinOut | read-only | current |
| acsSerialPortTableComSpeed OBJECT-TYPE Speed configured for this serial port. | 1.3.6.1.4.1.10418.16.2.3.2.1.7 | SerialPortSpeed | read-only | current |
| acsSerialPortTableComParity OBJECT-TYPE Parity configured for this serial port. | 1.3.6.1.4.1.10418.16.2.3.2.1.8 | INTEGER {none(1), odd(2), even(3)} | read-only | current |
| acsSerialPortTableComDataSize OBJECT-TYPE Data Size configured for this serial port. | 1.3.6.1.4.1.10418.16.2.3.2.1.9 | Integer32 | read-only | current |
| acsSerialPortTableComStopBits OBJECT-TYPE Number of Stop Bits configured for this serial port. | 1.3.6.1.4.1.10418.16.2.3.2.1.10 | Integer32 | read-only | current |
| acsSerialPortTableComFlowControl OBJECT-TYPE Flow Control configured for this serial port. | 1.3.6.1.4.1.10418.16.2.3.2.1.11 | INTEGER {none(1), hardware(2), software(3)} | read-only | current |
| acsSerialPortTableSignalStateDTR OBJECT-TYPE State of the DTR RS-232C signal. | 1.3.6.1.4.1.10418.16.2.3.2.1.12 | SerialPortSignalState | read-only | current |
| acsSerialPortTableSignalStateDCD OBJECT-TYPE State of the DCD RS-232C signal. | 1.3.6.1.4.1.10418.16.2.3.2.1.13 | SerialPortSignalState | read-only | current |
| acsSerialPortTableSignalStateRTS OBJECT-TYPE State of the RTS RS-232C signal. | 1.3.6.1.4.1.10418.16.2.3.2.1.14 | SerialPortSignalState | read-only | current |
| acsSerialPortTableSignalStateCTS OBJECT-TYPE State of the CTS RS-232C signal. | 1.3.6.1.4.1.10418.16.2.3.2.1.15 | SerialPortSignalState | read-only | current |
| acsSerialPortTableTxBytes OBJECT-TYPE The number of transmited bytes by the serial port. | 1.3.6.1.4.1.10418.16.2.3.2.1.16 | Integer32 | read-only | current |
| acsSerialPortTableRxBytes OBJECT-TYPE The number of received bytes by the serial port. | 1.3.6.1.4.1.10418.16.2.3.2.1.17 | Integer32 | read-only | current |
| acsSerialPortTableFrameError OBJECT-TYPE The number of frame error detected in the serial port. | 1.3.6.1.4.1.10418.16.2.3.2.1.18 | Integer32 | read-only | current |
| acsSerialPortTableParityError OBJECT-TYPE The number of parity error detected in the serial port. | 1.3.6.1.4.1.10418.16.2.3.2.1.19 | Integer32 | read-only | current |
| acsSerialPortTableBreak OBJECT-TYPE The number of break detected in the serial port. | 1.3.6.1.4.1.10418.16.2.3.2.1.20 | Integer32 | read-only | current |
| acsSerialPortTableOverrun OBJECT-TYPE The number of overrun error detected in the serial port. | 1.3.6.1.4.1.10418.16.2.3.2.1.21 | Integer32 | read-only | current |
| acsPowerMgmt OBJECT-IDENTITY | 1.3.6.1.4.1.10418.16.2.5 | |||
| acsPowerMgmtNumSerialPorts OBJECT-TYPE The number of Serial Ports that has PDU connected on the appliance. | 1.3.6.1.4.1.10418.16.2.5.1 | Integer32 | read-only | current |
| acsPowerMgmtSerialTable OBJECT-TYPE Information about each serial port thas has PDU connect. | 1.3.6.1.4.1.10418.16.2.5.2 | not-accessible | current | |
| acsPowerMgmtSerialTableEntry OBJECT-TYPE Information about each serial port thas has PDU connect. | 1.3.6.1.4.1.10418.16.2.5.2.1 | not-accessible | current | |
| acsPowerMgmtSerialTableIndex OBJECT-TYPE The index of the register. | 1.3.6.1.4.1.10418.16.2.5.2.1.1 | InterfaceIndex | read-only | current |
| acsPowerMgmtSerialTablePortNumber OBJECT-TYPE The number of the serial port when the PDU is connected. | 1.3.6.1.4.1.10418.16.2.5.2.1.2 | Integer32 | read-only | current |
| acsPowerMgmtSerialTableDeviceName OBJECT-TYPE The device name of this serial port. | 1.3.6.1.4.1.10418.16.2.5.2.1.3 | DisplayString | read-only | current |
| acsPowerMgmtSerialTableNumberPDUs OBJECT-TYPE Total number of units connected in this serial port. | 1.3.6.1.4.1.10418.16.2.5.2.1.4 | Integer32 | read-only | current |
| acsPowerMgmtPDUTable OBJECT-TYPE This table contains the list of detected PDUs. | 1.3.6.1.4.1.10418.16.2.5.3 | not-accessible | current | |
| acsPowerMgmtPDUTableEntry OBJECT-TYPE each entry has the information about the PDU. | 1.3.6.1.4.1.10418.16.2.5.3.1 | not-accessible | current | |
| acsPowerMgmtPDUTablePortNumber OBJECT-TYPE Number of serial port when the PDU is connected. | 1.3.6.1.4.1.10418.16.2.5.3.1.1 | InterfaceIndex | read-only | current |
| acsPowerMgmtPDUTablePduIndex OBJECT-TYPE A PDU position in the chain. | 1.3.6.1.4.1.10418.16.2.5.3.1.2 | InterfaceIndexOrZero | read-only | current |
| acsPowerMgmtPDUTablePduId OBJECT-TYPE PDU identification. | 1.3.6.1.4.1.10418.16.2.5.3.1.3 | DisplayString | read-only | current |
| acsPowerMgmtPDUTablePortName OBJECT-TYPE Name of serial port when the PDU is connected. | 1.3.6.1.4.1.10418.16.2.5.3.1.4 | DisplayString | read-only | current |
| acsPowerMgmtPDUTableModel OBJECT-TYPE Model of the PDU. | 1.3.6.1.4.1.10418.16.2.5.3.1.5 | DisplayString | read-only | current |
| acsPowerMgmtPDUTableVendor OBJECT-TYPE Vendor of the PDU. | 1.3.6.1.4.1.10418.16.2.5.3.1.6 | DisplayString | read-only | current |
| acsPowerMgmtPDUTableFirmwareVersion OBJECT-TYPE Version of the PDU firmware. | 1.3.6.1.4.1.10418.16.2.5.3.1.7 | DisplayString | read-only | current |
| acsPowerMgmtPDUTableNumberOfOutlets OBJECT-TYPE Number of outlets of the PDU. | 1.3.6.1.4.1.10418.16.2.5.3.1.8 | Integer32 | read-only | current |
| acsPowerMgmtPDUTableCurrentNOS OBJECT-TYPE Number of current sensors in the PDU. | 1.3.6.1.4.1.10418.16.2.5.3.1.9 | Integer32 | read-only | obsolete |
| acsPowerMgmtPDUTableCurrent1Value OBJECT-TYPE Current of the sensor 1 in this PDU unit in AMP. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.) | 1.3.6.1.4.1.10418.16.2.5.3.1.10 | Integer32 | read-only | obsolete |
| acsPowerMgmtPDUTableCurrent1Max OBJECT-TYPE Maximum current of the sensor 1 in this PDU unit in AMP. When the PDU does not have support for maximum value, the value will be 0. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.) Clear this value, set it with Zero value. | 1.3.6.1.4.1.10418.16.2.5.3.1.11 | Integer32 | read-write | obsolete |
| acsPowerMgmtPDUTableCurrent2Value OBJECT-TYPE Current of the sensor 2 in this PDU unit in AMP. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.) | 1.3.6.1.4.1.10418.16.2.5.3.1.12 | Integer32 | read-only | obsolete |
| acsPowerMgmtPDUTableCurrent2Max OBJECT-TYPE Maximum current of the sensor 2 in this PDU unit in AMP. When the PDU does not have support for maximum value, the value will be 0. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.) Clear this value, set it with Zero value. | 1.3.6.1.4.1.10418.16.2.5.3.1.13 | Integer32 | read-write | obsolete |
| acsPowerMgmtPDUTableCurrent3Value OBJECT-TYPE Current of the sensor 3 in this PDU unit in AMP. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.) | 1.3.6.1.4.1.10418.16.2.5.3.1.14 | Integer32 | read-only | obsolete |
| acsPowerMgmtPDUTableCurrent3Max OBJECT-TYPE Maximum current of the sensor 3 in this PDU unit in AMP. When the PDU does not have support for maximum value, the value will be 0. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : value is 5, the current is 0.5 AMP.) Clear this value, set it with Zero value. | 1.3.6.1.4.1.10418.16.2.5.3.1.15 | Integer32 | read-write | obsolete |
| acsPowerMgmtPDUTableTemperatureNOS OBJECT-TYPE Number of temperature sensors in the PDU. | 1.3.6.1.4.1.10418.16.2.5.3.1.16 | Integer32 | read-only | obsolete |
| acsPowerMgmtPDUTableTemperature1Value OBJECT-TYPE Temperature of this PM unit in Celsius degrees. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). | 1.3.6.1.4.1.10418.16.2.5.3.1.17 | Integer32 | read-only | obsolete |
| acsPowerMgmtPDUTableTemperature1Max OBJECT-TYPE Maximum temperature detected in this PM unit in Celsius degrees. The value will be Zero when the PDU does not have support for maximum value. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). Set with Zero value to clear the max. temperature. | 1.3.6.1.4.1.10418.16.2.5.3.1.18 | Integer32 | read-write | obsolete |
| acsPowerMgmtPDUTableTemperature2Value OBJECT-TYPE Temperature of this PM unit in Celsius degrees. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). | 1.3.6.1.4.1.10418.16.2.5.3.1.19 | Integer32 | read-only | obsolete |
| acsPowerMgmtPDUTableTemperature2Max OBJECT-TYPE Maximum temperature detected in this PM unit in Celsius degrees. The value will be Zero when the PDU does not have support for maximum value. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). Set with Zero value to clear the max. temperature. | 1.3.6.1.4.1.10418.16.2.5.3.1.20 | Integer32 | read-write | obsolete |
| acsPowerMgmtPDUTableTemperature3Value OBJECT-TYPE Temperature of this PM unit in Celsius degrees. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). | 1.3.6.1.4.1.10418.16.2.5.3.1.21 | Integer32 | read-only | obsolete |
| acsPowerMgmtPDUTableTemperature3Max OBJECT-TYPE Maximum temperature detected in this PM unit in Celsius degrees. The value will be Zero when the PDU does not have support for maximum value. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (Ex. : value is 240, the temperature is 24 Celsius.) If the temperature measurement is not installed this value will be 0. Valid values are 5 to 999 ( 0.5 to 99.9 Celsius). Set with Zero value to clear the max. temperature. | 1.3.6.1.4.1.10418.16.2.5.3.1.22 | Integer32 | read-write | obsolete |
| acsPowerMgmtPDUTableHumidityNOS OBJECT-TYPE Number of humidity sensors in the PDU. | 1.3.6.1.4.1.10418.16.2.5.3.1.23 | Integer32 | read-only | obsolete |
| acsPowerMgmtPDUTableHumidity1Value OBJECT-TYPE Humidity of this PM unit . If the humidity measurement is not installed this value will be 0. | 1.3.6.1.4.1.10418.16.2.5.3.1.24 | Integer32 | read-only | obsolete |
| acsPowerMgmtPDUTableHumidity1Max OBJECT-TYPE Maximum humidity detected in this PM unit. If the humidity measurement is not installed or the PDU does not have support for maximum value this value will be 0. Set with Zero value to clear the max. temperature. | 1.3.6.1.4.1.10418.16.2.5.3.1.25 | Integer32 | read-write | obsolete |
| acsPowerMgmtPDUTableHumidity2Value OBJECT-TYPE Humidity of this PM unit . If the humidity measurement is not installed this value will be 0. | 1.3.6.1.4.1.10418.16.2.5.3.1.26 | Integer32 | read-only | obsolete |
| acsPowerMgmtPDUTableHumidity2Max OBJECT-TYPE Maximum humidity detected in this PM unit. If the humidity measurement is not installed or the PDU does not have support for maximum value this value will be 0. Set with Zero value to clear the max. temperature. | 1.3.6.1.4.1.10418.16.2.5.3.1.27 | Integer32 | read-write | obsolete |
| acsPowerMgmtPDUTableHumidity3Value OBJECT-TYPE Humidity of this PM unit . If the humidity measurement is not installed this value will be 0. | 1.3.6.1.4.1.10418.16.2.5.3.1.28 | Integer32 | read-only | obsolete |
| acsPowerMgmtPDUTableHumidity3Max OBJECT-TYPE Maximum humidity detected in this PM unit. If the humidity measurement is not installed or the PDU does not have support for maximum value this value will be 0. Set with Zero value to clear the max. temperature. | 1.3.6.1.4.1.10418.16.2.5.3.1.29 | Integer32 | read-write | obsolete |
| acsPowerMgmtPDUTableVoltageNOS OBJECT-TYPE Number of voltage sensors in the PDU. | 1.3.6.1.4.1.10418.16.2.5.3.1.30 | Integer32 | read-only | obsolete |
| acsPowerMgmtPDUTableVoltage1Value OBJECT-TYPE Voltage of this sensor in this PDU unit. | 1.3.6.1.4.1.10418.16.2.5.3.1.31 | Integer32 | read-only | obsolete |
| acsPowerMgmtPDUTableVoltage1Max OBJECT-TYPE Maximum voltage of this sensor in this PDU unit. Set with Zero value to clear the maximum voltage. | 1.3.6.1.4.1.10418.16.2.5.3.1.32 | Integer32 | read-write | obsolete |
| acsPowerMgmtPDUTableVoltage2Value OBJECT-TYPE Voltage of this sensor in this PDU unit. | 1.3.6.1.4.1.10418.16.2.5.3.1.33 | Integer32 | read-only | obsolete |
| acsPowerMgmtPDUTableVoltage2Max OBJECT-TYPE Maximum voltage of this sensor in this PDU unit. Set with Zero value to clear the maximum voltage. | 1.3.6.1.4.1.10418.16.2.5.3.1.34 | Integer32 | read-write | obsolete |
| acsPowerMgmtPDUTableVoltage3Value OBJECT-TYPE Voltage of this sensor in this PDU unit. | 1.3.6.1.4.1.10418.16.2.5.3.1.35 | Integer32 | read-only | obsolete |
| acsPowerMgmtPDUTableVoltage3Max OBJECT-TYPE Maximum voltage of this sensor in this PDU unit. Set with Zero value to clear the maximum voltage. | 1.3.6.1.4.1.10418.16.2.5.3.1.36 | Integer32 | read-write | obsolete |
| acsPowerMgmtPDUTableNumberOfPhases OBJECT-TYPE Number of phases of this PDU unit. | 1.3.6.1.4.1.10418.16.2.5.3.1.37 | INTEGER {single-phase(0), three-phase(3)} | read-only | current |
| acsPowerMgmtPDUTableNumberOfBanks OBJECT-TYPE Number of banks of this PDU unit. | 1.3.6.1.4.1.10418.16.2.5.3.1.38 | Integer32 | read-only | current |
| acsPowerMgmtPDUTableCurrentValue OBJECT-TYPE Actual value of current sensor in this PDU.( A x 10 ) | 1.3.6.1.4.1.10418.16.2.5.3.1.39 | Integer32 | read-only | current |
| acsPowerMgmtPDUTableCurrentMax OBJECT-TYPE Max detected value of current sensor in this PDU.( A x 10 ) | 1.3.6.1.4.1.10418.16.2.5.3.1.40 | Integer32 | read-only | current |
| acsPowerMgmtPDUTableCurrentMin OBJECT-TYPE Min detected value of current sensor in this PDU.( A x 10 ) | 1.3.6.1.4.1.10418.16.2.5.3.1.41 | Integer32 | read-only | current |
| acsPowerMgmtPDUTableCurrentAvg OBJECT-TYPE Average value for current sensor in this PDU.( A x 10 ) | 1.3.6.1.4.1.10418.16.2.5.3.1.42 | Integer32 | read-only | current |
| acsPowerMgmtPDUTableCurrentReset OBJECT-TYPE Reset max, min and avg values of current. | 1.3.6.1.4.1.10418.16.2.5.3.1.43 | INTEGER {no-action(1), reset(2)} | read-write | current |
| acsPowerMgmtPDUTableVoltageType OBJECT-TYPE Type of voltage values. | 1.3.6.1.4.1.10418.16.2.5.3.1.44 | INTEGER {none-sensor(0), estimated(1), read(2)} | read-only | current |
| acsPowerMgmtPDUTableVoltageValue OBJECT-TYPE Actual value of voltage sensor in this PDU unit.( V ) | 1.3.6.1.4.1.10418.16.2.5.3.1.45 | Integer32 | read-only | current |
| acsPowerMgmtPDUTableVoltageMax OBJECT-TYPE Max detected value of voltage sensor in this PDU unit.( V ) | 1.3.6.1.4.1.10418.16.2.5.3.1.46 | Integer32 | read-only | current |
| acsPowerMgmtPDUTableVoltageMin OBJECT-TYPE Min detected value of voltage sensor in this PDU unit.( V ) | 1.3.6.1.4.1.10418.16.2.5.3.1.47 | Integer32 | read-only | current |
| acsPowerMgmtPDUTableVoltageAvg OBJECT-TYPE Average value for voltage sensor in this PDU unit.( V ) | 1.3.6.1.4.1.10418.16.2.5.3.1.48 | Integer32 | read-only | current |
| acsPowerMgmtPDUTableVoltageReset OBJECT-TYPE Reset max, min and avg values of voltage. | 1.3.6.1.4.1.10418.16.2.5.3.1.49 | INTEGER {no-action(1), reset(2)} | read-write | current |
| acsPowerMgmtPDUTablePowerType OBJECT-TYPE Type of power consumption values.( W x 10 ) | 1.3.6.1.4.1.10418.16.2.5.3.1.50 | INTEGER {none-sensor(0), estimated(1), read(2)} | read-only | current |
| acsPowerMgmtPDUTablePowerValue OBJECT-TYPE Actual value of power consumption in this PDU unit.( W x 10 ) | 1.3.6.1.4.1.10418.16.2.5.3.1.51 | Integer32 | read-only | current |
| acsPowerMgmtPDUTablePowerMax OBJECT-TYPE Max detected value of power consumption in this PDU unit.( W x 10 ) | 1.3.6.1.4.1.10418.16.2.5.3.1.52 | Integer32 | read-only | current |
| acsPowerMgmtPDUTablePowerMin OBJECT-TYPE Min detected value of power consumption in this PDU unit.( W x 10 ) | 1.3.6.1.4.1.10418.16.2.5.3.1.53 | Integer32 | read-only | current |
| acsPowerMgmtPDUTablePowerAvg OBJECT-TYPE Average value for power consumption in this PDU unit.( W x 10 ) | 1.3.6.1.4.1.10418.16.2.5.3.1.54 | Integer32 | read-only | current |
| acsPowerMgmtPDUTablePowerReset OBJECT-TYPE Reset max, min and avg values of power consumption. | 1.3.6.1.4.1.10418.16.2.5.3.1.55 | INTEGER {no-action(1), reset(2)} | read-write | current |
| acsPowerMgmtPDUTablePowerFactorType OBJECT-TYPE Type of power factor values. | 1.3.6.1.4.1.10418.16.2.5.3.1.56 | INTEGER {none-sensor(0), estimated(1), read(2)} | read-only | current |
| acsPowerMgmtPDUTablePowerFactorValue OBJECT-TYPE Actual value of power factor in this PDU unit.( PF x 100 ) | 1.3.6.1.4.1.10418.16.2.5.3.1.57 | Integer32 | read-only | current |
| acsPowerMgmtPDUTablePowerFactorMax OBJECT-TYPE Max detected value of power factor in this PDU unit.( PF x 100 ) | 1.3.6.1.4.1.10418.16.2.5.3.1.58 | Integer32 | read-only | current |
| acsPowerMgmtPDUTablePowerFactorMin OBJECT-TYPE Min detected value of power factor in this PDU unit.( PF x 100 ) | 1.3.6.1.4.1.10418.16.2.5.3.1.59 | Integer32 | read-only | current |
| acsPowerMgmtPDUTablePowerFactorAvg OBJECT-TYPE Average value for power factor in this PDU unit.( PF x 100 ) | 1.3.6.1.4.1.10418.16.2.5.3.1.60 | Integer32 | read-only | current |
| acsPowerMgmtPDUTablePowerFactorReset OBJECT-TYPE Reset max, min and avg values of power factor. | 1.3.6.1.4.1.10418.16.2.5.3.1.61 | INTEGER {no-action(1), reset(2)} | read-write | current |
| acsPowerMgmtPDUTableAlarm OBJECT-TYPE Show the PDU alarm status. | 1.3.6.1.4.1.10418.16.2.5.3.1.62 | INTEGER {normal(1), blow-fuse(2), hw-ocp(3), high-critical(4), high-warning(5), low-warning(6), low-critical(7)} | read-only | current |
| acsPowerMgmtPDUTableEnvSensors OBJECT-TYPE Number of environmental sensor in this PDU. | 1.3.6.1.4.1.10418.16.2.5.3.1.63 | Integer32 | read-only | current |
| acsPowerMgmtTotalNumberOfOutlets OBJECT-TYPE Number of outlets managed by the appliance. | 1.3.6.1.4.1.10418.16.2.5.4 | Integer32 | read-only | current |
| acsPowerMgmtOutletsTable OBJECT-TYPE This table contains the information about outlets. | 1.3.6.1.4.1.10418.16.2.5.5 | not-accessible | current | |
| acsPowerMgmtOutletsTableEntry OBJECT-TYPE each entry has the information about the outlet. | 1.3.6.1.4.1.10418.16.2.5.5.1 | not-accessible | current | |
| acsPowerMgmtOutletsTablePortNumber OBJECT-TYPE Serial Port number. | 1.3.6.1.4.1.10418.16.2.5.5.1.1 | InterfaceIndex | read-only | current |
| acsPowerMgmtOutletsTablePduNumber OBJECT-TYPE Index. | 1.3.6.1.4.1.10418.16.2.5.5.1.2 | InterfaceIndex | read-only | current |
| acsPowerMgmtOutletsTableNumber OBJECT-TYPE Number of the outlet in the PDU. | 1.3.6.1.4.1.10418.16.2.5.5.1.3 | InterfaceIndex | read-only | current |
| acsPowerMgmtOutletsTableName OBJECT-TYPE Name of the outlet. | 1.3.6.1.4.1.10418.16.2.5.5.1.4 | DisplayString | read-only | current |
| acsPowerMgmtOutletsTableStatus OBJECT-TYPE Status of the outlet. | 1.3.6.1.4.1.10418.16.2.5.5.1.5 | INTEGER {off(1), on(2)} | read-only | current |
| acsPowerMgmtOutletsTablePowerControl OBJECT-TYPE A set value of power*(2-6) will send command to PDU. noAction(1) = always returned in a GET. Does nothing if SET. powerOn(2) = when SET the power On command is sent to PDU. powerOff(3) = when SET the power Off command is sent to PDU. powerCycle(4)=when SET the power cycle command is sent to PDU. powerLock(5)= when SET the power lock command is sent to PDU. powerUnlock(6)=when SET the power unlock command is sent to PDU. The powerLock and powerUnlock are valid only for Cyclades-PM PDUs | 1.3.6.1.4.1.10418.16.2.5.5.1.6 | INTEGER {noAction(1), powerOn(2), powerOff(3), powerCycle(4), powerLock(5), powerUnlock(6)} | read-write | current |
| acsPowerMgmtOutletsTablePortName OBJECT-TYPE Serial Port Name where the PDU is connected. | 1.3.6.1.4.1.10418.16.2.5.5.1.7 | DisplayString | read-only | current |
| acsPowerMgmtOutletsTablePduId OBJECT-TYPE PDU identification. | 1.3.6.1.4.1.10418.16.2.5.5.1.8 | DisplayString | read-only | current |
| acsPowerMgmtNumberOfOutletGroup OBJECT-TYPE Number of configured group of outlets. | 1.3.6.1.4.1.10418.16.2.5.6 | Integer32 | read-only | current |
| acsPowerMgmtGroupTable OBJECT-TYPE This table contains the information about group of outlets. | 1.3.6.1.4.1.10418.16.2.5.7 | not-accessible | current | |
| acsPowerMgmtGroupTableEntry OBJECT-TYPE each entry has the information about group of outlets. | 1.3.6.1.4.1.10418.16.2.5.7.1 | not-accessible | current | |
| acsPowerMgmtGroupTableIndex OBJECT-TYPE Index of the group. | 1.3.6.1.4.1.10418.16.2.5.7.1.1 | InterfaceIndexOrZero | read-only | current |
| acsPowerMgmtGroupTableName OBJECT-TYPE Name of the group of outlets. | 1.3.6.1.4.1.10418.16.2.5.7.1.2 | DisplayString | read-only | current |
| acsPowerMgmtGroupTableStatus OBJECT-TYPE Status of the group of outlet. | 1.3.6.1.4.1.10418.16.2.5.7.1.3 | INTEGER {off(1), on(2)} | read-only | current |
| acsPowerMgmtGroupTablePowerControl OBJECT-TYPE A set value of power*(2-6) will send command to PDU. noAction(1) = always returned in a GET. Does nothing if SET. powerOn(2) = when SET the power On command is sent to PDU. powerOff(3) = when SET the power Off command is sent to PDU. powerCycle(4)=when SET the power cycle command is sent to PDU. | 1.3.6.1.4.1.10418.16.2.5.7.1.4 | INTEGER {noAction(1), powerOn(2), powerOff(3), powerCycle(4)} | read-write | current |
| acsPowerMgmtPhasesTable OBJECT-TYPE This table contains data monitoring of each detected phase. | 1.3.6.1.4.1.10418.16.2.5.8 | not-accessible | current | |
| acsPowerMgmtPhasesTableEntry OBJECT-TYPE each entry has the data monitoring about phases. | 1.3.6.1.4.1.10418.16.2.5.8.1 | not-accessible | current | |
| acsPowerMgmtPhasesTablePortNumber OBJECT-TYPE Number of serial port when the PDU is connected. | 1.3.6.1.4.1.10418.16.2.5.8.1.1 | InterfaceIndex | read-only | current |
| acsPowerMgmtPhasesTablePduIndex OBJECT-TYPE A PDU position in the chain. | 1.3.6.1.4.1.10418.16.2.5.8.1.2 | InterfaceIndexOrZero | read-only | current |
| acsPowerMgmtPhasesTablePhaseIndex OBJECT-TYPE phase index in the PDU. | 1.3.6.1.4.1.10418.16.2.5.8.1.3 | InterfaceIndexOrZero | read-only | current |
| acsPowerMgmtPhasesTablePhaseName OBJECT-TYPE phase name in the PDU. | 1.3.6.1.4.1.10418.16.2.5.8.1.4 | DisplayString | read-only | current |
| acsPowerMgmtPhasesTablePduId OBJECT-TYPE PDU identification. | 1.3.6.1.4.1.10418.16.2.5.8.1.5 | DisplayString | read-only | current |
| acsPowerMgmtPhasesTablePortName OBJECT-TYPE Name of serial port when the PDU is connected. | 1.3.6.1.4.1.10418.16.2.5.8.1.6 | DisplayString | read-only | current |
| acsPowerMgmtPhasesTableCurrentValue OBJECT-TYPE Actual value of current sensor in this phase.( A x 10 ) | 1.3.6.1.4.1.10418.16.2.5.8.1.7 | Integer32 | read-only | current |
| acsPowerMgmtPhasesTableCurrentMax OBJECT-TYPE Max detected value of current sensor in this phase.( A x 10 ) | 1.3.6.1.4.1.10418.16.2.5.8.1.8 | Integer32 | read-only | current |
| acsPowerMgmtPhasesTableCurrentMin OBJECT-TYPE Min detected value of current sensor in this phase.( A x 10 ) | 1.3.6.1.4.1.10418.16.2.5.8.1.9 | Integer32 | read-only | current |
| acsPowerMgmtPhasesTableCurrentAvg OBJECT-TYPE Average value for current sensor in this phase.( A x 10 ) | 1.3.6.1.4.1.10418.16.2.5.8.1.10 | Integer32 | read-only | current |
| acsPowerMgmtPhasesTableCurrentReset OBJECT-TYPE Reset max, min and avg values of current. | 1.3.6.1.4.1.10418.16.2.5.8.1.11 | INTEGER {no-action(1), reset(2)} | read-write | current |
| acsPowerMgmtPhasesTableVoltageType OBJECT-TYPE Type of voltage values. | 1.3.6.1.4.1.10418.16.2.5.8.1.12 | INTEGER {none-sensor(0), estimated(1), read(2)} | read-only | current |
| acsPowerMgmtPhasesTableVoltageValue OBJECT-TYPE Actual value of voltage sensor in this phase.( V ) | 1.3.6.1.4.1.10418.16.2.5.8.1.13 | Integer32 | read-only | current |
| acsPowerMgmtPhasesTableVoltageMax OBJECT-TYPE Max detected value of voltage sensor in this phase.( V ) | 1.3.6.1.4.1.10418.16.2.5.8.1.14 | Integer32 | read-only | current |
| acsPowerMgmtPhasesTableVoltageMin OBJECT-TYPE Min detected value of voltage sensor in this phase.( V ) | 1.3.6.1.4.1.10418.16.2.5.8.1.15 | Integer32 | read-only | current |
| acsPowerMgmtPhasesTableVoltageAvg OBJECT-TYPE Average value for voltage sensor in this phase.( V ) | 1.3.6.1.4.1.10418.16.2.5.8.1.16 | Integer32 | read-only | current |
| acsPowerMgmtPhasesTableVoltageReset OBJECT-TYPE Reset max, min and avg values of voltage. | 1.3.6.1.4.1.10418.16.2.5.8.1.17 | INTEGER {no-action(1), reset(2)} | read-write | current |
| acsPowerMgmtPhasesTablePowerType OBJECT-TYPE Type of power consumption values. | 1.3.6.1.4.1.10418.16.2.5.8.1.18 | INTEGER {none-sensor(0), estimated(1), read(2)} | read-only | current |
| acsPowerMgmtPhasesTablePowerValue OBJECT-TYPE Actual value of power consumption in this phase.( W x 10 ) | 1.3.6.1.4.1.10418.16.2.5.8.1.19 | Integer32 | read-only | current |
| acsPowerMgmtPhasesTablePowerMax OBJECT-TYPE Max detected value of power consumption in this phase.( W x 10 ) | 1.3.6.1.4.1.10418.16.2.5.8.1.20 | Integer32 | read-only | current |
| acsPowerMgmtPhasesTablePowerMin OBJECT-TYPE Min detected value of power consumption in this phase.( W x 10 ) | 1.3.6.1.4.1.10418.16.2.5.8.1.21 | Integer32 | read-only | current |
| acsPowerMgmtPhasesTablePowerAvg OBJECT-TYPE Average value for power consumption in this phase.( W x 10 ) | 1.3.6.1.4.1.10418.16.2.5.8.1.22 | Integer32 | read-only | current |
| acsPowerMgmtPhasesTablePowerReset OBJECT-TYPE Reset max, min and avg values of power consumption. | 1.3.6.1.4.1.10418.16.2.5.8.1.23 | INTEGER {no-action(1), reset(2)} | read-write | current |
| acsPowerMgmtPhasesTablePowerFactorType OBJECT-TYPE Type of power factor values. | 1.3.6.1.4.1.10418.16.2.5.8.1.24 | INTEGER {none-sensor(0), estimated(1), read(2)} | read-only | current |
| acsPowerMgmtPhasesTablePowerFactorValue OBJECT-TYPE Actual value of power factor in this phase.( PF x 100 ) | 1.3.6.1.4.1.10418.16.2.5.8.1.25 | Integer32 | read-only | current |
| acsPowerMgmtPhasesTablePowerFactorMax OBJECT-TYPE Max detected value of power factor in this phase.( PF x 100 ) | 1.3.6.1.4.1.10418.16.2.5.8.1.26 | Integer32 | read-only | current |
| acsPowerMgmtPhasesTablePowerFactorMin OBJECT-TYPE Min detected value of power factor in this phase.( PF x 100 ) | 1.3.6.1.4.1.10418.16.2.5.8.1.27 | Integer32 | read-only | current |
| acsPowerMgmtPhasesTablePowerFactorAvg OBJECT-TYPE Average value for power factor in this phase.( PF x 100 ) | 1.3.6.1.4.1.10418.16.2.5.8.1.28 | Integer32 | read-only | current |
| acsPowerMgmtPhasesTablePowerFactorReset OBJECT-TYPE Reset max, min and avg values of power factor. | 1.3.6.1.4.1.10418.16.2.5.8.1.29 | INTEGER {no-action(1), reset(2)} | read-write | current |
| acsPowerMgmtPhasesTableAlarm OBJECT-TYPE Show the phase alarm status. | 1.3.6.1.4.1.10418.16.2.5.8.1.30 | INTEGER {normal(1), blow-fuse(2), hw-ocp(3), high-critical(4), high-warning(5), low-warning(6), low-critical(7)} | read-only | current |
| acsPowerMgmtBanksTable OBJECT-TYPE This table contains data monitoring of each detected bank. | 1.3.6.1.4.1.10418.16.2.5.9 | not-accessible | current | |
| acsPowerMgmtBanksTableEntry OBJECT-TYPE each entry has the data monitoring about bank. | 1.3.6.1.4.1.10418.16.2.5.9.1 | not-accessible | current | |
| acsPowerMgmtBanksTablePortNumber OBJECT-TYPE Number of serial port when the PDU is connected. | 1.3.6.1.4.1.10418.16.2.5.9.1.1 | InterfaceIndex | read-only | current |
| acsPowerMgmtBanksTablePduIndex OBJECT-TYPE A PDU position in the chain. | 1.3.6.1.4.1.10418.16.2.5.9.1.2 | InterfaceIndexOrZero | read-only | current |
| acsPowerMgmtBanksTableBankIndex OBJECT-TYPE Bank index in the PDU. | 1.3.6.1.4.1.10418.16.2.5.9.1.3 | InterfaceIndexOrZero | read-only | current |
| acsPowerMgmtBanksTableBankName OBJECT-TYPE Bank name in the PDU. | 1.3.6.1.4.1.10418.16.2.5.9.1.4 | DisplayString | read-only | current |
| acsPowerMgmtBanksTablePduId OBJECT-TYPE PDU identification. | 1.3.6.1.4.1.10418.16.2.5.9.1.5 | DisplayString | read-only | current |
| acsPowerMgmtBanksTablePortName OBJECT-TYPE Name of serial port when the PDU is connected. | 1.3.6.1.4.1.10418.16.2.5.9.1.6 | DisplayString | read-only | current |
| acsPowerMgmtBanksTableCurrentValue OBJECT-TYPE Actual value of current sensor in this bank.( A x 10 ) | 1.3.6.1.4.1.10418.16.2.5.9.1.7 | Integer32 | read-only | current |
| acsPowerMgmtBanksTableCurrentMax OBJECT-TYPE Max detected value of current sensor in this bank.( A x 10 ) | 1.3.6.1.4.1.10418.16.2.5.9.1.8 | Integer32 | read-only | current |
| acsPowerMgmtBanksTableCurrentMin OBJECT-TYPE Min detected value of current sensor in this bank.( A x 10 ) | 1.3.6.1.4.1.10418.16.2.5.9.1.9 | Integer32 | read-only | current |
| acsPowerMgmtBanksTableCurrentAvg OBJECT-TYPE Average value for current sensor in this bank.( A x 10 ) | 1.3.6.1.4.1.10418.16.2.5.9.1.10 | Integer32 | read-only | current |
| acsPowerMgmtBanksTableCurrentReset OBJECT-TYPE Reset max, min and avg values of current. | 1.3.6.1.4.1.10418.16.2.5.9.1.11 | INTEGER {no-action(1), reset(2)} | read-write | current |
| acsPowerMgmtBanksTableVoltageType OBJECT-TYPE Type of voltage values. | 1.3.6.1.4.1.10418.16.2.5.9.1.12 | INTEGER {none-sensor(0), estimated(1), read(2)} | read-only | current |
| acsPowerMgmtBanksTableVoltageValue OBJECT-TYPE Actual value of voltage sensor in this bank.( V ) | 1.3.6.1.4.1.10418.16.2.5.9.1.13 | Integer32 | read-only | current |
| acsPowerMgmtBanksTableVoltageMax OBJECT-TYPE Max detected value of voltage sensor in this bank.( V ) | 1.3.6.1.4.1.10418.16.2.5.9.1.14 | Integer32 | read-only | current |
| acsPowerMgmtBanksTableVoltageMin OBJECT-TYPE Min detected value of voltage sensor in this bank.( V ) | 1.3.6.1.4.1.10418.16.2.5.9.1.15 | Integer32 | read-only | current |
| acsPowerMgmtBanksTableVoltageAvg OBJECT-TYPE Average value for voltage sensor in this bank.( V ) | 1.3.6.1.4.1.10418.16.2.5.9.1.16 | Integer32 | read-only | current |
| acsPowerMgmtBanksTableVoltageReset OBJECT-TYPE Reset max, min and avg values of voltage. | 1.3.6.1.4.1.10418.16.2.5.9.1.17 | INTEGER {no-action(1), reset(2)} | read-write | current |
| acsPowerMgmtBanksTablePowerType OBJECT-TYPE Type of power consumption values. | 1.3.6.1.4.1.10418.16.2.5.9.1.18 | INTEGER {none-sensor(0), estimated(1), read(2)} | read-only | current |
| acsPowerMgmtBanksTablePowerValue OBJECT-TYPE Actual value of power consumption in this bank.( W x 10 ) | 1.3.6.1.4.1.10418.16.2.5.9.1.19 | Integer32 | read-only | current |
| acsPowerMgmtBanksTablePowerMax OBJECT-TYPE Max detected value of power consumption in this bank.( W x 10 ) | 1.3.6.1.4.1.10418.16.2.5.9.1.20 | Integer32 | read-only | current |
| acsPowerMgmtBanksTablePowerMin OBJECT-TYPE Min detected value of power consumption in this bank.( W x 10 ) | 1.3.6.1.4.1.10418.16.2.5.9.1.21 | Integer32 | read-only | current |
| acsPowerMgmtBanksTablePowerAvg OBJECT-TYPE Average value for power consumption in this bank.( W x 10 ) | 1.3.6.1.4.1.10418.16.2.5.9.1.22 | Integer32 | read-only | current |
| acsPowerMgmtBanksTablePowerReset OBJECT-TYPE Reset max, min and avg values of power consumption. | 1.3.6.1.4.1.10418.16.2.5.9.1.23 | INTEGER {no-action(1), reset(2)} | read-write | current |
| acsPowerMgmtBanksTablePowerFactorType OBJECT-TYPE Type of power factor values. | 1.3.6.1.4.1.10418.16.2.5.9.1.24 | INTEGER {none-sensor(0), estimated(1), read(2)} | read-only | current |
| acsPowerMgmtBanksTablePowerFactorValue OBJECT-TYPE Actual value of power factor in this bank.( PF x 100 ) | 1.3.6.1.4.1.10418.16.2.5.9.1.25 | Integer32 | read-only | current |
| acsPowerMgmtBanksTablePowerFactorMax OBJECT-TYPE Max detected value of power factor in this bank.( PF x 100 ) | 1.3.6.1.4.1.10418.16.2.5.9.1.26 | Integer32 | read-only | current |
| acsPowerMgmtBanksTablePowerFactorMin OBJECT-TYPE Min detected value of power factor in this bank.( PF x 100 ) | 1.3.6.1.4.1.10418.16.2.5.9.1.27 | Integer32 | read-only | current |
| acsPowerMgmtBanksTablePowerFactorAvg OBJECT-TYPE Average value for power factor in this bank.( PF x 100 ) | 1.3.6.1.4.1.10418.16.2.5.9.1.28 | Integer32 | read-only | current |
| acsPowerMgmtBanksTablePowerFactorReset OBJECT-TYPE Reset max, min and avg values of power factor. | 1.3.6.1.4.1.10418.16.2.5.9.1.29 | INTEGER {no-action(1), reset(2)} | read-write | current |
| acsPowerMgmtBanksTableAlarm OBJECT-TYPE Show the bank alarm status. | 1.3.6.1.4.1.10418.16.2.5.9.1.30 | INTEGER {normal(1), blow-fuse(2), hw-ocp(3), high-critical(4), high-warning(5), low-warning(6), low-critical(7)} | read-only | current |
| acsPowerMgmtEnvMonTable OBJECT-TYPE This table contains data monitoring of each detected environmental sensor. | 1.3.6.1.4.1.10418.16.2.5.10 | not-accessible | current | |
| acsPowerMgmtEnvMonTableEntry OBJECT-TYPE each entry has the data monitoring about environmental sensors. | 1.3.6.1.4.1.10418.16.2.5.10.1 | not-accessible | current | |
| acsPowerMgmtEnvMonTablePortNumber OBJECT-TYPE Number of serial port when the PDU is connected. | 1.3.6.1.4.1.10418.16.2.5.10.1.1 | InterfaceIndex | read-only | current |
| acsPowerMgmtEnvMonTablePduIndex OBJECT-TYPE A PDU position in the chain. | 1.3.6.1.4.1.10418.16.2.5.10.1.2 | InterfaceIndexOrZero | read-only | current |
| acsPowerMgmtEnvMonTableIndex OBJECT-TYPE envmon sensor index. | 1.3.6.1.4.1.10418.16.2.5.10.1.3 | InterfaceIndexOrZero | read-only | current |
| acsPowerMgmtEnvMonTableName OBJECT-TYPE envmon sensor name. | 1.3.6.1.4.1.10418.16.2.5.10.1.4 | DisplayString | read-only | current |
| acsPowerMgmtEnvMonTablePduId OBJECT-TYPE PDU identification. | 1.3.6.1.4.1.10418.16.2.5.10.1.5 | DisplayString | read-only | current |
| acsPowerMgmtEnvMonTablePortName OBJECT-TYPE Name of serial port when the PDU is connected. | 1.3.6.1.4.1.10418.16.2.5.10.1.6 | DisplayString | read-only | current |
| acsPowerMgmtEnvMonTableType OBJECT-TYPE The type of environmental monitor. | 1.3.6.1.4.1.10418.16.2.5.10.1.7 | INTEGER {temp-internal(1), temperature(2), humidity(3), air-flow(4), smoke(5), dry-concact(6), water-level(7), motion(8), unplugged(9), unknown(10)} | read-only | current |
| acsPowerMgmtEnvMonTableStatus OBJECT-TYPE Status of digital sensors: Dry-Contact, Water level, Smoke sensor, Motion sensor. | 1.3.6.1.4.1.10418.16.2.5.10.1.8 | INTEGER {normal(1), triggered(2), not-applicable(3)} | read-only | current |
| acsPowerMgmtEnvMonTableValue OBJECT-TYPE Detected value for envmon sensors. Temperature: C x 10. Humidity: %. Air flow: afu. | 1.3.6.1.4.1.10418.16.2.5.10.1.9 | Integer32 | read-only | current |
| acsPowerMgmtEnvMonTableMaxValue OBJECT-TYPE Max detected value for envmon sensors. Temperature: C x 10. Humidity: %. Air flow: afu. | 1.3.6.1.4.1.10418.16.2.5.10.1.10 | Integer32 | read-only | current |
| acsPowerMgmtOutElecMonTable OBJECT-TYPE This table contains the information about data monitoring of outlets. | 1.3.6.1.4.1.10418.16.2.5.11 | not-accessible | current | |
| acsPowerMgmtOutElecMonTableEntry OBJECT-TYPE each entry has the information about the outlet. | 1.3.6.1.4.1.10418.16.2.5.11.1 | not-accessible | current | |
| acsPowerMgmtOutElecMonTablePortNumber OBJECT-TYPE Serial Port number. | 1.3.6.1.4.1.10418.16.2.5.11.1.1 | InterfaceIndex | read-only | current |
| acsPowerMgmtOutElecMonTablePduNumber OBJECT-TYPE Index. | 1.3.6.1.4.1.10418.16.2.5.11.1.2 | InterfaceIndex | read-only | current |
| acsPowerMgmtOutElecMonTableNumber OBJECT-TYPE Number of the outlet in the PDU. | 1.3.6.1.4.1.10418.16.2.5.11.1.3 | InterfaceIndex | read-only | current |
| acsPowerMgmtOutElecMonTableCurrentValue OBJECT-TYPE Actual value of outlet current sensor.( A x 10 ) | 1.3.6.1.4.1.10418.16.2.5.11.1.4 | Integer32 | read-only | current |
| acsPowerMgmtOutElecMonTableCurrentMax OBJECT-TYPE Max detected value of outlet current sensor.( A x 10 ) | 1.3.6.1.4.1.10418.16.2.5.11.1.5 | Integer32 | read-only | current |
| acsPowerMgmtOutElecMonTableCurrentMin OBJECT-TYPE Min detected value of outlet current sensor.( A x 10 ) | 1.3.6.1.4.1.10418.16.2.5.11.1.6 | Integer32 | read-only | current |
| acsPowerMgmtOutElecMonTableCurrentAvg OBJECT-TYPE Average value for outlet current sensor.( A x 10 ) | 1.3.6.1.4.1.10418.16.2.5.11.1.7 | Integer32 | read-only | current |
| acsPowerMgmtOutElecMonTableCurrentReset OBJECT-TYPE Reset max, min and avertage values of outlet current. | 1.3.6.1.4.1.10418.16.2.5.11.1.8 | INTEGER {noAction(1), reset(2)} | read-write | current |
| acsPowerMgmtOutElecMonTablePowerValue OBJECT-TYPE Actual value of outlet power comsumption sensor.( W x 10 ) | 1.3.6.1.4.1.10418.16.2.5.11.1.9 | Integer32 | read-only | current |
| acsPowerMgmtOutElecMonTablePowerMax OBJECT-TYPE Max detected value of outlet power comsumption sensor.( W x 10 ) | 1.3.6.1.4.1.10418.16.2.5.11.1.10 | Integer32 | read-only | current |
| acsPowerMgmtOutElecMonTablePowerMin OBJECT-TYPE Min detected value of outlet power comsumption sensor.( W x 10 ) | 1.3.6.1.4.1.10418.16.2.5.11.1.11 | Integer32 | read-only | current |
| acsPowerMgmtOutElecMonTablePowerAvg OBJECT-TYPE Average value for outlet power comsumption sensor.( W x 10 ) | 1.3.6.1.4.1.10418.16.2.5.11.1.12 | Integer32 | read-only | current |
| acsPowerMgmtOutElecMonTablePowerReset OBJECT-TYPE Reset max, min and avertage values of outlet power comsumption. | 1.3.6.1.4.1.10418.16.2.5.11.1.13 | INTEGER {noAction(1), reset(2)} | read-write | current |
| acsPowerMgmtOutElecMonTableVoltageValue OBJECT-TYPE Actual value of outlet voltage sensor.( V ) | 1.3.6.1.4.1.10418.16.2.5.11.1.14 | Integer32 | read-only | current |
| acsPowerMgmtOutElecMonTableVoltageMax OBJECT-TYPE Max detected value of outlet voltage sensor.( V ) | 1.3.6.1.4.1.10418.16.2.5.11.1.15 | Integer32 | read-only | current |
| acsPowerMgmtOutElecMonTableVoltageMin OBJECT-TYPE Min detected value of outlet voltage sensor.( V ) | 1.3.6.1.4.1.10418.16.2.5.11.1.16 | Integer32 | read-only | current |
| acsPowerMgmtOutElecMonTableVoltageAvg OBJECT-TYPE Average value for outlet voltage sensor.( V ) | 1.3.6.1.4.1.10418.16.2.5.11.1.17 | Integer32 | read-only | current |
| acsPowerMgmtOutElecMonTableVoltageReset OBJECT-TYPE Reset max, min and avertage values of outlet voltage. | 1.3.6.1.4.1.10418.16.2.5.11.1.18 | INTEGER {noAction(1), reset(2)} | read-write | current |
| acsPowerMgmtOutElecMonTablePowerFactorValue OBJECT-TYPE Actual value of outlet power-factor sensor.( PF x 100 ) | 1.3.6.1.4.1.10418.16.2.5.11.1.19 | Integer32 | read-only | current |
| acsPowerMgmtOutElecMonTablePowerFactorMax OBJECT-TYPE Max detected value of outlet power-factor sensor.( PF x 100 ) | 1.3.6.1.4.1.10418.16.2.5.11.1.20 | Integer32 | read-only | current |
| acsPowerMgmtOutElecMonTablePowerFactorMin OBJECT-TYPE Min detected value of outlet power-factor sensor.( PF x 100 ) | 1.3.6.1.4.1.10418.16.2.5.11.1.21 | Integer32 | read-only | current |
| acsPowerMgmtOutElecMonTablePowerFactorAvg OBJECT-TYPE Average value for outlet power-factor sensor.( PF x 100 ) | 1.3.6.1.4.1.10418.16.2.5.11.1.22 | Integer32 | read-only | current |
| acsPowerMgmtOutElecMonTablePowerFactorReset OBJECT-TYPE Reset max, min and avertage values of outlet power-factor. | 1.3.6.1.4.1.10418.16.2.5.11.1.23 | INTEGER {noAction(1), reset(2)} | read-write | current |
| acsPowerMgmtOutElecMonTableAlarm OBJECT-TYPE Show the outlet alarm status. | 1.3.6.1.4.1.10418.16.2.5.11.1.24 | INTEGER {normal(1), blow-fuse(2), hw-ocp(3), high-critical(4), high-warning(5), low-warning(6), low-critical(7)} | read-only | current |
| acsTrapObject OBJECT-IDENTITY | 1.3.6.1.4.1.10418.16.2.6 |